[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-108-1-alarm-evacuation-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-警報與避難系統消防安全設備概要-040","fire-108-1-alarm-evacuation-040",108,1,40,"依各類場所消防安全設備設置標準規定，緊急供電系統之配線的保護下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"排煙設備的緊急電源到排煙口的配線應採耐燃保護","無線電通信輔助設備的緊急電源到增幅器的配線應採耐燃保護","瓦斯漏氣火警自動警報設備的受信總機到檢知器的配線應採耐燃保護","火警自動警報設備的受信總機到定址式探測器的配線應採耐燃保護","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 235 條、第 236 條緊急供電系統配線之耐燃保護與耐熱保護區分。\n【正解理由】依《各類場所消防安全設備設置標準》第 235 條第三款，電源回路之配線應施予耐燃保護；同條第四款，標示燈回路及控制回路之配線應施予耐熱保護；第 236 條並規定消防安全設備緊急供電系統之配線，依該條之表區分，施予耐燃保護或耐熱保護。火警自動警報設備自受信總機至探測器之配線，屬感知信號與控制路徑而非電源回路，依前開區分施予耐熱保護即可，敘述稱應採耐燃保護與規定不符，為本題應選者，故選 D。\n【逐項排除】\n(A) 排煙設備自緊急電源至排煙口之配線屬電源回路，依第 235 條第三款施予耐燃保護，敘述正確。\n(B) 無線電通信輔助設備自緊急電源至增幅器之配線同屬電源回路，依同款施予耐燃保護，敘述正確。\n(C) 瓦斯漏氣火警自動警報設備自受信總機至檢知器之配線，依第 236 條之表列屬應施予耐燃保護者，敘述與規定相符；該檢知器回路並依第 144 條第二款採串接式配線並加設終端電阻，以便藉由受信總機作斷線自動檢出。\n(D) 受信總機至定址式探測器之配線並非電源回路，耐熱保護即為已足，將其提升為耐燃保護與條文區分不合。\n【記憶點】「電源回路耐燃、控制與標示燈回路耐熱」是第 235 條的主軸，個別設備別再回到第 236 條的表核對。","《各類場所消防安全設備設置標準》第 235 條是緊急供電系統配線的總則，四款依序規定：一、電氣配線應設專用回路，不得與一般電路相接，且開關有消防安全設備別之明顯標示；二、緊急用電源回路及操作回路，使用六百伏特耐熱絕緣電線，或同等耐熱效果以上之電線；三、電源回路之配線施予耐燃保護；四、標示燈回路及控制回路之配線施予耐熱保護。第 236 條再把個別消防安全設備的配線，依該條之表區分施予耐燃保護或耐熱保護。兩條是總則與細目的關係，答題時先用第 235 條判斷回路屬性，再用第 236 條核對設備別。\n耐燃與耐熱的實質差別在施工方法。耐燃保護依第 235 條第三款有三種做法：電線裝於金屬導線管槽內，並埋設於防火構造物之混凝土內，混凝土保護厚度為二十毫米以上，但在使用不燃材料建造且符合建築技術規則防火區劃規定之管道間，得免埋設；使用 MI 電纜或耐燃電纜時，得按電纜裝設法直接敷設；其他經中央主管機關指定之耐燃保護裝置。耐熱保護依第四款則放寬為：電線於金屬導線管槽內裝置；使用 MI 電纜、耐燃電纜或耐熱電線電纜時，得按電纜裝設法直接敷設；其他經中央主管機關指定之耐熱保護裝置。最鮮明的對比是耐燃要「埋入混凝土二十毫米」，耐熱只要「裝在金屬導線管槽內」。\n判斷回路屬性的訣竅是問一句：這段配線燒斷會怎樣。電源回路一斷，整套設備停止運轉，後果最嚴重，故要求最高的耐燃；標示燈回路與控制回路斷線只影響顯示或個別動作，降一級為耐熱。火警自動警報設備自受信總機到探測器屬感知信號路徑，歸耐熱；瓦斯漏氣火警自動警報設備的檢知器回路則依第 236 條之表列為耐燃，並依第 144 條第一款以直流五百伏特額定之絕緣電阻計測定其絕緣電阻值，對地電壓在一百五十伏特以下者應在零點一 MΩ 以上，超過者在零點二 MΩ 以上。\n配線題常與電源題合併命題。第 145 條規定瓦斯漏氣火警自動警報設備之緊急電源應使用蓄電池設備，其容量應能使二回路有效動作十分鐘以上、其他回路能監視十分鐘以上。回路屬性、絕緣電阻與緊急電源容量，是同一組考點的三個面向。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-alarm-evacuation-039","依各類場所消防安全設備設置標準規定，下列何種場所不須設置緊急電源插座？",39,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-109-1-alarm-evacuation-001","常開式之火警探測器信號回路，加設終端電阻之目的為何？",109,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-alarm-evacuation-038","依各類場所消防安全設備設置標準規定，特別安全梯及緊急昇降機間兼用排煙室時排煙閘門面積為 4 m2，忽略溫度的影響，測試點量得的平均風速 V(m\u002Fsec)應為多少以上為合格？",38,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-109-1-alarm-evacuation-002","使用「加瓦斯試驗器」進行瓦斯漏氣檢知器性能檢查時，若檢測對象的瓦斯對空氣之比重大於 1 者，應使用何種氣體來檢測？",2,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-alarm-evacuation-037","某機場候機室樓地板面積 300 m2，自然排煙設備其窗戶都在天花板或其下方 80 公分範圍內，共有 10 扇窗，採正向由上往外推可達 90°，請問每一扇窗面積多大才合格？",37,{"webId":49,"stem":50,"number":51,"year":35,"session":12},"fire-109-1-alarm-evacuation-003","瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",3,[53,57,60,64],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-040",110,"避難器具之裝設規定，下列何者正確？",{"webId":58,"year":35,"stem":59,"number":13},"fire-109-1-alarm-evacuation-040","有關火警自動警報設備受信總機周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":61,"year":62,"stem":63,"number":13},"fire-107-1-alarm-evacuation-040",107,"依各類場所消防安全設備檢修及申報作業基準規定，緩降機應以測量下降距離及下降時間，計算出下降速度，最大下降速度應在每秒多少公分以內？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-040",106,"有關出口標示燈具閃滅或音聲引導功能者，依規定下列何者錯誤？",1785123172146]