[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-032","fire-108-1-fire-law-032",108,1,32,"依各類場所消防安全設備檢修及申報作業基準規定，有關避難器具開口部大小之檢查，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"救助袋之開口部大小，高 50 cm 以上，寬 60 cm 以上","緩降機之開口部大小，高 80 cm 以上，寬 50 cm 以上或高 100 cm 以上，寬 45 cm 以上","滑台之開口部大小，高 60 cm 以上，寬為滑台最大寬度以上","避難橋之開口部大小，高 160 cm 以上，寬為避難橋最大寬度以上","B",null,[],false,"本題考點：避難器具開口部的最小尺寸，依《消防安全設備及必要檢修項目檢修基準》第十八章避難器具外觀檢查「開口部」之表 18-2，四類器具各占一列，數值與《各類場所消防安全設備設置標準》第 162 條之開口面積表相同。\n【正解理由】表 18-2 就緩降機、避難梯、避難繩索及滑杆列為「高 80cm 以上，寬 50cm 以上或高 100cm 以上，寬 45cm 以上」，第 162 條亦以相同文字規定，採「高窄」與「矮寬」二者擇一的併列寫法，選項所述與該列逐字相符，故選 B。\n【逐項排除】\n(A) 救助袋該列為「高 60cm 以上、寬 60cm 以上」，高與寬同為 60cm，選項把高寫成 50cm，低於表列下限。\n(B) 與表 18-2 緩降機該列完全一致，含「或高 100cm 以上，寬 45cm 以上」之替代組合亦相符，為正確敘述。\n(C) 滑台該列為「高 80cm 以上；寬為滑台最大寬度以上」，寬的寫法無誤，但高不是 60cm，表列下限為 80cm。\n(D) 避難橋該列為「高 180cm 以上；寬為避難橋最大寬度以上」，160cm 不足；避難橋供人員直立通過，高度取四者中最大值。\n【記憶點】開口高度由小到大排：救助袋 60、緩降機這一組 80（或 100）、滑台 80、避難橋 180。","開口部尺寸表是把「人與器具要能通過」量化成數字。緩降機、避難梯、避難繩索及滑杆共用一列，並給「高 80cm 以上、寬 50cm 以上」或「高 100cm 以上、寬 45cm 以上」兩組擇一，原因在於這類器具是使用者以身體穿越開口後沿繩索或梯級下降，開口能讓人通過即可，故容許高窄與矮寬互換；救助袋是把入口零件架在開口上、袋口本身即為通道，故高寬同為 60cm；滑台與避難橋則是把整個台面或橋面接上開口，寬度自然以「器具最大寬度以上」為準，避難橋因使用者多為直立步行通過，高度拉到 180cm。\n《各類場所消防安全設備設置標準》第 162 條的開口面積表與檢修基準表 18-2 是同一組數值，差別只在前者規範設置時應保有的開口、後者是檢修時的判定依據，所以本題名為考檢修基準，實則一題兩用。\n同章外觀檢查另有三張表常一併入題，務必分清：表 18-1 操作面積（救助袋寬 1.5m、長 1.5m，緩降機 0.5m2 以上且邊長 60cm 以上）、表 18-3 下降空間（緩降機為以器具中心半徑 0.5m 之圓柱形範圍，直降式救助袋為以中心半徑 1 公尺之圓柱形範圍，並與牆壁保持 30cm 以上間距）、表 18-4 下降空地（斜降式救助袋為最下端起 2.5m 及中心線左右各 1m 所圍範圍）。\n開口部的判定不只有尺寸：由地板面至開口部下端之高度應在 150cm 以下，開口部不得加設固定板、木條，附近不得有書架、展示台堵塞，開啟後制動器須確實動作而不因振動鬆開。數值題之外的文字要件同樣是命題點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-031","依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-033","依各類場所消防安全設備檢修及申報作業基準規定，有關配線絕緣阻抗試驗合格之判定，若電壓超過 300 V 者，其絕緣電阻值至少應為多少以上？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-030","依各類場所消防安全設備設置標準規定，下列何種處所得免設排煙設備？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-034","依消防法施行細則，有關消防安全設備之設計、監造、裝置及檢修工作項目之規定，下列何者正確？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-029","依各類場所消防安全設備設置標準，下列有關室內消防栓箱的規定何者錯誤？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-035","依建築技術規則建築設計施工編規定，女兒牆之高度應在多少公尺以內？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-032",111,"供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-032",110,"裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-032",109,"依各類場所消防安全設備檢修及申報作業基準，有關滅火器外觀檢查之規定，滅火器本體上端與樓地板面之距離，18 公斤以上者不得超過 a 公尺，未滿 18 公斤者不得超過 b 公尺。a、b 值各為下列何者？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-032",107,"依各類場所消防安全設備設置標準之規定，有關無線電通信輔助設備，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-032",106,"水霧滅火設備水源，應連結加壓送水裝置。其用於防護電氣設備者，出水壓力達每平方公分多少公斤以上？",1785123159195]