[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-108-1-警報與避難系統消防安全設備概要-001","fire-108-1-alarm-evacuation-001",108,1,"某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",{"A":15,"B":16,"C":17,"D":18},"一齊鳴動","地下層各層及 1 樓鳴動","地下層各層、1 樓及 2 樓鳴動","地下層 1 層、1 樓及 2 樓鳴動","C",null,[],false,"本題考點：火警自動警報設備分區鳴動的適用門檻,以及起火層為地面層時的鳴動範圍。\n【正解理由】依《各類場所消防安全設備設置標準》第一百十三條,火警自動警報設備之鳴動方式,建築物在五樓以上且總樓地板面積在三千平方公尺以上者,依該條各款分區鳴動。本例地上六層加地下二層共八個樓層,每層四百平方公尺,總樓地板面積三千二百平方公尺,已同時滿足五樓以上與三千平方公尺以上;該條第二款明定「起火層為地面層時,限該樓層與其直上層及地下層各層鳴動」,一樓即地面層,鳴動範圍為一樓、二樓及地下層各層,故選 C。\n【逐項排除】\n(A) 一齊鳴動:是未達第一百十三條所定樓層與面積門檻的建築物才適用的方式,本例已達門檻,應採分區鳴動。\n(B) 地下層各層及 1 樓鳴動:漏掉第二款明列的「直上層」二樓,鳴動範圍不足。\n(C) 地下層各層、1 樓及 2 樓鳴動:與第二款文字完全相符,為正確答案。\n(D) 地下層 1 層、1 樓及 2 樓鳴動:條文寫的是「地下層各層」,地下二層亦須鳴動,只鳴動地下一層並不符合;「直下一層」是起火層在地上二層以上時第一款才有的概念。\n【記憶點】地面層起火:本層加直上一層,地下層全部一起鳴。","第一百十三條三款要一起背:起火層為地上二層以上時,限該樓層與其直上二層及其直下層鳴動;起火層為地面層時,限該樓層與其直上層及地下層各層鳴動;起火層為地下層時,限地面層及地下層各層鳴動。三款共同的邏輯是煙與熱往上蔓延,而地下層缺乏水平避難路徑、煙一旦竄入樓梯間即難以逃生,因此地面層與地下層起火時一律讓地下各層同時警報,先讓最危險的人離開。若全棟一齊鳴動,樓梯間會同時湧入大量人流,反而延誤真正受威脅樓層的避難,分區鳴動就是為了控制避難流量而設。\n《消防安全設備及必要檢修項目檢修基準》火警自動警報設備性能檢查的音響裝置項目,對分區鳴動的敘述與上述三款一致,並補充分區鳴動必要時可以手動操作一齊鳴動;音壓與音色的判定則是設於有其他機械噪音之處所者,應與噪音有明顯區別且清晰。緊急廣播設備章的揚聲器鳴動方式採同一套分區邏輯,並多一項相互鳴動:設有二台以上操作裝置或遠隔操作裝置之建築物,由任一操作裝置或遠隔操作裝置均能使揚聲器鳴動。\n本題型常與火警分區合併命題。第一百十二條規定每一火警分區不得超過一樓層,且樓地板面積在六百平方公尺以下,但上下二層樓地板面積之和在五百平方公尺以下者得二層共用一分區;每一分區任一邊長在五十公尺以下,裝設光電式分離型探測器時得放寬為一百公尺以下;如由主要出入口或直通樓梯出入口能直接觀察該樓層任一角落時,六百平方公尺得增為一千平方公尺;樓梯或斜坡通道垂直距離每四十五公尺以下為一火警分區,且地下層部分應為另一火警分區。本例每層四百平方公尺,單層即成一個火警分區。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-107-1-alarm-evacuation-040","依各類場所消防安全設備檢修及申報作業基準規定，緩降機應以測量下降距離及下降時間，計算出下降速度，最大下降速度應在每秒多少公分以內？",40,107,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-002","特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-107-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，緊急廣播設備之啟動裝置應符合 CNS 10522 之規定，且設在距樓地板高度 X 公尺以上 Y 公尺以下範圍內，下列何者正確？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-003","用途為補習班，居室樓地板面積 300 平方公尺，採用有效通風方式檢討，其排煙口設於天花板下方 80 公分內，試問有效通風面積最少須要多少平方公尺以上方可符合規定？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-107-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，差動式分布型及偵煙式探測器之探測區域，指探測器裝置面之四周以淨高多少公分以上之樑或類似構造體區劃包圍者？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-004","某一防火構造建築物，地上 5 層且為無開口樓層，1 至 2 層供辦公室用途使用，3 至 5 層供餐廳用途使用，各樓層樓地板面積皆為 200 平方公尺，依照各類場所消防安全設備設置標準之規定，請問本場所火警自動警報設備之設置情形，下列何者正確？",4,[53,57,61,65,68],{"webId":54,"year":55,"stem":56,"number":12},"fire-111-1-alarm-evacuation-001",111,"依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":58,"year":59,"stem":60,"number":12},"fire-110-1-alarm-evacuation-001",110,"下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":62,"year":63,"stem":64,"number":12},"fire-109-1-alarm-evacuation-001",109,"常開式之火警探測器信號回路，加設終端電阻之目的為何？",{"webId":66,"year":31,"stem":67,"number":12},"fire-107-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，除供甲類場所、地下建築物、高層建築物或應設置偵煙式探測器之場所外，若要以自動撒水設備免設火警自動警報設備，有關密閉型撒水頭之規定，下列那一項正確？",{"webId":69,"year":70,"stem":71,"number":12},"fire-106-1-alarm-evacuation-001",106,"某一 KTV 視聽歌唱場所設於大樓地下層，依規定樓地板面積如合計超過多少，應設置瓦斯漏氣火警自動警報設備？",1785123171725]