[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-011","fire-108-1-water-chemical-011",108,1,11,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",{"A":16,"B":17,"C":18,"D":19},"1.1","1.4","1.5","1.9","C",null,[],false,"本題考點：二氧化碳滅火設備使用氣體啟動者，其啟動用氣體容器之充填比下限；充填比指容器內容積（公升）與液化氣體重量（公斤）之比值。\n【正解理由】依《各類場所消防安全設備設置標準》二氧化碳滅火設備使用氣體啟動者之規定，啟動用氣體容器之充填比在一點五以上；《消防安全設備及必要檢修項目檢修基準》第十一章性能檢查之共同事項亦列「二氧化碳滅火設備之充填比應在 1.5 以上」，故選 C。\n【逐項排除】\n(A) 1.1 過小。充填比越小代表同一容器裝入越多藥劑，1 公升容器可裝約 0.91 公斤，裝填過滿、受熱膨脹餘裕不足。\n(B) 1.4 仍未達門檻。1 公升容器可裝約 0.71 公斤，與 1.1 同屬其他充填比規定常見的數字。\n(C) 1.5 正確，與檢修基準所列判定值一致，且與題示一公升、零點六公斤相容。\n(D) 1.9 過大。1 公升容器僅能充填約 0.53 公斤，反而牴觸「零點六公斤以上」，兩項下限互相矛盾。\n【演算步驟】F＝內容積 V（公升）÷液化氣體重量 W（公斤）。代入題示下限 V＝1 公升、W＝0.6 公斤：F＝1÷0.6≈1.67。門檻 1.5 時最大充填量 W＝1÷1.5≈0.67 公斤，0.6≤0.67 相容；門檻 1.9 時 W＝1÷1.9≈0.53 公斤＜0.6 公斤，矛盾。故下限為 1.5。\n【記憶點】啟動用氣體容器「一公升、零點六公斤、充填比一點五」。","充填比是容器內容積（公升）除以所充填液化氣體重量（公斤）的比值，物理意義是「每公斤藥劑分配到多少容器空間」，數值越大代表容器越空。二氧化碳臨界溫度約攝氏三十一點一度，常溫下以高壓液化狀態儲存，若裝填過滿，環境溫度上升時液相膨脹會使容器內壓急遽攀升，因此法規以充填比訂下限，實質上是訂裝填量的上限——這也是為何條文寫「充填比在一點五以上」而非「以下」，初學者最容易在這裡反向記錯。\n啟動用氣體容器是氣壓式啟動的動力來源：它本身不是滅火藥劑，而是以小容器的二氧化碳經操作管推動容器閥開放裝置與選擇閥，再由主儲存容器放出藥劑。可與《各類場所消防安全設備設置標準》第 110 條的乾粉版本對照記憶，該條明定啟動用氣體容器能耐每平方公分二百五十公斤或 25MPa 之壓力、內容積有零點二七公升以上、所儲存之氣體量在一百四十五公克以上、充填比在一點五以上，且不得兼供防護區域之自動關閉裝置使用。兩者的容器規模不同（二氧化碳為一公升、零點六公斤；乾粉為零點二七公升、一百四十五公克），充填比門檻卻同為一點五以上；以乾粉數值反算，零點二七公升除以零點一四五公斤約為一點八六，同樣滿足一點五的下限，可見這是同一套安全裝填邏輯。\n《消防安全設備及必要檢修項目檢修基準》第十一章之性能檢查則規定藥劑量的量測方式：以台秤測定計、水平液面計或鋼瓶液面計量得藥劑量後，與重量表或圖面明細表核對，判定其差值應在充填值 10％ 以下，並在共同事項中列出「二氧化碳滅火設備之充填比應在 1.5 以上」。線上可得之最早版本為 109.08.21，晚於本題考試日，體例與判定方式可資對照。常見考法是把充填比與內容積、藥劑重量三個數值任意互換，或以其他容器的充填比數字替換，記住「一公升、零點六公斤、一點五」這組即可辨識。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-010","有一電信機械室，設置二氧化碳滅火設備，採全區放射方式，其所核算之滅火藥劑量應於多少秒內全部放射完畢？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-012","主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-009","有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-013","依各類場所消防安全設備設置標準之規定，乾粉滅火設備配管及閥類，下列設置規定何者錯誤？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-008","移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-014","依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",14,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-011",107,"加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-011",106,"鹵化烴滅火設備進行性能檢查時，控制裝置之遲延裝置檢查項目，於操作啟動按鈕後至容器閥開放裝置動作，其所需時間應為：",1785123167432]