[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-108-1-water-chemical-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-002","fire-108-1-water-chemical-002",108,1,2,"自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",{"A":16,"B":17,"C":18,"D":19},"X=2.8；Y=24；Z=0.01","X=2.8；Y=12；Z=0.1","X=0.28；Y=12；Z=0.1","X=0.28；Y=24；Z=0.01","D",null,[],false,"本題考點：自動撒水設備竣工試驗中，密閉乾式管系「空氣壓試驗」的壓力、時間與容許漏氣三個法定數值。\n【正解理由】依《各類場所消防安全設備設置標準》第 45 條，自動撒水設備竣工時應做加壓試驗，其測試方法準用第 33 條；但密閉乾式管系應併行空氣壓試驗，條文明定「應使空氣壓力達到每平方公分二點八公斤或 0.28MPa 之標準，其壓力持續二十四小時，漏氣減壓量應在每平方公分零點一公斤以下或 0.01MPa 以下為合格」。題目三格皆以 MPa 表示，X 取 0.28、Y 取 24、Z 取 0.01，故選 D。\n【逐項排除】\n(A) X=2.8 是把每平方公分二點八公斤的公斤制數值直接搬進 MPa 欄位，兩套單位相差約十倍，Y 與 Z 雖對仍不合格。\n(B) X 同樣誤用 2.8，Y 又寫成 12 小時，不足條文所定的持續二十四小時，Z=0.1 亦是誤引公斤制的零點一。\n(C) X=0.28 正確，但 Y=12 小時只有法定時間的一半，Z=0.1MPa 更放寬到法定 0.01MPa 的十倍，判定失之過寬。\n(D) 0.28MPa、24 小時、0.01MPa 三值與條文的 MPa 表述完全一致，為正確組合。\n【記憶點】乾式管系空氣壓試驗記「零點二八、二十四、零點零一」，壓力、時間、容許漏氣依序好記。","體例與準用關係：第 45 條把水壓試驗方法「準用第 33 條」，因此濕式管系的驗收基準要回到消防立管的規定——依第 33 條，試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓，並繼續維持二小時無漏水現象為合格。乾式管系之所以要「併行」空氣壓試驗，是因為依第 43 條，密閉乾式的定義為「平時管內貯滿高壓空氣，撒水頭動作時先排空氣，繼而撒水」，管內平時是空氣而非水，若只做水壓試驗，無法檢出微量漏氣造成的壓力衰減，火災時將延誤排氣與撒水。\n單位換算：1 kgf\u002Fcm² 約等於 0.098 MPa，工程上取近似 0.1 MPa。條文採「每平方公分二點八公斤或 0.28MPa」「零點一公斤以下或 0.01MPa 以下」的雙軌寫法，正是這個近似關係；考題最愛把兩套單位交叉組合成誘答，看到 2.8 與 0.28 同時出現時，先確認題目問的是哪一種單位制。\n配套數值對照：與本題常合併命題的是第 55 條——密閉乾式或預動式流水檢知裝置二次側之加壓空氣，其空氣壓縮機為專用，並能在三十分鐘內加壓達二次側配管之設定壓力值；二次側之減壓警報設於平時有人處；撒水頭動作後，流水檢知裝置應在一分鐘內使撒水頭放水；撒水頭並使用向上型。第 44 條則要求二次側配管施予鍍鋅等防腐蝕處理，支管每十公尺傾斜四公分、主管每十公尺傾斜二公分，於明顯易見處設排水閥並標明字樣。\n相關考點：竣工試驗的三組數字（全閉揚程一點五倍／二小時、0.28MPa／二十四小時、0.01MPa）常改寫成是非題或填空題，也常與末端查驗閥、流水檢知裝置的設置規定串成一組出題。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-108-1-water-chemical-003","中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-107-1-water-chemical-040","進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",40,107,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-004","密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-107-1-water-chemical-039","為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-005","開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",5,[53,57,61,65,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-002",111,"有關室外消防栓與室內消防栓之瞄子放水壓力之敘述，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-002",110,"連結送水管之中繼幫浦放水測試時，應從送水口以送水設計壓力送水，並以口徑 21 公厘瞄子在最頂層測試，其放水壓力不得小於 X kgf\u002Fcm2，且放水量不得小於 Y L\u002Fmin。X、Y 分別為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-002",109,"某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",{"webId":66,"year":39,"stem":67,"number":13},"fire-107-1-water-chemical-002","有關連結送水管之送水口設置規定，下列何者錯誤？",{"webId":69,"year":70,"stem":71,"number":13},"fire-106-1-water-chemical-002",106,"依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",1785123167332]