[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-006","fire-108-1-water-chemical-006",108,1,6,"使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",{"A":16,"B":17,"C":18,"D":19},"管徑在 50 毫米以上","查驗閥依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端","查驗閥之一次側設有與撒水頭同等放水性能之限流孔，二次側設壓力表","距離地板面之高度在 1.5 公尺以下，並附有排水管裝置，並標明末端查驗閥字樣","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 56 條，使用密閉式撒水頭之自動撒水設備末端查驗閥的四款配置規定——管徑、裝設位置、一二次側配件與離地高度。\n【正解理由】第 56 條第二款明定「查驗閥依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端」；接在最遠、壓力最低點，是因為該點若能達到規定放水壓力，同一配管系統其餘各點必然合格，故選 B。\n【逐項排除】\n(A) 錯在管徑。第 56 條第一款為「管徑在二十五毫米以上」，並非 50 毫米；50 毫米是配管主管常見的數字，屬命題者刻意布置的混淆值。\n(B) 正確，與第 56 條第二款逐字相符；一棟建築物設有數個流水檢知裝置時，每一配管系統各自配置一個末端查驗閥。\n(C) 一次側與二次側顛倒。第 56 條第三款為「一次側設壓力表，二次側設有與撒水頭同等放水性能之限流孔」，壓力表在上游量測供水壓力，限流孔在下游模擬一個撒水頭動作放水。\n(D) 高度數值錯誤。第 56 條第四款為「距離地板面之高度在二點一公尺以下」，不是 1.5 公尺；其後附排水管裝置並標明末端查驗閥字樣的敘述則屬正確。\n【記憶點】末端查驗閥記「25 毫米、最遠最低、上表下孔、2.1 公尺」。","密閉式撒水頭平時封閉，無法像開放式那樣以實際撒水驗證系統，因此第 56 條要求在配管最不利點裝一個末端查驗閥，並以「與撒水頭同等放水性能之限流孔」模擬一個撒水頭動作，等於替整個系統留一個可重複操作的體檢孔。四款規定各有其道理：管徑二十五毫米對應單一撒水頭的流量級距；接在放水壓力最低之最遠支管末端，是取水力上最不利點做保守驗證；一次側（靠加壓送水裝置一側）設壓力表以讀取供水壓力，二次側（下游）設限流孔以固定流量；離地二點一公尺以下並附排水管，則使查驗閥處於可操作高度且放出的水有去處。\n《消防安全設備及必要檢修項目檢修基準》第四章自動撒水設備「三、綜合檢查（一）密閉式撒水設備」承接同一設計：切換成緊急電源供電後，於最遠支管末端打開查驗閥，確認應設有與撒水頭同等放水性能之限流孔，並對加壓送水裝置最近及最遠的末端查驗閥各進行放水試驗；判定方法不論幫浦方式或重力水箱、壓力水箱方式，均明列「末端查驗管之放水壓力應在 1 kgf\u002Fcm² 以上 10 kgf\u002Fcm² 以下」（此判定值依線上可得之 109.08.21 版檢修基準，體例與判定方式可對照理解）。壓力下限呼應第 50 條撒水頭放水壓力每平方公分一公斤以上、放水量每分鐘八十公升以上的要求，上限則避免壓力過高造成撒水型態不良或配管負擔。\n易混淆處：末端查驗閥驗的是「系統末端能否放水」，與流水檢知裝置本身的試驗閥，以及第 55 條密閉乾式所定「撒水頭動作後，流水檢知裝置應在一分鐘內，使撒水頭放水」分屬不同標的。另依第 211 條，公共危險物品場所之自動撒水設備，其末端查驗閥設置準用第 56 條，數值完全一致。相關考法幾乎都在四款數值互換：把 25 毫米換成 50、2.1 公尺換成 1.5，或把壓力表與限流孔對調，記牢原文順序即可全數擋下。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-005","開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-007","有關水霧滅火設備，下列設置規定何者錯誤？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-004","密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-008","移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-003","中央主管機關認定儲存大量可燃物之場所天花板高度超過 X 公尺，或其他場所天花板高度超過 Y 公尺者，應採用放水型撒水頭。X、Y 分別為何？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-009","有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",9,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-006",111,"消防幫浦之防止水溫上升用排放裝置，防止水溫上升用之排水管內之流水量，當幫浦在全閉狀態下連續運轉時，不使幫浦內部水溫，升高至攝氏多少度以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-006",110,"有關撒水頭位置裝置之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-006",109,"消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-006",107,"泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-006",106,"全區放射二氧化碳滅火設備進行綜合檢查時，如為低壓式儲存系統，在放射試驗時需放射多少藥劑量？",1785123167380]