[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-028":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-028","fire-108-1-alarm-evacuation-028",108,1,28,"有關緊急廣播設備之敘述，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"廣播區域在 50 平方公尺以下時，設 L 級、M 級或 S 級揚聲器","若設有緊急廣播設備時，得免設火警發信機之火警警鈴","室內安全梯或特別安全梯應垂直距離每 45 公尺單獨設定一廣播分區","揚聲器裝設於樓梯或斜坡通道時，至少垂直距離每 15 公尺設一個 L 級或 M 級揚聲器","D",null,[],false,"本題考點：緊急廣播設備之揚聲器級別與廣播分區規定，爭點在《設置標準》第 133 條第二款第五目對樓梯間揚聲器所限定的級別。\n【正解理由】第 133 條第二款第五目明定「設於樓梯或斜坡通道時，至少垂直距離每十五公尺設一個Ｌ級揚聲器」，級別限定為 L 級，不得以 M 級替代。樓梯間屬垂直避難動線，斷面狹長、回響大且與各層之門相隔，條文因此要求音壓最高的 L 級——依同條第一款音壓表，距揚聲器一公尺處 L 級應在 92 分貝以上，M 級為 87 分貝以上未滿 92 分貝，S 級為 84 分貝以上未滿 87 分貝。選項 D 把單一級別擴充成「L 級或 M 級」二選一，與條文不符，題目問何者錯誤，故選 D。\n【逐項排除】\n(A) 依第 133 條第二款第三目「廣播區域在五十平方公尺以下時，設Ｌ級、Ｍ級或Ｓ級揚聲器」，敘述正確。\n(B) 依第 131 條第二項「依本章第三節設有緊急廣播設備時，得免設前項火警警鈴」，敘述正確。\n(C) 依第 134 條第二款「室內安全梯或特別安全梯應垂直距離每四十五公尺單獨設定一廣播分區」，敘述正確。\n(D) 樓梯或斜坡通道之揚聲器限用 L 級，選項多列了 M 級，為本題應選者。\n【記憶點】樓梯間只認 L 級、每十五公尺一個；四十五公尺是廣播分區的切法，兩者不可互換。","緊急廣播設備的條文可以拆成「聲音夠不夠大」與「範圍怎麼切」兩條線。聲音線是第 133 條：第一款先訂音壓門檻，L 級 92 分貝以上、M 級 87 分貝以上未滿 92 分貝、S 級 84 分貝以上未滿 87 分貝，全部以距揚聲器一公尺處測得；第二款再把級別綁到廣播區域面積——超過一百平方公尺設 L 級，超過五十平方公尺一百平方公尺以下設 L 級或 M 級，五十平方公尺以下設 L 級、M 級或 S 級，級別隨面積遞減，邏輯一貫。第四目另訂水平距離十公尺以下之限制，並給了免設但書：居室樓地板面積在六平方公尺、或由居室通往地面之主要走廊及通道樓地板面積在六平方公尺以下、其他非居室部分在三十平方公尺以下，且與相鄰接區域揚聲器之水平距離相距八公尺以下者，得免設。\n第三款則是進階題常考的替代路徑：樓梯或斜坡通道以外之場所，若廣播區域內距樓地板面一公尺處依 P＝p＋10log10(Q\u002F4πr²＋4(1－α)\u002FSα) 求得之音壓在七十五分貝以上，即不受前款第四目水平距離十公尺之限制；殘響時間在三秒以上時，距樓地板面一公尺處至揚聲器之距離另須在 r＝(3\u002F4)√(QSα\u002Fπ(1－α)) 求得值以下。式中 Q 為指向係數、r 為受音點至揚聲器距離、α 為平均吸音率、S 為牆壁樓地板天花板面積合計。注意這條例外明文排除樓梯與斜坡通道，也就是說樓梯間的 L 級與十五公尺間隔沒有計算式可以繞過。\n範圍線則是第 134 條的三款：每一廣播分區不得超過一樓層；室內安全梯或特別安全梯垂直距離每四十五公尺單獨設定一廣播分區，其地下層部分另設一分區；建築物挑空構造部分所設揚聲器音壓符合規定時，該部分得為一廣播分區。與第 112 條火警分區對照著背，可避免把六百平方公尺與五十平方公尺這兩組面積混用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-027","依各類場所消防安全設備設置標準第 112 條，有關火警自動警報設備之火警分區劃定規定，下列何者錯誤？",27,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-029","消防安全設備測試報告書測試方法及判定要領中規定，火警自動警報設備外觀試驗，其定溫式感知線型探測器之判定要領中，下列何者正確？",29,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，裝置面高度 10 公尺者，不可選擇下列何種探測器設置？",26,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-030","利用各種減光罩對光電式分離型探測器進行測試，以確認其火災動作試驗、不作動試驗、故障警報試驗並判定是否符合規定，下列方式何者錯誤？",30,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-025","依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",25,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-alarm-evacuation-031","依各類場所消防安全設備設置標準對於出口標示燈設置之相關規定，下列何者正確？",31,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-028",110,"瓦斯漏氣火警自動警報設備進行性能檢查時，檢知區域警報裝置其音壓在距 1 公尺處應為多少分貝以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-alarm-evacuation-028",109,"有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-028",107,"依各類場所消防安全設備檢修及申報作業基準規定，對火警自動警報設備進行二信號性能檢查時，有關判定方法，下列敘述何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-028",106,"大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",1785123172016]