[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-024","fire-108-1-alarm-evacuation-024",108,1,24,"某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",{"A":16,"B":17,"C":18,"D":19},"差動式局限型探測器 1 種","定溫式局限型探測器 1 種","火焰式局限型探測器 1 種","偵煙式局限型探測器 1 種","B",null,[],false,"本題考點：探測器之適應性。三溫暖洗澡區屬水蒸氣會大量滯留之場所，選型受《各類場所消防安全設備設置標準》第 117 條拘束，而非受高度限制。\n【正解理由】裝置面高度 3.6 公尺依第 114 條落在「未滿四公尺」欄，各式探測器均在列，高度不是篩選點；篩選點在第 117 條：第一項第一款明定偵煙式或熱煙複合式局限型不得設於「塵埃、粉末或水蒸氣會大量滯留之場所」，第二項第二款明定火焰式不得設於「水蒸氣會大量滯留之處所」，同條第三項附表於該欄亦未將差動式局限型列為適用。洗澡區蒸氣長時間滯留、室溫緩慢上升，四選項中僅定溫式局限型未被排除，它以標稱動作溫度動作，故選 B。\n【逐項排除】\n(A) 差動式局限型 1 種：以溫升速率動作，第 117 條附表在水蒸氣欄未將其列為適用（該欄僅差動式分布型二種獲標記）。\n(B) 定溫式局限型 1 種：未被第 117 條排除；依第 120 條，防火構造建築物、高度未滿四公尺時其一種有效探測範圍 60 平方公尺，130 平方公尺設 3 個即可涵蓋，為本題應選者。\n(C) 火焰式局限型 1 種：第 117 條第二項第二款明文將「水蒸氣會大量滯留之處所」列為火焰式不得設置之處所。\n(D) 偵煙式局限型 1 種：第 117 條第一項第一款明文排除，水蒸氣粒子會被誤判為煙而誤報。\n【記憶點】三溫暖看蒸氣不看高度：偵煙式、火焰式出局，差動式局限型也不適用，定溫式才對。","《設置標準》對探測器選型採三層過濾：先看第 114 條的裝置場所高度表決定可用種類，再看第 117 條的場所環境排除不適用者，最後用第 120 條以下的有效探測範圍表算出應設數量。本題三溫暖屬第 12 條第一款第七目「三溫暖、公共浴室」之甲類場所，過濾點落在第二層。\n第 117 條的結構值得整條記：第一項列偵煙式或熱煙複合式局限型不得設置之八種處所——塵埃粉末或水蒸氣大量滯留、散發腐蝕性氣體、廚房及平時煙會滯留、顯著高溫、排放廢氣大量滯留、煙會大量流入、會結露、其他造成機能障礙者；第二項列火焰式不得設置之處所，準用第一項第二款至第四款、第六款、第七款，再加上水蒸氣會大量滯留與用火設備火焰外露；第三項才以附表按八種場所狀況指定適用探測器。歸納起來，偵煙式怕的是「假煙」（粉塵、水蒸氣、油煙），火焰式怕的是「假火焰」與遮蔽。\n數量計算走第 120 條：防火構造建築物且裝置面高度未滿四公尺時，差動式局限型一種 90、二種 70 平方公尺；補償式局限型一種 90、二種 70；定溫式局限型特種 70、一種 60、二種 20 平方公尺。同欄若為其他建築物則分別降為 50、40、50、40、40、30、15 平方公尺，防火構造與否直接影響設置個數，這是常考的對照。\n同條第三款是高溫場所的隱藏考點：具定溫式性能之探測器，應裝設在平時之最高周圍溫度比其標稱動作溫度低攝氏二十度以上之處；具二種以上標稱動作溫度者，以最低標稱動作溫度為準。洗澡區平時溫度偏高，標稱動作溫度就得往上選，否則天天誤報。\n易混淆對照：差動式看升溫速率、定溫式看絕對溫度、補償式兩者兼具。浴室蒸氣造成的緩慢溫升不足以觸發差動式，凝結水氣卻會影響其感熱室與洩漏孔，這正是條文把差動式局限型排除於水蒸氣場所之外的理由。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-023","偵煙式局限型探測器裝設於防火構造建築物天花板高度 8 公尺之裝置面時，若樓地板面積為 500 平方公尺，且其天花板中間有一下垂 40 公分的樑隔開，試問至少須設置幾個偵煙式局限型 1 種探測器？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-025","依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-022","依照各類場所消防安全設備檢修及申報作業基準之規定，會結露之場所適用的探測器為下列何者？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，裝置面高度 10 公尺者，不可選擇下列何種探測器設置？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-021","依各類場所消防安全設備設置標準規定，下列危險物品場所何者不須設置火警自動警報設備？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-027","依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",27,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-024",110,"差動式分布型探測器採熱電偶式時，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-024",109,"有關標示設備設在避難出口避難指標之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-024",107,"P 型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，依各類場所消防安全設備設置標準規定，不得超過多少個？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-024",106,"依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",1785123171974]