[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-019","fire-108-1-water-chemical-019",108,1,19,"依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",{"A":16,"B":17,"C":18,"D":19},"1","2","3","5","C",null,[],false,"本題考點：以水平液面計測定氣體系滅火藥劑量時，放射線源鈷 60 的有效使用年限。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第十一章惰性氣體滅火設備「二、性能檢查」滅火藥劑量之注意事項，以水平液面計測定時，不得任意卸取放射線源（鈷 60），萬一有異常時應即時連絡專業處理單位，且「鈷 60 有效使用年限約為 3 年，如已超過時，應即時連絡專業單位處理或更換」。相同文字在第十章海龍滅火設備、第十二章鹵化烴滅火設備一致出現，故選 C。\n【逐項排除】\n(A) 1：基準未以一年為鈷 60 之有效使用年限；放射源並非逐年更換，而是依其強度隨時間衰減的特性，另定約三年的年限。\n(B) 2：同樣不是注意事項所載年限，易與其他檢查週期或年度抽樣分配的年數相混。\n(C) 3：與原文「鈷 60 有效使用年限約為 3 年」相符，超過即應連絡專業單位處理或更換，為本題正解。\n(D) 5：本項注意事項並無此年限；同段落的其他數字為藥劑量差值應在充填值 10％以下、容器重量約 150 公斤，均非年限。\n【記憶點】水平液面計靠鈷 60 射源，年限約 3 年；射源不得自行卸取，使用者並須取得原子能主管機關許可登記。","氣體系滅火設備的藥劑量檢查有三種方法，各有適用場合。台秤測定法先將裝設在容器閥之容器閥開放裝置、連接管、操作管及容器固定器具取下，把容器置於台秤上測定其重量計算至小數點第一位，再扣除容器閥及容器重量得藥劑量，最直接，但容器重量約 150 公斤，有傾倒或操作時應加以注意。水平液面計法利用鈷 60 射源與探針，使容器維持平常之狀態置於液面計探針與放射源之間，緩緩使檢出部上下移動，當儀表指針振動差異較大時即為藥劑存量高度，再以專用之換算尺換算藥劑量；因涉及放射源，不得任意卸取，使用具放射源者應取得主管機關之許可登記，射源強度亦會隨時間衰減，故基準訂有約 3 年的有效使用年限。鋼瓶液面計法則打開保護蓋緩慢抽出表尺，當表尺被鋼瓶內浮球之磁性吸引而停頓時讀取刻度，再對照各廠商提供之專用換算表讀取藥劑重量，並需考慮溫度變化造成之影響。\n判定方法統一為：將藥劑量之測定結果與重量表或圖面明細表核對，其差值應在充填值 10％以下；二氧化碳滅火設備之充填比應在 1.5 以上。測量後應將容器號碼、充填量記載於重量表及檢查表上；當滅火藥劑量或容器內壓減少時，應迅即進行調查並採取必要之措施。\n外觀檢查則另有一組環境條件：設在專用鋼瓶室之鋼瓶應有適當之固定措施，設於防護區域內者應置於不燃性或難燃性材料製成之防護箱內；設置場所應具適當採光、無檢查及使用上之障礙，周圍濕度未過高且溫度在 40℃ 以下，並無遭日光曝曬、雨水淋濕之虞。\n相關考點會延伸到低壓式二氧化碳的警報與安全裝置動作壓力：破壞板動作壓力 37kgf\u002Fcm²、安全閥起噴壓力 25kgf\u002Fcm²、壓力上升警報 23kgf\u002Fcm²、冷凍機啟動 22kgf\u002Fcm²、冷凍機停止 21kgf\u002Fcm²、壓力下降警報 19kgf\u002Fcm²，常用壓力範圍即落在冷凍機啟停之間，這組數字常以排序題形式出現。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-018","依各類場所消防安全設備檢修及申報作業基準，固定式泡沫滅火設備（低發泡）綜合檢查，設置泡沫頭者，每次選擇全部放射區域數之若干%以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-020","公共危險物品等場所之滅火設備分類，下列敘述何者錯誤？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-017","依各類場所消防安全設備檢修及申報作業基準，有關室內消防栓設備之第一種消防栓水帶及瞄子檢查方法，製造年份超過 10 年或無法辨識製造年份之水帶，應將消防水帶兩端之快速接頭連接於耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。則 X+Y 為若干？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-021","某鍋爐房樓地板面積為 20 m×15 m，依法其所需之滅火效能值為何？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-016","依各類場所消防安全設備檢修及申報作業基準，公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之室內消防栓，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。則 X+Y 為若干？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-022","有關潔淨藥劑氣體滅火設備滅火藥劑主要成分之敘述，下列何者正確？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-019",111,"下列有關滅火器性能檢查之敘述，何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-019",109,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-019",107,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-019",106,"進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",1785123167513]