[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-034","fire-107-1-water-chemical-034",107,1,34,"依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"FE-13 應在 30 秒以內","IG-541 應在 60 秒以內","Halon 1301 應在 60 秒以內","FM-200 應在 30 秒以內","B",null,[],false,"本題考點：NFPA 2001 對潔淨氣體滅火系統「達設計濃度百分之九十五所需放射時間」的規定，鹵化烴類與惰性氣體類兩者時間不同。\n【正解理由】依 NFPA 2001 之規定，一般場所的藥劑放射時間以達到設計濃度百分之九十五為量測終點：鹵化烴類藥劑以液態高壓儲存，放射時迅速汽化、瞬間流量大，要求在十秒以內放射完畢；惰性氣體類藥劑以氣態高壓儲存，注入體積龐大且會使防護區域壓力急遽上升，須以較長時間釋放以免破壞區劃，故放寬為六十秒以內。IG-541 屬惰性氣體類，故選 B。\n【逐項排除】\n(A) FE-13 化學名為三氟甲烷，屬鹵化烴類藥劑，應在十秒以內，並非三十秒。\n(B) IG-541 為氮氣、氬氣與二氧化碳之混合惰性氣體，適用六十秒以內之規定，敘述正確。\n(C) Halon 1301 為海龍藥劑，其系統設計係另循 NFPA 12A，NFPA 2001 本即為海龍替代藥劑而訂，且其放射時間要求亦非六十秒。\n(D) FM-200 化學名為七氟丙烷，同屬鹵化烴類藥劑，應在十秒以內，並非三十秒。\n【記憶點】化學藥劑十秒、惰性氣體六十秒；三十秒是命題者虛設的中間值。","NFPA 2001《潔淨藥劑滅火系統標準》是蒙特婁議定書逐步禁止海龍生產之後，為海龍替代藥劑量身訂定的規範，一九九○年代中期首度發布，並隨新藥劑上市持續修訂。它把潔淨藥劑分成兩大陣營：鹵化烴類（halocarbon，如 HFC-227ea 的 FM-200、HFC-23 的 FE-13、FK-5-1-12）與惰性氣體類（inert gas，如 IG-100、IG-01、IG-55、IG-541）。\n兩類的放射時間之所以相差六倍，根源在儲存狀態與滅火機制。鹵化烴以液態高壓充填，放射時瞬間汽化，單位時間可送出的質量極大；其滅火主要靠汽化吸熱降低火焰溫度並兼有化學抑制，唯有快速建立濃度才能在火勢成長前壓制，故要求十秒以內達設計濃度的百分之九十五。惰性氣體以高壓氣態儲存，滅火機制是稀釋氧氣使燃燒無法維持，所需注入的氣體體積遠大於鹵化烴；若同樣在十秒內灌入，防護區域的壓力峰值足以掀開天花板或吹壞輕隔間，故放寬至六十秒，並須配合洩壓口設計。\n另一組常考數值是浸潤時間：藥劑放射完畢後，設計濃度須在防護區域內維持一定時間（一般要求十分鐘），以避免深層悶燒復燃。此外 IG-541 之所以含約百分之八的二氧化碳，是利用二氧化碳刺激呼吸中樞的生理作用，使人員在氧濃度降低的環境中仍能維持換氣。延伸考點常把兩類藥劑的時間對調，或把海龍系統誤植為 NFPA 2001 的適用對象。\n應試時的操作要領很單純：看到選項先把藥劑代號歸類，凡是以 IG 開頭者一律屬惰性氣體類、對應六十秒；凡是 FM、FE、HFC、FK 開頭者屬鹵化烴類、對應十秒；Halon 開頭者根本不在 NFPA 2001 的射程之內。代號歸類正確，這一類題就解掉大半。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-033","自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-032","泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-036","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-037","有關撒水頭設置之敘述，下列何者正確？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-034",111,"第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-034",110,"依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-034",109,"乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-034",108,"依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-034",106,"第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",1785123168101]