[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-013":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-013","fire-108-1-alarm-evacuation-013",108,1,13,"有關避難器具之外觀試驗，下列何者不屬於外觀試驗？",{"A":16,"B":17,"C":18,"D":19},"裝置器具檢查","固定部材料檢查","構造、性能檢查","拉拔強度試驗","D",null,[],false,"本題考點：避難器具查驗中「外觀試驗」與「性能試驗」的分野，判準在於該項目是否須對構件施加荷重並量測其強度，屬分類辨識題。\n【正解理由】外觀試驗係以目視、尺量或簡易操作，確認器具本體、裝置器具與固定部之材料規格、設置狀況、標示及有無變形損傷等可自外部辨識之事項；拉拔強度試驗則須以試驗機具對錨定螺栓或固定部施加規定拉力，量測其抗拉能力是否達到要求，屬對強度之實測，無法僅憑外觀判定，應歸入性能層次，故選 D。\n【逐項排除】\n(A) 裝置器具檢查係確認支固器具、入口零件等有無變形、龜裂、腐蝕、損傷及安裝是否確實，以目視即可完成，不需藉助量測儀器，屬外觀試驗。\n(B) 固定部材料檢查係核對固定架與螺栓螺帽之材質規格及耐腐蝕加工，並確認固定基礎有無龜裂破損，同屬自外部辨識之事項，性質上是規格核對。\n(C) 構造、性能檢查在此指以目視及簡易操作確認構造是否符合規定、轉動或折疊部之動作是否順暢，並未對構件施加荷重，其重點在動作是否順暢，仍列為外觀試驗。\n(D) 拉拔強度試驗須施力量測固定部之抗拉強度，屬性能層次之實測項目，不屬外觀試驗，為本題應選者。\n【記憶點】看得出來的歸外觀，要出力量測的歸性能。","避難器具的查核可分兩個時點：竣工時的查驗，與使用中的定期檢修。竣工查驗依內政部函頒之審查及查驗作業基準，體例上先做外觀試驗、再做性能試驗，前者確認「東西對不對、裝得對不對」，後者確認「拉得動、撐得住」。定期檢修則依《消防安全設備及必要檢修項目檢修基準》避難器具一章，分外觀檢查、性能檢查與綜合檢查三階段，其中綜合檢查明定係在完成外觀檢查及性能檢查之後實施，檢查時應使避難器具成使用狀態，確認其性能是否正常。兩套體例的共同邏輯是由外而內、由靜態到動態、由不施力到施力。\n從檢修基準的內容更能看出分界落在何處。性能檢查中，救助袋之支固器具及入口零件係以目視、操作及扭力扳手確認，判定事項包含支固器具應無變形、龜裂、腐蝕及損傷，螺栓、螺帽等固定零件應無龜裂、損傷、鬆動或脫落，固定部應無腐蝕、生鏽、變形、龜裂等對強度有影響之異常，固定基礎應無因龜裂而引起之破損，且穿孔錨栓工法之錨栓所使用螺帽之栓緊應符合表列栓緊轉矩；緩降機一節同樣要求固定部以目視及扭力扳手確認。可見凡是需要拿工具施力量測的事項，即使量的是轉矩而非拉力，也都被歸在性能層次，而不是單純的外觀。\n考試上要抓住三個對比。其一，外觀憑感官判斷，性能憑儀器讀值；其二，外觀不改變受檢物的受力狀態，性能與強度試驗則主動對受檢物施加作用；其三，避難器具因人命直接懸掛其上，固定部的強度是最後一道防線，因此設置端於《各類場所消防安全設備設置標準》第 174 條以埋入深度與轉矩值加以量化，檢修端以扭力扳手覆核栓緊狀態，竣工端再以拉拔強度試驗實測抗拉能力，三者其實是同一件事的三道關卡。遇到這類分類題，只要自問一句：這個項目用眼睛看得完嗎？看得完的就是外觀試驗。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-012","有關依各類場所消防安全設備設置標準規定設置之耐燃保護、耐熱保護措施，室內消防栓、室外消防栓、自動撒水、水霧、泡沫、乾粉、二氧化碳滅火設備、連結送水管設備等之配管，於實施施工、加壓試驗及配合建築物樓地板、樑、柱、牆施工須預埋消防管線時，消防專技人員何人應一併拍照建檔存證以供消防機關查核，消防機關並得視需要隨時派員前往查驗？",12,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-014","緊急照明設備性能試驗之水平面照度測試，切換為緊急電源狀態亮燈，經過 A 分鐘後，使用 B 測試，確認緊急照明燈之照度有無達到法規所規定之值。請問前述 A、B 為何？",14,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-011","為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",11,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-015","依建築技術規則對緊急用昇降機之相關規定，下列何者正確？",15,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-010","某一廣播區域面積為 150 平方公尺，設有揚聲器，請問距所設揚聲器 1 m 處所測得之音壓須達多少以上才符合規定？",10,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-016","依照各類場所消防安全設備檢修及申報作業基準之規定，某燃燒器具的瓦斯，對空氣比重大於 1 時，其檢知器應設於距瓦斯燃燒器具或瓦斯導管貫穿牆壁處水平距離 A 公尺以內；檢知器上端，應裝設在距樓地板面 B 公分範圍內。請問前述 A、B 為何？",16,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-013",110,"容易受風影響之場所（如大廳、禮拜堂、大樓頂上之機械室等），依消防安全設備及必要檢修項目檢修基準之規定，可在下列何種探測器中進行選設？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-013",109,"無線電通信輔助設備設置之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-013",107,"依各類場所消防安全設備設置標準規定，火警自動警報設備之配線，除依屋內線路裝置規則外，其電源回路導線間及導線與大地間之絕緣電阻值，以直流 250 伏特額定之絕緣電阻計測定，對地電壓在 150 伏特以下者，應該在多少 MΩ 以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-013",106,"集合住宅計算收容人數以設置避難器具時，每戶收容人數以多少人計算？",1785123171857]