[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-038","fire-108-1-alarm-evacuation-038",108,1,38,"依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",{"A":16,"B":17,"C":18,"D":19},"1.5 m\u002Fsec","1.4 m\u002Fsec","1.3 m\u002Fsec","1.0 m\u002Fsec","A",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 189 條特別安全梯或緊急昇降機間排煙室之排煙量，兼用時為每秒六立方公尺以上，並據以回推閘門處的平均風速。\n【正解理由】依《各類場所消防安全設備設置標準》第 189 條第二款第四目，「排煙機、進風機之排煙量、進風量在每秒四立方公尺（兼用時，每秒六立方公尺）以上，且可隨排煙口、進風口開啟而自動啟動」。題幹為特別安全梯與緊急昇降機間兼用之排煙室，應適用括號內的兼用值每秒六立方公尺；風量等於平均風速乘以通過斷面積，以排煙閘門面積四平方公尺回推，測得的平均風速須在一點五公尺每秒以上，才能達到法定風量，故選 A。\n【逐項排除】\n(A) 一點五公尺每秒對應風量六立方公尺每秒，恰達兼用時之法定下限，判定合格，為本題應選者。\n(B) 一點四公尺每秒對應五點六立方公尺每秒，未達六立方公尺每秒。\n(C) 一點三公尺每秒對應五點二立方公尺每秒，同樣不足。\n(D) 一點零公尺每秒對應四立方公尺每秒，那是非兼用排煙室的排煙量門檻，本題排煙室為兼用，不得援用較低的數值。\n【演算步驟】風量公式 Q = V × A；法定兼用排煙量 Q = 6 m³\u002Fsec、排煙閘門面積 A = 4 m²；V = Q ÷ A = 6 m³\u002Fsec ÷ 4 m² = 1.5 m\u002Fsec。\n【記憶點】排煙室排煙量「單用四、兼用六」（每秒立方公尺），除以閘門面積就是風速下限。","《各類場所消防安全設備設置標準》第 189 條給的是特別安全梯或緊急昇降機間排煙室的兩條路：第一款走自然排煙，設置直接面向戶外之窗戶，窗戶與煙接觸部分使用不燃材料、有效開口面積位於天花板高度二分之一以上之範圍內、有效開口面積在二平方公尺以上（兼用時三平方公尺以上），平時關閉之窗戶並設手動開關裝置，其操作部分設於距離樓地板面八十公分以上一百五十公分以下之牆面；第二款走機械排煙，設置排煙、進風風管，排煙口位於天花板高度二分之一以上之範圍內，進風口位於天花板高度二分之一以下之範圍內，進風口直接面向戶外時開口面積在一平方公尺以上（兼用時一點五平方公尺以上），排煙機、進風機之排煙量、進風量在每秒四立方公尺以上（兼用時每秒六立方公尺以上），且排煙口、進風口、排煙機及進風機連接緊急電源，供電容量應供其有效動作三十分鐘以上。\n把兼用與非兼用的四組數字排在一起會發現一個漂亮的規律：窗戶有效開口面積二對三、進風口面積一對一點五、排煙量四對六，全部是一點五倍。理由很直觀，兼用的排煙室同時服務特別安全梯與緊急昇降機間，煙可能從兩個方向侵入、使用人數也加倍，所以能力等比放大。記住「兼用一律乘一點五」，比逐個硬背省力得多。\n單位是本題型最大的陷阱。第 189 條用每秒立方公尺，第 188 條的室內排煙與地下通道卻用每分鐘立方公尺（一百二十與六百）。換算後每秒六立方公尺等於每分鐘三百六十立方公尺，遠高於室內排煙的一百二十，這正說明排煙室在避難動線上的地位：它是進入安全梯前的最後緩衝，必須以正壓與大排煙量把煙擋在門外。\n風速題的解法可以固定成三步：先由「兼用與否」選出法定風量，再確認題目給的是閘門或風管的通過斷面積，最後以 V = Q ÷ A 求風速。若題目反過來給風速一點二公尺每秒、問閘門面積至少多少，就改成 A = Q ÷ V = 6 ÷ 1.2 = 5 平方公尺。同一組數據可以正算也可以反算，是命題者很喜歡的變化型。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-037","某機場候機室樓地板面積 300 m2，自然排煙設備其窗戶都在天花板或其下方 80 公分範圍內，共有 10 扇窗，採正向由上往外推可達 90°，請問每一扇窗面積多大才合格？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，下列何種場所不須設置緊急電源插座？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-036","依各類場所消防安全設備設置標準第 28 條應設置排煙設備之規定，下列何者錯誤？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-alarm-evacuation-040","依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-035","依各類場所消防安全設備設置標準規定，在應設排煙設備之場所，有關其排煙設備設置之描述，下列何者錯誤？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-109-1-alarm-evacuation-001","常開式之火警探測器信號回路，加設終端電阻之目的為何？",109,[53,57,60,64],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-038",110,"特別安全梯排煙室設置直接面向戶外之窗戶時，窗戶之有效開口面積應在多少平方公尺以上？",{"webId":58,"year":51,"stem":59,"number":13},"fire-109-1-alarm-evacuation-038","有關應設置緊急照明設備之場所，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":61,"year":62,"stem":63,"number":13},"fire-107-1-alarm-evacuation-038",107,"依各類場所消防安全設備設置標準規定，差動式分布型及偵煙式探測器之探測區域，指探測器裝置面之四周以淨高多少公分以上之樑或類似構造體區劃包圍者？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-038",106,"依各類場所消防安全設備設置標準規定，避難指標設於出入口裝設應距樓地板面的高度要求為多少？",1785123172126]