[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-108-1-water-chemical-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":51,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-004","fire-108-1-water-chemical-004",108,1,4,"密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",{"A":16,"B":17,"C":18,"D":19},"密閉乾式或預動式流水檢知裝置一次側之加壓空氣，其空氣壓縮機為專用，並能在 30 分鐘內，加壓達流水檢知裝置二次側配管之設定壓力值","流水檢知裝置一次側之減壓警報設於平時有人處","撒水頭動作後，流水檢知裝置應在 30 秒內，使撒水頭放水","撒水頭使用向上型。但配管能採取有效措施者，不在此限","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》中密閉乾式與預動式自動撒水設備之特別規定，包含加壓空氣、減壓警報、放水時限與撒水頭裝設方向四項要件。\n【正解理由】依《各類場所消防安全設備設置標準》關於密閉乾式、預動式自動撒水設備之規定，因流水檢知裝置二次側配管平時為加壓空氣而非充水，若撒水頭朝下裝設，管內凝結水易積存於撒水頭處造成腐蝕與動作不良，故明定撒水頭應使用向上型，惟配管能採取有效排水等措施者不在此限，故選 D。\n【逐項排除】\n(A) 錯在「一次側」。應加壓的是流水檢知裝置「二次側」配管的空氣，一次側為加壓水側；專用空氣壓縮機須於 30 分鐘內達二次側設定壓力值。\n(B) 錯在「一次側」。減壓警報係監視二次側空氣壓力是否異常下降，藉以察覺配管洩漏或撒水頭誤動作，故設於二次側並設在平時有人之處所。\n(C) 錯在時間值。撒水頭動作後，流水檢知裝置應在 1 分鐘內使撒水頭放水，30 秒並非法定值；乾式設備因須先排空管內空氣，本即無法要求過短之放水時間。\n(D) 敘述與規定相符，向上型為原則、配管有有效措施者得為例外，是正解。\n【記憶點】乾式與預動式的口訣：空氣在二次側、減壓警報在二次側、放水 1 分鐘內、撒水頭朝上。","密閉乾式與預動式自動撒水設備之所以另立特別規定，源自其配管狀態與濕式截然不同。濕式設備二次側常時充水，撒水頭一動作立刻放水；乾式則在二次側充填加壓空氣，撒水頭動作後空氣須先洩出，流水檢知裝置才會開放使水前進到撒水頭，中間存在無可避免的延遲。法規因而設下「1 分鐘內放水」的上限，用意是限制這段空管延遲不得過長，否則初期火勢已擴大。預動式再多一層感知裝置連動，須探測器先動作開放預動閥、撒水頭再動作才放水，屬於「雙重確認」設計，主要用於電腦機房、圖書館、博物館等最忌誤放水之場所。\n\n加壓空氣的規定同樣有其道理。空氣壓縮機明定為專用，是避免與廠內生產用空氣系統共用而在需要時無氣可用；30 分鐘內須加壓達設定壓力值，則是限制系統於放水後或維修復歸後的回復時間，使設備不致長時間處於失能狀態。二次側減壓警報設在平時有人處所，用意是讓配管微量洩漏或撒水頭遭碰撞損壞能被即時察覺，這也是乾式系統最常見的失效模式。\n\n撒水頭向上型的要求，關鍵在凝結水。加壓空氣進入配管後會隨溫度變化析出水分，若採向下型，凝結水會積在撒水頭與短立管處，長期造成腐蝕、結垢，寒冷地區甚至結凍阻塞。改採向上型並使配管具適當洩水坡度，水分可回流至洩水裝置排除。所謂「配管能採取有效措施者不在此限」，即指採用乾式豎管或具排水構造之特殊撒水頭等設計。\n\n易混淆概念對照：密閉濕式（二次側充水、反應最快）、密閉乾式（二次側充氣、有延遲、防凍）、預動式（充氣加探測器連動、防誤放水）、開放式（撒水頭無感熱元件，一齊開放閥開啟即全區放水，用於危險性高的場所）。四者常以「何者二次側為加壓空氣」「何者需與探測器連動」交叉命題。\n\n相關考點連結：同一條文亦常考流水檢知裝置每一樓層之設置、警報逆止閥、末端查驗閥之位置與試驗方法，數值與方向性記憶是得分關鍵。",true,[28,32,36,40,44,47],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-003","中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",3,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-005","開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",5,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-002","自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",2,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-006","使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",6,{"webId":45,"stem":46,"number":12,"year":11,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"webId":48,"stem":49,"number":50,"year":11,"session":12},"fire-108-1-water-chemical-007","有關水霧滅火設備，下列設置規定何者錯誤？",7,[52,56,60,64,68],{"webId":53,"year":54,"stem":55,"number":13},"fire-114-1-water-chemical-004",114,"依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",{"webId":57,"year":58,"stem":59,"number":13},"fire-112-1-water-chemical-004",112,"依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",{"webId":61,"year":62,"stem":63,"number":13},"fire-111-1-water-chemical-004",111,"裝置於舞臺之開放式自動撒水設備，依規定下列何者正確？",{"webId":65,"year":66,"stem":67,"number":13},"fire-110-1-water-chemical-004",110,"下列有關室內消防栓設備之規定，何者錯誤？",{"webId":69,"year":70,"stem":71,"number":13},"fire-109-1-water-chemical-004",109,"供集會堂使用之舞臺，應設置何種自動撒水設備？",1785123167363]