[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-107-1-water-chemical-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-107-1-水與化學系統消防安全設備概要-036","fire-107-1-water-chemical-036",107,1,36,"有關自動撒水設備末端查驗閥之敘述，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"開放式自動撒水設備應設置","限流孔之放水性能應與標準撒水頭相同","管徑小於 25 公厘","配置距離地板面之高度在 3 公尺以下","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第五十六條末端查驗閥的四項要件——適用設備、管徑、限流孔性能與裝設高度。\n【正解理由】第五十六條第三款明定，查驗閥之一次側設壓力表，二次側設有「與撒水頭同等放水性能之限流孔」。限流孔的作用，是在不使現場真正放水的情形下模擬一顆撒水頭開啟時的放水量與壓力，藉以驗證流水檢知裝置與加壓送水裝置能否確實動作，故 (B) 之敘述與條文相符，故選 B。\n【逐項排除】\n(A) 錯誤：第五十六條適用對象為「使用密閉式撒水頭之自動撒水設備」；開放式自動撒水設備依第五十三條第二款，是在一齊開放閥二次側配管裝設試驗用裝置，於該放水區域不放水的情形下測試閥的動作。\n(B) 正確：如前所述，二次側之限流孔須具與撒水頭同等之放水性能。\n(C) 錯誤：第五十六條第一款為「管徑在二十五毫米以上」，屬下限規定，題目寫成小於二十五公厘，方向正好相反。\n(D) 錯誤：同條第四款為距離地板面之高度在二點一公尺以下，並附有排水管裝置且標明末端查驗閥字樣，非三公尺以下。\n【記憶點】密閉式才設末端查驗閥：管徑二十五以上、高度二點一以下、限流孔比照撒水頭。","末端查驗閥的裝設位置藏著整套設計思想。第五十六條第二款要求查驗閥依各流水檢知裝置配管系統配置，並接裝在建築物各層「放水壓力最低之最遠支管末端」，也就是全系統的最不利點。最不利點若能達到規定的放水壓力與放水量，其餘位置自然更沒問題，這是以最嚴苛條件反證全系統合格的典型手法。一次側壓力表讀取的是流水檢知裝置二次側的壓力，二次側限流孔則把放水行為標準化，使每次查驗的條件一致、可以逐年比較。\n開放式自動撒水設備走的是另一套邏輯。它的撒水頭本身沒有感熱元件、平時管內無水，配管末端無壓可查，因此驗證重心落在一齊開放閥：依第五十三條，每一放水區域設置一個一齊開放閥，並在其二次側配管裝設試驗用裝置，使該放水區域在不放水的情形下也能測試一齊開放閥動作，且一齊開放閥所承受之壓力應在其最高使用壓力以下；啟動端則依第五十二條設自動與手動啟動裝置，放水區域依第五十四條每一舞臺在四個以下。\n對密閉乾式管系而言，末端查驗閥還兼負驗證第五十五條「撒水頭動作後，流水檢知裝置應在一分鐘內使撒水頭放水」的功能，因為乾式系統多了排除二次側空氣的時間差。此外，公共危險物品等場所設置之自動撒水設備，依第二百十一條第一款，末端查驗閥同樣準用第五十六條規定，並非另有一套標準。\n另一個常考的細節是查驗閥與流水檢知裝置的對應關係：查驗閥係依「各流水檢知裝置配管系統」逐一配置，一個系統對應一個查驗閥，既不是一棟建築物只設一個，也不是每層樓一律設一個，配置題與數量計算題都會從這裡切入。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-107-1-water-chemical-037","有關撒水頭設置之敘述，下列何者正確？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-107-1-water-chemical-034","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-107-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何種場所不需設置室外消防栓設備？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-107-1-water-chemical-033","自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-036",111,"二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-036",110,"依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-036",109,"任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",{"webId":66,"year":67,"stem":68,"number":13},"fire-108-1-water-chemical-036",108,"依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-036",106,"低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",1785123168120]