[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-009","fire-108-1-water-chemical-009",108,1,9,"有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",{"A":16,"B":17,"C":18,"D":19},"1.5","1.2","1.0","0.9","B",null,[],false,"本題考點：二氧化碳滅火設備採全區放射方式時，總機室這類電氣類場所每立方公尺防護區域所需之滅火藥劑量。\n【正解理由】依《各類場所消防安全設備設置標準》關於二氧化碳滅火設備滅火藥劑量之規定，全區放射方式所需藥劑量依防護區域之用途性質與體積列表核算；總機室與電信機械室屬以電子通信設備為主的場所，在表中單獨列為一級，每立方公尺防護區域所需滅火藥劑量為一點二公斤，故選 B。\n【逐項排除】\n(A) 一點五公斤並非總機室的表列值；此類電氣場所的藥劑量已由表格單獨列出，不得任意取更高的數值套用。\n(B) 總機室與電信機械室同屬表列的電氣類場所，每立方公尺取一點二公斤，與題意相符，為正確答案。\n(C) 一點零公斤屬一般防護區域在體積較小時的量級，總機室另有專屬且較嚴格的表列值，不能套用一般場所數字。\n(D) 零點九公斤是一般防護區域體積增大後遞減的量級，用於總機室會低於專屬表列的一點二公斤，藥劑量不足。\n【記憶點】總機室與電信機械室是二氧化碳的「一點二」級，比一般場所嚴，放射時間也拉長。","為什麼電氣場所要單獨列一級：二氧化碳滅火以稀釋氧濃度的窒息作用為主、兼有部分冷卻效果，不導電且放射後汽化不留殘渣，因此長期被指定用於總機室、電信機械室、電腦室、變電室等以電子設備為主的空間。這類場所可燃物總量雖不多，但設備密集，纜線與絕緣材燃燒時容易形成陰燃與深層火災；加上機房為求隔音防塵常設夾層與高架地板，藥劑不易均勻擴散到火點，故單位體積藥劑量訂得比一般防護區域高，放射時間也相應放寬，讓藥劑有時間滲入夾層並維持滅火濃度。\n配套安全規定：第 85 條明定全區或局部放射方式防護區域內之通風換氣裝置，應在滅火藥劑放射前停止運轉。機房幾乎都配有大風量空調，若不先停止運轉，藥劑會被持續抽離，設計濃度根本無法建立，這正是本條在電氣場所格外重要的理由。\n放射方式的體例差異：全區放射方式以「單位體積」乘以防護區域體積核算藥劑量；局部放射方式則改以防護對象表面積或假想防護空間核算，兩者思路完全不同，作答時須先辨識題目給的是哪一種放射方式，再套用對應算式，切勿把體積法直接用在局部放射的題目上。判斷訣竅是看題目給的是「防護區域體積」還是「防護對象表面積」，前者走全區、後者走局部，題幹只要出現「總機室」「電信機械室」等空間名稱，通常就是全區放射。\n考點延伸：二氧化碳滅火設備的題目通常成組出現——藥劑量、放射時間、噴頭放射壓力、儲存容器充填比、啟動用氣體容器規格等，命題者常在同一份考卷連出數題。把「場所類別」與各項數值配成一張橫向對照表記憶，投資報酬率最高，也最能避免把一般場所與電氣場所的數字互相張冠李戴。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-008","移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-010","有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-007","有關水霧滅火設備，下列設置規定何者錯誤？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-011","二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-006","使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-012","主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-009",111,"泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-009",110,"依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-009",109,"進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-009",107,"某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-009",106,"如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",1785123167406]