[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-002","fire-108-1-alarm-evacuation-002",108,1,2,"特別安全梯的安全梯與緊急昇降機兼用時，其排煙機、進風機之排煙量、進風量須在每秒多少立方公尺以上？",{"A":16,"B":17,"C":18,"D":19},"6","4","360","240","A",null,[],false,"本題考點：特別安全梯或緊急昇降機間排煙室採排煙、進風風管時,兼用情形的排煙量與進風量。\n【正解理由】依《各類場所消防安全設備設置標準》第一百八十九條第二款,排煙室設置排煙、進風風管時,其第四目明定「排煙機、進風機之排煙量、進風量在每秒四立方公尺(兼用時,每秒六立方公尺)以上,且可隨排煙口、進風口開啟而自動啟動」。題幹為特別安全梯排煙室與緊急昇降機間兼用,應適用括號內的兼用值每秒六立方公尺,故選 A。\n【逐項排除】\n(A) 6:即每秒六立方公尺,與第四目括號內兼用時的下限相符,為正確答案。\n(B) 4:是排煙室單獨設置、未與緊急昇降機間兼用時的數值,本題已言明兼用,不能用此值。\n(C) 360:是把每秒六立方公尺乘以六十換算成每分鐘的數字,題目問的單位是每秒,量值來源對而單位不合。\n(D) 240:同時取了非兼用的四立方公尺又換算成每分鐘,場所條件與單位都不對。\n【記憶點】排煙室風量每秒四,兼用加二變六。","第一百八十九條給了兩條路:設直接面向戶外的窗戶,或設排煙、進風風管。走窗戶者,窗戶與煙接觸部分應使用不燃材料,有效開口面積須位於天花板高度二分之一以上之範圍內,面積在二平方公尺以上,兼用時提高為三平方公尺以上;平時關閉的窗戶應設手動開關裝置,操作部設於距離樓地板面八十公分以上一百五十公分以下之牆面,並標示簡易之操作方式。走風管者,排煙口、排煙風管、進風口、進風風管及其他與煙接觸部分應使用不燃材料;風管貫穿防火區劃時應在貫穿處設防火閘門,該風管與貫穿部位合成之構造應具所貫穿構造之防火時效,跨樓層設置時立管應置於防火區劃之管道間。排煙口位於天花板高度二分之一以上之範圍內並與連通戶外之排煙風管、排煙機連接;進風口位於天花板高度二分之一以下之範圍內,直接面向戶外者開口面積在一平方公尺以上,兼用時為一點五平方公尺以上。\n兼用一律加成是本條最好用的記憶線:窗戶有效開口面積二平方公尺變三平方公尺,進風口一平方公尺變一點五平方公尺,風量每秒四立方公尺變六立方公尺,理由是兼用時同一個排煙室要同時服務兩條垂直動線,需處理的煙量與進風需求都變大。另外進風口、排煙口除手動開關裝置外還要設探測器連動的自動開關裝置,平時保持關閉,開口葉片之構造應不受開啟時所生氣流之影響而關閉;排煙口、進風口、排煙機及進風機均應連接緊急電源,供電容量應供其有效動作三十分鐘以上。\n上位規定則在第二十八條第五款:依建築技術規則應設置之特別安全梯或緊急昇降機間應設置排煙設備;第十一條把排煙設備(含緊急昇降機間、特別安全梯間排煙設備、室內排煙設備)列為消防搶救上之必要設備;第四十九條並把室內安全梯間、特別安全梯間或緊急昇降機間之排煙室列為得免裝撒水頭的處所,三條合起來就是排煙室的完整考點鏈。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-108-1-alarm-evacuation-001","某一新建建築物地面六層、地下二層，用途為辦公室，每層樓地板面積為 400 平方公尺，設置火警自動警報系統，假設 1 樓發生火警時，依各類場所消防安全設備設置標準規定，其鳴動方式為何？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-108-1-alarm-evacuation-003","用途為補習班，居室樓地板面積 300 平方公尺，採用有效通風方式檢討，其排煙口設於天花板下方 80 公分內，試問有效通風面積最少須要多少平方公尺以上方可符合規定？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-107-1-alarm-evacuation-040","依各類場所消防安全設備檢修及申報作業基準規定，緩降機應以測量下降距離及下降時間，計算出下降速度，最大下降速度應在每秒多少公分以內？",40,107,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-004","某一防火構造建築物，地上 5 層且為無開口樓層，1 至 2 層供辦公室用途使用，3 至 5 層供餐廳用途使用，各樓層樓地板面積皆為 200 平方公尺，依照各類場所消防安全設備設置標準之規定，請問本場所火警自動警報設備之設置情形，下列何者正確？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-107-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，緊急廣播設備之啟動裝置應符合 CNS 10522 之規定，且設在距樓地板高度 X 公尺以上 Y 公尺以下範圍內，下列何者正確？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-005","瓦斯漏氣火警自動警報設備進行性能檢查，下列敘述何者正確？",5,[53,57,61,64],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-002",110,"某樓高 12 層觀光旅館於最高樓層開設之餐廳，依各類場所消防安全設備設置標準之規定，其位於同樓層的廚房無須設置下列何種裝置？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-002",109,"使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",{"webId":62,"year":39,"stem":63,"number":13},"fire-107-1-alarm-evacuation-002","差動式分布型探測器為熱半導體式時，裝接於一個檢出器之感熱器數量，下列何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-002",106,"對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",1785123171741]