[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-029","fire-108-1-fire-law-029",108,1,29,"依各類場所消防安全設備設置標準，下列有關室內消防栓箱的規定何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"箱身為厚度在 1.6 毫米以上之鋼板或具同等性能以上之不燃材料者","具有足夠裝設消防栓、水帶及瞄子等裝備之深度","箱面表面積在 0.7 平方公尺以上","箱面有明顯而不易脫落之消防栓字樣，每字在 2 平方公分以上","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 35 條所定室內消防栓箱的箱身厚度、箱面表面積與字樣大小。\n【正解理由】依《各類場所消防安全設備設置標準》第 35 條,室內消防栓箱箱面應有明顯而不易脫落之消防栓字樣,每字在二十平方公分以上。(D) 把字樣大小寫成每字二平方公分以上,整整少了一個位數,與條文明定的規格不符,故選 D。\n【逐項排除】\n(A) 正確。條文明定箱身為厚度在一點六毫米以上之鋼板或具同等性能以上之不燃材料,確保箱體在火場受熱時不致變形卡死。\n(B) 正確。條文要求箱體具有足夠裝設消防栓、水帶及瞄子等裝備之深度,深度不足會使水帶取出與收納都發生困難。\n(C) 正確。同一款並規定箱面表面積在零點七平方公尺以上,使開門操作與字樣標示都能有足夠面積。\n(D) 錯誤,為本題應選者。字樣每字應在二十平方公分以上,寫成二平方公分僅約指甲大小,在濃煙的火場中根本無法辨識。\n【記憶點】室內消防栓箱記「鋼板一點六毫米、箱面零點七平方公尺、每字二十平方公分」。","「每字在二十平方公分以上」不是室內消防栓箱獨有的規格,而是本標準對消防設備箱體標示的通用要求,一次記完可以省下好幾題:依《各類場所消防安全設備設置標準》第 40 條,室外消防栓附設之水帶箱,箱面有明顯而不易脫落之水帶箱字樣,每字在二十平方公分以上。依同標準第 180 條,連結送水管之出水口箱標明出水口字樣,每字在二十平方公分以上。依第 182 條,設於十一層以上樓層之水帶箱標明水帶箱字樣,每字應在二十平方公分以上。唯一的例外是第 191 條的緊急電源插座保護箱,箱蓋標示緊急電源插座字樣,每字在二平方公分以上——本題的錯誤選項正是把這個唯一的例外值搬到室內消防栓箱上,是典型的跨條文混淆設計。\n\n箱面表面積也有一組對照值。室內消防栓箱為零點七平方公尺以上,是這組數字裡最小的。依第 40 條,室外消防栓附設之水帶箱,箱面表面積在零點八平方公尺以上;第 182 條之水帶箱亦為零點八平方公尺以上,均略大於室內消防栓箱。鋼板厚度反而高度一致:第 35 條的消防栓箱、第 180 條的出水口箱、第 182 條的水帶箱與第 191 條的插座保護箱,都要求厚度在一點六毫米以上之鋼板或具同等性能以上之不燃材料。\n\n記憶方式是「一點六毫米打底、字樣二十平方公分、箱面室內零點七室外零點八」,唯一需要單獨記住的例外,就是緊急電源插座保護箱的每字二平方公分。這類數值題看似瑣碎,卻是消防法規概要年年出現的送分題型,把同類規格橫向並排一次記熟,遠比逐條背誦有效率。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-028","依可燃性高壓氣體儲存場所防爆牆設置基準規定，防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，其強度應能承受可能預料之氣體爆炸衝擊。下列有關其構造規定何者錯誤？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-030","依各類場所消防安全設備設置標準規定，下列何種處所得免設排煙設備？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-027","下列有關二氧化碳滅火設備各種標示規格規定之敘述，何者錯誤？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-031","依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-026","依防火牆及防火水幕設置基準規定，若防火水幕之防護高度為 12 公尺，請問其每公尺水幕長度放水量應在每分鐘多少公升以上？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-032","依各類場所消防安全設備檢修及申報作業基準規定，有關避難器具開口部大小之檢查，下列何者正確？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-029",111,"依各類場所消防安全設備設置標準規定，下列何場所之樓地板面積合計未達 1 千平方公尺，得設置水道連結型自動撒水設備或與現行法令同等以上效能之滅火設備？①產後護理之家 ②團體家屋 ③精神護理之家 ④兒童及少年福利機構",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-029",110,"有一室外儲槽，其容量為 9000 公秉，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，設有防火水幕，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-029",109,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，全閉揚程應為性能曲線上全揚程之多少以下？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-029",107,"依各類場所消防安全設備設置標準之規定，下列何者應設置室外消防栓設備？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-029",106,"下列有關簡易自動滅火設備規定之敘述，何者錯誤？",1785123159158]