[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-108-1-water-chemical-003":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-003","fire-108-1-water-chemical-003",108,1,3,"中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",{"A":16,"B":17,"C":18,"D":19},"X=5；Y=10","X=6；Y=20","X=6；Y=10","X=10；Y=5","C",null,[],false,"本題考點：撒水頭配置規定中，天花板高度達到多少公尺時必須改採放水型撒水頭。\n【正解理由】依《各類場所消防安全設備設置標準》關於撒水頭配置之規定，中央主管機關認定儲存大量可燃物之場所，天花板高度超過六公尺者，以及其他場所天花板高度超過十公尺者，應採用放水型撒水頭。理由在於密閉式撒水頭靠感熱元件動作，天花板越高，煙氣抵達時已被冷空氣稀釋而難以動作。X 為 6、Y 為 10，故選 C。\n【逐項排除】\n(A) X=5 過低，五公尺並非法定分界，一般場所在十公尺以下仍得使用密閉式撒水頭，此值會過早要求放水型。\n(B) X=6 正確，但 Y=20 錯誤；二十公尺是探測器裝置面高度的免設門檻，屬警報設備，與撒水頭無關。\n(C) 儲存大量可燃物之場所六公尺、其他場所十公尺，與法定分界完全相符，為正確組合。\n(D) 把兩個數值對調成十公尺與五公尺，等於放寬可燃物倉庫、收緊一般場所，與「可燃物多者從嚴」的方向相反。\n【記憶點】可燃物多的先從嚴——六公尺就要放水型，其他場所可撐到十公尺。","立法脈絡：放水型撒水頭之所以以天花板高度設門檻，是因為密閉式撒水頭靠感熱元件動作，火羽流上升途中不斷捲入冷空氣，天花板越高，煙氣到達時的溫度越低，動作時間被大幅拉長；即使動作，撒出的水滴也可能在下降途中蒸發或被上升氣流吹散，無法到達燃燒面。放水型撒水頭改以大水滴放射或可動式掃射方式直接射向火點，正是為了克服高大空間的這兩個障礙。\n數值配套：依第 50 條，撒水頭之放水量每分鐘應在八十公升以上（設於高架倉庫者為一百十四公升），放水壓力在每平方公分一公斤以上或 0.1MPa 以上；小區劃型撒水頭之放水量則為每分鐘五十公升以上。同條第二項另定放水型撒水頭之放水量，應達防護區域每平方公尺每分鐘五公升以上，但儲存可燃物場所應達每平方公尺每分鐘十公升以上。放水型改採「單位面積放水量」而非「每顆放水量」，是與密閉式最大的體例差異，也是常見誘答點。\n易混淆高度對照：本題的十公尺與二十公尺極易互相干擾。依第 116 條，探測器除火焰式外，裝置面高度超過二十公尺者得免設探測器；六公尺、十公尺是撒水頭改採放水型的分界，二十公尺則是探測器的免設分界，兩者分屬滅火設備與警報設備，記憶時務必連同設備類別一起背。\n相關考點：命題者常把「天花板高度」與「裝置面高度」兩個名詞交替使用製造混淆，作答時先辨識題目問的是滅火設備還是警報設備，再套對應的高度門檻。另一個爭點是條文用語為「中央主管機關認定儲存大量可燃物之場所」，並非任何倉庫都自動適用六公尺門檻，需經認定始有適用。",true,[28,32,36,39,43,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-002","自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",2,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-004","密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",4,{"webId":37,"stem":38,"number":12,"year":11,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-108-1-water-chemical-005","開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",5,{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-107-1-water-chemical-040","進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",40,107,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-006","使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",6,[53,57,61,65,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-003",111,"某公共危險物品場所設置室外消防栓設備，在裝置全部消防栓數量 5 支時，其所需之水源容量至少應為多少立方公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-003",110,"公共危險物品等場所消防設計及消防安全設備，顯著滅火困難場所之室外儲槽場所，儲存硫磺，應設置何種滅火設備？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-003",109,"某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",{"webId":66,"year":47,"stem":67,"number":13},"fire-107-1-water-chemical-003","水霧滅火設備之水源容量規定，下列何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-106-1-water-chemical-003",106,"有關滅火器設置間距之規定，下列何者錯誤？",1785123167349]