[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-fire-law-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-消防法規概要-037","fire-108-1-fire-law-037",108,1,37,"依避難器具支固器具及固定部之結構、強度計算及施工方法規定，裝置避難器具之固定部，應能承受承載荷重與附加荷重之和。若避難器具為緩降機，其承載荷重應為最大使用人數乘以多少？",{"A":16,"B":17,"C":18,"D":19},"285","390","660","900","B",null,[],false,"本題考點：避難器具固定部的強度計算。依《避難器具支固器具及固定部之結構、強度計算及施工方法》，裝置避難器具之固定部應能承受承載荷重與附加荷重之和，而承載荷重依器具種類分別規定，緩降機是以最大使用人數為基數乘上定值。\n【正解理由】依該規定關於承載荷重之計算，緩降機之承載荷重為最大使用人數乘以 390（約相當於每一使用者 3.9 kN），此定值已把使用者體重與下降時的動態衝擊計入，再與附加荷重相加，據以檢核固定部強度，故選 B。\n【逐項排除】\n(A) 285 小於緩降機該項所定之基數，以之計算會低估固定部須承受的承載荷重，不是緩降機適用的值。\n(B) 390 即緩降機承載荷重之基數，乘以最大使用人數後即為該具緩降機的承載荷重，敘述正確。\n(C) 660 不是緩降機該項所列的基數；承載荷重按避難器具種類逐項規定，不得把其他器具的數值套到緩降機。\n(D) 900 同樣不是緩降機所適用的基數，數值明顯偏高，與以最大使用人數為基數的計算方式不相稱。\n【記憶點】緩降機承載荷重＝最大使用人數×390，固定部還要再加上附加荷重一併檢核。","本題法源是內政部依《各類場所消防安全設備設置標準》授權訂定的技術規定，體例為章節而無條號。它把固定部的檢核寫成一個加法：固定部應能承受承載荷重與附加荷重之和。承載荷重屬「使用者這一側」的荷重，依避難器具種類分別規定，緩降機以最大使用人數為基數乘上定值，人數越多、固定部要求越高；附加荷重則是器具本體與支固器具自身重量等固定側荷重。兩者相加才是檢核值，只算其中一項是常見失分點。\n與強度有關的規定要一起記：《各類場所消防安全設備設置標準》第 173 條明定，供緩降機或救助袋使用之支固器具，以及供懸吊型梯、滑杆或避難繩索使用之固定架，應使用符合 CNS 二四七三、四四三五規定或具有同等以上強度及耐久性之材料，並應施予耐腐蝕加工處理。材料規格在設置標準、荷重計算在技術規定、日後查驗在檢修基準，三層各管一段，命題時常交錯出現。\n檢修端可對照《消防安全設備及必要檢修項目檢修基準》第十八章避難器具之性能檢查：固定部以目視及扭力扳手確認，判定要件包括螺栓、螺帽無鬆動或脫落，穿孔錨栓工法之錨栓所使用螺帽之拴緊應符合表 18-6 之規定，固定基礎無因龜裂而破損，固定安裝部分無明顯腐蝕、生鏽、變形、龜裂等影響強度之異常。緩降機另有綜合檢查，以實際下降測得之平均下降速度應在每秒 80 至 100cm、最大下降速度在每秒 150cm 以內。荷重是設計端的數字，栓緊轉矩與下降速度是檢修端的數字，兩邊不要互套。\n本題型的另一種問法是換掉器具別（例如改問避難梯或救助袋），基數即隨器具別而不同，讀題時要先鎖定器具別再找對應的那一列，和「下降空間、下降空地依器具別分列」是同一種閱讀方式。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-fire-law-036","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，下列何者不符合呼水裝置之規定？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-fire-law-038","依據消防設備師及消防設備士管理辦法規定，有關技術研討活動或訓練，其辦理機關（構）、團體應於舉辦 X 個月前，檢附文件向中央主管機關申請認可，中央主管機關並於舉辦 Y 個月前准駁之，另於技術研討活動或訓練結束後 Z 個月內應檢附參加之消防設備師及消防設備士簽到表及參加時數清冊，向中央主管機關申請訓練積分審查及登記。請問下列何者正確？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-fire-law-035","依建築技術規則建築設計施工編規定，女兒牆之高度應在多少公尺以內？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-fire-law-039","依建築技術規則建築設計施工編規定，下列何者不屬於「無窗戶居室」？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-fire-law-034","依消防法施行細則，有關消防安全設備之設計、監造、裝置及檢修工作項目之規定，下列何者正確？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-fire-law-040","依建築技術規則建築設計施工編之規定，下列何者列入觀眾席樓地板面積計算？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-037",111,"依據乾粉滅火設備各種標示規格規定，其標示規格為長 480 mm 以上，寬 270 mm 以上，黃底黑字，每字大小為 25 mm×25 mm 以上，係屬下列何者？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-037",110,"有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-fire-law-037",109,"依建築技術規則建築設計施工編之定義，每層陽臺面積之和，以不超過建築面積多少為限？其未達 8 平方公尺者，得建築 8 平方公尺。",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-037",107,"依防火牆及防火水幕設置基準之規定，有一儲槽其水平剖面最大半徑為 5 公尺，內裝有公共危險物品，該公共危險物品之閃火點為攝氏八十度，則假想火面高度為多少公尺？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-037",106,"下列有關消防幫浦之性能規定之敘述，何者正確？",1785123159245]