[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-036","fire-108-1-fire-law-036",108,1,36,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，下列何者不符合呼水裝置之規定？",{"A":16,"B":17,"C":18,"D":19},"呼水槽應使用鋼板，並予有效防銹處理，或使用具有防火能力之塑膠槽","呼水槽應有 100 公升以上之有效儲存量","減水警報之發訊裝置應採用浮筒開關或電極方式，當呼水槽水位降至其容量三分之一前，應能發出警報音響至平時有人駐在處","呼水槽自動給水裝置應使用自來水管或屋頂水箱，經由球塞自動給水","C",null,[],false,"本題考點：消防幫浦呼水裝置的規格要求。《各類場所消防安全設備設置標準》第 234 條明定，消防幫浦、電動機、附屬裝置及配管摩擦損失計算由中央消防機關另定之，呼水裝置即屬該附屬裝置，其規格見《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》。\n【正解理由】呼水裝置用於幫浦吸水口高於水源水面時，使幫浦與吸水管內經常保持滿水。依該基準關於呼水裝置減水警報之規定，發訊水位是以呼水槽容量之二分之一為界，選項所寫的三分之一與該規定不符；本題問不符合者，故選 C。\n【逐項排除】\n(A) 呼水槽採鋼板並施予有效防銹處理，或使用具防火能力之塑膠槽，與該基準對槽體材質之要求相符。\n(B) 呼水槽應有 100 公升以上之有效儲存量，是該基準所定的容量下限，敘述與規定一致。\n(C) 發訊裝置採浮筒開關或電極方式的部分無誤，但把作動水位寫成容量三分之一，與所定之二分之一不同，為應選者。\n(D) 自動給水裝置以自來水管或屋頂水箱經由球塞自動給水，是維持呼水槽常保滿水的規定方式，敘述相符。\n【記憶點】呼水槽四件事：鋼板防銹、100 公升、球塞補水，水少一半就要叫——是二分之一，不是三分之一。","呼水裝置處理的是「幫浦位置高於水源水面」時的啟動問題：此時吸水管與幫浦內若未常保滿水，幫浦一啟動就會空轉而吸不上水，因此以呼水槽經呼水管把水補進幫浦與吸水管，並於呼水管設逆止閥防止回流。整組裝置的組成常被拆開命題：呼水槽、呼水管、溢水用排水管、補給水管、減水警報裝置與自動給水裝置。\n四個選項恰好對應四個規格面向：材質（鋼板加有效防銹處理，或具防火能力之塑膠槽）、容量（有效儲存量的下限）、警報（發訊方式採浮筒開關或電極方式，並訂出發訊水位）與補水（以自來水管或屋頂水箱經球塞自動給水）。其中警報一項最常被改數字——水位降到一半前就要在平時有人駐守處發出警報音響，是因為呼水槽水量減少本身即代表底閥或吸水管漏水，必須在幫浦仍能正常啟動之前就讓人知道；若等到剩三分之一才叫，處置餘裕已被壓縮。\n法源層級也要記清楚：《各類場所消防安全設備設置標準》第 234 條規定，依該標準設置之室內消防栓、室外消防栓、自動撒水、水霧滅火、泡沫滅火、冷卻撒水、射水設備及連結送水管等設備，其消防幫浦、電動機、附屬裝置及配管摩擦損失計算，由中央消防機關另定之。本題基準即由此授權而來，體例為章節而無條號。\n常與呼水裝置合併命題的是幫浦本體規定，例如同標準第 37 條之室內消防栓消防幫浦，出水量第一種每支每分鐘 150 公升以上、第二種每支每分鐘 90 公升以上，全揚程 H＝h1＋h2＋h3＋17m。\n易混淆的是消防幫浦其他附屬裝置：呼水裝置管的是「啟動前吸得到水」，防止水溫上升用排放裝置管的是「閉水運轉時水溫不致過高」，幫浦性能試驗裝置管的是「事後能驗證出水量與揚程」，三者目的各異，選項常互換敘述。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-035","依建築技術規則建築設計施工編規定，女兒牆之高度應在多少公尺以內？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-037","依避難器具支固器具及固定部之結構、強度計算及施工方法規定，裝置避難器具之固定部，應能承受承載荷重與附加荷重之和。若避難器具為緩降機，其承載荷重應為最大使用人數乘以多少？",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-034","依消防法施行細則，有關消防安全設備之設計、監造、裝置及檢修工作項目之規定，下列何者正確？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-038","依據消防設備師及消防設備士管理辦法規定，有關技術研討活動或訓練，其辦理機關（構）、團體應於舉辦 X 個月前，檢附文件向中央主管機關申請認可，中央主管機關並於舉辦 Y 個月前准駁之，另於技術研討活動或訓練結束後 Z 個月內應檢附參加之消防設備師及消防設備士簽到表及參加時數清冊，向中央主管機關申請訓練積分審查及登記。請問下列何者正確？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-033","依各類場所消防安全設備檢修及申報作業基準規定，有關配線絕緣阻抗試驗合格之判定，若電壓超過 300 V 者，其絕緣電阻值至少應為多少以上？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-039","依建築技術規則建築設計施工編規定，下列何者不屬於「無窗戶居室」？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-036",111,"受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-036",110,"依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-036",109,"依避難器具支固器具及固定部之結構、強度計算及施工方法之規定，裝置避難器具固定部材料，使用直徑 1 公分錨定螺栓，設定試驗荷重 500 公斤力（kgf）時，則鎖緊扭力應為多少公斤力\u002F公分（kgf\u002Fcm）？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-036",107,"依防火牆及防火水幕設置基準之規定，防火水幕設備之水源應連結加壓送水裝置，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-036",106,"下列有關各類場所消防安全設備檢修及申報作業基準行政函釋之敘述，何者錯誤？",1785123159237]