[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-025","fire-108-1-alarm-evacuation-025",108,1,25,"依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",{"A":16,"B":17,"C":18,"D":19},"一般配線","耐熱保護","耐燃保護","同軸電纜","A",null,[],false,"本題考點：火警自動警報設備配線之保護區分。耐燃、耐熱保護的對象是緊急供電系統之配線，發信機至受信總機的信號回路不在其列。\n【正解理由】依《各類場所消防安全設備設置標準》第 236 條，應依附表區分施予耐燃或耐熱保護者，限於「消防安全設備緊急供電系統之配線」。非定址式火警發信機與 P 型受信總機之間傳送的是發信動作信號，屬第 127 條所規範之火警自動警報設備信號回路；該條所定要求為信號回路採串接式並加設終端電阻、共用線供應之分區數不得超過七個、探測器回路電阻五十Ω以下，通篇未要求耐燃或耐熱保護。既非緊急供電系統配線，即依屋內線路裝置規則以一般配線施作，故選 A。\n【逐項排除】\n(A) 一般配線：該信號回路不屬第 236 條之緊急供電系統配線，僅須符合第 127 條之串接、電阻與絕緣電阻要求，為本題應選者。\n(B) 耐熱保護：係第 236 條附表所定保護方式之一，依《消防安全設備及必要檢修項目檢修基準》配線章之體例，對象為控制回路及標示燈回路。\n(C) 耐燃保護：同屬第 236 條附表所定方式，對象為電源回路配線，須用 MI 電纜、耐燃電纜或裝於金屬導線管槽並埋設於混凝土內。\n(D) 同軸電纜：第 236 條附表與檢修基準配線章所列電線種類均無同軸電纜，該線材用於高頻影音訊號傳輸，非火警信號回路用線。\n【記憶點】耐燃看電源、耐熱看控制與標示燈，發信機信號回路走一般配線。","這題的骨架是「哪一段線需要在火場中活下來」。耐燃保護要求的是即使被火直接烘烤仍能維持供電的路徑，因此對象是電源回路；耐熱保護要求的是在高溫環境下維持一段時間可用，對象是控制回路與標示燈回路；至於探測器與火警發信機的信號回路，只要斷線能被受信總機自動檢出即可，因此走一般配線。第 127 條第一款把「常開式之探測器信號回路採串接式並加設終端電阻」寫成強制規定，正是為了讓受信總機能藉終端電阻的迴路電流判斷斷線——線斷了會被立刻發現，就不必用昂貴的耐燃線去保它。\n《檢修基準》配線章外觀檢查列出的表 27-1、27-2 是配套的細節：耐燃與耐熱配線可用的電線種類幾乎相同，包含六○○Ｖ耐熱聚氯乙烯絕緣電線 HIV、聚四氟乙烯絕緣電線、交連聚乙烯絕緣聚氯乙烯被覆耐火電纜、六○○Ｖ聚乙烯絕緣電線 IE、乙丙烯橡膠絕緣電纜、鋼帶鎧裝電纜、鉛皮覆電纜、矽橡膠絕緣電線與匯流排槽；差別在施工方法——耐燃配線須裝於金屬導線管槽內並埋設於防火構造物之混凝土內，但以不燃材料建造且符合建築技術規則防火區劃規定之管道間得免埋設；耐熱配線只需裝於金屬導線管槽內即可。至於耐燃電纜與 MI 電纜，因線材本身已具耐火性能，得按電纜裝設法直接敷設，這是最常被拿來設計選擇題的一格。\n第 127 條的數字也應一併記：共用線分區數上限七個、探測器回路電阻五十Ω以下、對地電壓一百五十伏特以下者絕緣電阻零點一ＭΩ以上、超過者零點二ＭΩ以上、探測器回路每一火警分區零點一ＭΩ以上、與電力線間距三十公分以上。與第 131 條火警警鈴電鈴絕緣電阻二十ＭΩ以上放在一起背，可避免把兩個絕緣電阻值互換。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-024","某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，裝置面高度 10 公尺者，不可選擇下列何種探測器設置？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-023","偵煙式局限型探測器裝設於防火構造建築物天花板高度 8 公尺之裝置面時，若樓地板面積為 500 平方公尺，且其天花板中間有一下垂 40 公分的樑隔開，試問至少須設置幾個偵煙式局限型 1 種探測器？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-027","依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-022","依照各類場所消防安全設備檢修及申報作業基準之規定，會結露之場所適用的探測器為下列何者？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-028","有關緊急廣播設備之敘述，下列何者錯誤？",28,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-025",110,"下列有關火警受信總機之裝置規定，何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-025",109,"有關火焰式探測器之設置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-025",107,"有一飯店，其三樓之樓地板面積為 1200 平方公尺，依各類場所消防安全設備設置標準規定，於設置出口標示燈時，除應使用 A 級或 B 級外，出口標示燈標示面光度應在多少燭光（cd）以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-025",106,"依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",1785123171979]