[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-108-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-108-1-水與化學系統消防安全設備概要-031","fire-108-1-water-chemical-031",108,1,31,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"0.85 以上、1.45 以下","1.05 以上、1.75 以下","1.1 以上、1.9 以下","1.5 以上、2.5 以下","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 102 條乾粉滅火藥劑儲存容器的充填比級距表。\n【正解理由】第 102 條第一款之表明定充填比：第一種乾粉為零點八五以上、一點四五以下；第二種乾粉或第三種乾粉為一點零五以上、一點七五以下；第四種乾粉為一點五以上、二點五以下。題目問第四種乾粉，對應級距即 1.5 以上、2.5 以下，故選 D。\n【逐項排除】\n(A) 0.85 以上、1.45 以下是第一種乾粉（主成分碳酸氫鈉）的充填比，種別對錯位。\n(B) 1.05 以上、1.75 以下是第二種乾粉或第三種乾粉共用的級距，同樣不是第四種。\n(C) 1.1 以上、1.9 以下不屬乾粉表中任何一格；1.1 與 1.9 分別是第 87 條二氧化碳滅火藥劑儲存容器低壓式的下限與高壓式的上限，屬跨設備拼湊的誘答。\n(D) 1.5 以上、2.5 以下與第 102 條第一款表中第四種乾粉欄逐字相符，為本題應選者。\n【記憶點】乾粉充填比由小到大：一種 0.85–1.45、二三種 1.05–1.75、四種 1.5–2.5。","充填比的定義見第 87 條第二項：指容器內容積（公升）與液化氣體重量（公斤）之比值，也就是每公斤藥劑分到多少公升的容器空間。比值越大，代表同樣重量的藥劑占用越大的容器容積；比值訂上下限，是為了同時避免充填過密（壓力異常、放射不順）與過鬆（容器浪費、壓力不足）。理解這個定義，就能看懂為什麼第四種乾粉的級距整體最高——第四種乾粉主成分為碳酸氫鉀及尿素化合物，單位體積所裝的重量相對較少，需要較大的容器空間。\n三張「種別表」建議一起背，因為考題常混搭：第 99 條藥劑量（第一種 0.6／4.5、第二種 0.36／2.7、第三種 0.36／2.7、第四種 0.24／1.8）、第 111 條移動式每分鐘放射量（第一種 45、第二或第三種 27、第四種 18 kg\u002Fmin）、第 102 條充填比（0.85–1.45／1.05–1.75／1.5–2.5）。可以觀察到一個趨勢：從第一種到第四種，單位體積所需藥劑量與放射量遞減，充填比則遞增，因為第四種乾粉的滅火效率最高、用量最省。\n第 102 條除充填比外，還規定儲存場所應置於防護區域外、置於溫度攝氏四十度以下且溫度變化較少處、不得置於有日光曝曬或雨水淋濕之處；儲存容器於明顯處所標示充填藥劑量、滅火藥劑種類、最高使用壓力（限於加壓式）、製造年限及製造廠商；蓄壓式儲存容器內壓在每平方公分十公斤以上或 1 MPa 以上者，設符合 CNS 一○八四八及一○八四九規定之容器閥；並應設置排出殘留氣體之排出裝置與處理配管殘留藥劑之清洗裝置。\n易混淆對照：二氧化碳滅火藥劑儲存容器依第 87 條，充填比在高壓式為一點五以上一點九以下、低壓式為一點一以上一點四以下；低壓式並應設液面計、壓力表及壓力警報裝置，壓力在每平方公分二十三公斤以上或每平方公分十九公斤以下時發出警報，且應設自動冷凍機維持容器內部溫度於攝氏零下二十度以上、零下十八度以下。乾粉與二氧化碳的充填比數字近似而分屬不同條文，是本題型最主要的失分來源。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-108-1-water-chemical-030","依滅火器設置規定，下列何者錯誤？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-108-1-water-chemical-032","依法令規定下列場所何者應設置滅火器？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-108-1-water-chemical-029","有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-108-1-water-chemical-033","某百貨商場（10 樓以下）內設有一般反應型撒水頭 15 個，試問其消防幫浦最低出水量應為何？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-108-1-water-chemical-028","依法令規定在應設水霧、泡沫、乾粉、二氧化碳滅火設備之場所，但外牆開口面積（常時開放部分）達該層樓地板面積百分之多少以上者，上列滅火設備得採移動式設置？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-108-1-water-chemical-034","依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-031",107,"惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-031",106,"B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",1785123167636]