[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-108-1-water-chemical-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":26,"sameNumber":52,"hasEssay":25},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":24,"freq":12,"indexable":25},"fire-108-1-水與化學系統消防安全設備概要-001","fire-108-1-water-chemical-001",108,1,"在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"A":15,"B":16,"C":17,"D":18},"X=20；Y=20","X=20；Y=40","X=40；Y=20","X=40；Y=40","D",null,[],false,"本題考點：應設室內消防栓設備之場所,因設有室外消防栓設備而得免設時的距離要件與樓層限制。\n【正解理由】依《各類場所消防安全設備設置標準》關於室內消防栓設備應設場所及其免設範圍之規定,應設室內消防栓設備之場所,若設有室外消防栓設備,其有效滅火範圍以「第一層水平距離四十公尺以下、第二層步行距離四十公尺以下」界定,且免設效果僅及於第一層與第二層。兩個數值同為四十公尺,差別在量測方式,故選 D。\n【逐項排除】\n(A) 兩層皆取二十公尺,數值小於規定的四十公尺,會不當限縮室外消防栓的有效滅火範圍,與免設要件不符。\n(B) 第二層四十公尺雖與規定相符,但第一層誤植為二十公尺;規定的兩個距離數值相同,並無第一層較嚴的設計。\n(C) 與 (B) 恰好相反,第一層四十公尺正確而第二層誤植為二十公尺,同樣不符兩層同為四十公尺的規定。\n(D) 第一層水平距離四十公尺以下、第二層步行距離四十公尺以下,數值與量測方式均與規定一致,為本題應選者。\n【記憶點】室外栓救裡面:一、二層各四十,第一層量水平、第二層算步行。","這條規定的設計邏輯值得先釐清。滅火設備的免設條款大致分兩種型態:一種是「同一位置已有更強的滅火設備」,例如場所已依標準設有自動撒水、水霧、泡沫、二氧化碳或乾粉等滅火設備者,在該有效範圍內得免設室內消防栓;另一種是本題的型態,以室外消防栓的射水能力涵蓋建築物低樓層,因此附加了距離與樓層的雙重限制。室外消防栓部署於建築物外部,水帶延伸與人員進入的可行性隨樓層升高而急遽下降,故免設效果被限定在第一層與第二層,三層以上不得援用。\n\n兩個距離的量測方式不同,是本題的真正陷阱。第一層以「水平距離」計,即平面上的直線距離,反映射水可直接及於的範圍;第二層須經樓梯上樓,故改以「步行距離」計,依實際可通行路徑量測,通常較同一直線距離為長。看到題目把兩個數值設成不同,多半就是在測驗考生是否把量測方式與數值混為一談。\n\n易混淆對照:一般場所與公共危險物品場所的室內消防栓規定差距很大,可並列記憶。依《各類場所消防安全設備設置標準》第二百零九條,公共危險物品場所之室內消防栓應設第一種消防栓,任一點至消防栓接頭水平距離在二十五公尺以下,同時使用時瞄子放水壓力在每平方公分三點五公斤以上,放水量在每分鐘二百六十公升以上,水源容量按繼續放水三十分鐘計算,超過五支以五支計。同標準第二百十條之室外消防栓則規定口徑六十三毫米以上、與防護對象各部分水平距離四十公尺以下且設二支以上,放水量每分鐘四百五十公升以上。相對地,一般場所之室內消防栓水源容量,依同標準第三十六條規定為繼續放水二十分鐘之水量,且該樓層消防栓超過二支時以二支計算。\n\n第一種與第二種室內消防栓的硬體差異亦常同時命題,依同標準第三十二條,立管管徑第一種在六十三毫米以上、第二種在五十毫米以上;屋頂水箱水量第一種零點五立方公尺以上、第二種零點三立方公尺以上,與其他滅火設備並用時取最大值。把「二十五公尺\u002F三十公尺\u002F四十公尺」與各自對應的設備放在同一張表上背,是這一章最有效的整理方式。",true,[27,32,36,40,44,48],{"webId":28,"stem":29,"number":30,"year":31,"session":12},"fire-107-1-water-chemical-040","進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",40,107,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-002","自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",2,{"webId":37,"stem":38,"number":39,"year":31,"session":12},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",39,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-003","中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",3,{"webId":45,"stem":46,"number":47,"year":31,"session":12},"fire-107-1-water-chemical-038","依各類場所消防安全設備設置標準之規定，下列何種場所不需設置室外消防栓設備？",38,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-004","密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",4,[53,57,61,65,68],{"webId":54,"year":55,"stem":56,"number":12},"fire-111-1-water-chemical-001",111,"依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":58,"year":59,"stem":60,"number":12},"fire-110-1-water-chemical-001",110,"公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",{"webId":62,"year":63,"stem":64,"number":12},"fire-109-1-water-chemical-001",109,"下列場所何者未達依法應設置滅火器之條件？",{"webId":66,"year":31,"stem":67,"number":12},"fire-107-1-water-chemical-001","撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",{"webId":69,"year":70,"stem":71,"number":12},"fire-106-1-water-chemical-001",106,"依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",1785123167323]