[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-006","fire-109-1-alarm-evacuation-006",109,1,6,"差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",{"A":16,"B":17,"C":18,"D":19},"120 秒","90 秒","60 秒","30 秒","D",null,[],false,"本題考點：《各類場所消防安全設備檢修及申報作業基準》火警自動警報設備之性能檢查中，感熱型局限型探測器加熱試驗的動作時間判定。\n【正解理由】該基準在火警自動警報設備之性能檢查訂有加熱試驗程序：對定溫式及差動式（再用型）局限型探測器，使用加熱試驗器對探測器加熱，確認至動作之時間及警戒區域之表示是否正常；其判定所引之探測器動作時間表中，差動式局限型不分一種、二種均為三十秒，定溫式局限型則為特種四十秒、一種六十秒、二種一百二十秒。因此差動式局限型自加熱起應在三十秒內動作，故選 D。\n【逐項排除】\n(A) 120 秒：是同表中定溫式局限型二種的動作時間，不是差動式局限型的判定值。\n(B) 90 秒：屬偵煙式局限型（離子式、光電式）三種加煙試驗的動作時間，與感熱型加熱試驗無涉。\n(C) 60 秒：為定溫式局限型一種的動作時間，也是偵煙式局限型二種加煙試驗的時間，最容易與本題互相混淆。\n(D) 30 秒：差動式局限型一種、二種共同的動作時間，與題意相符。\n【記憶點】差動式局限型一律三十秒；定溫式依特種、一種、二種拉長為四十、六十、一百二十秒。","該基準對火警自動警報設備採「外觀檢查、性能檢查、綜合檢查」三段體例，本題落在性能檢查的探測器項目。感熱型局限型中，定溫式（非再用型）因加熱即破壞，改按選取檢查數量表抽驗：設置數量 1 至 10 個取 1 個、11 至 50 個取 2 個、51 至 100 個取 4 個、101 個以上取 7 個，再依再用型的方式進行加熱試驗；這是級距表，不是固定比例，抽驗數不會隨面積或數量等比放大。動作時間的判定另有蓄積性能的加成規定：對感熱式探測器加熱時，應在動作時間表所示時間，加上蓄積式中繼器或受信總機設定之蓄積時間（合計最大二十秒）內動作；對偵煙式探測器加煙時，非蓄積型為表列時間加蓄積時間（合計最大六十秒），蓄積型再加上標稱蓄積時間並外加五秒；火焰式探測器以動作試驗器之紅外線或紫外線照射時，為三十秒加蓄積時間（最大二十秒）。蓄積性能檢查的選取個數同樣是級距：火警分區五十以下各取一個、五十一以上各取二個，且應輪流選取並在圖面或檢查表註記位置。同一設備的外觀檢查則不看時間而看狀態：以目視確認探測器有無變形、腐蝕、脫落，確認設置後有無因用途變更、隔間變更形成之未警戒部分，感知區域之種別與個數是否符合探測區域及裝置高度，並確認有無被塗漆、光電式分離型受光部有無日光直射等影響性能之顧慮。相關考點連結：綜合檢查則要求不復舊地使任意五回路（不滿五回路者為全部回路）進行火災動作表示試驗，並在緊急電源或預備電源供電狀態下確認火災表示與音響鳴動；地區音響裝置之音壓於距設置位置中心一公尺處量測，應在九十分貝以上，八十五年六月三十日前取得建造執照者為八十五分貝。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-005","差動式局限型探測器係利用下列何構件，來防止設置場所因正常溫度變化而造成火災誤報？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-007","除火焰式探測器外，一般局限型探測器裝設時，依各類場所消防安全設備設置標準之規定，不得傾斜幾度以上？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-004","某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-008","緊急照明燈在地面之水平面照度，使用低照度測定用光電管照度計測得之值，在地下建築物之地下通道，其地板面應在 X 勒克司（Lux）以上，其他場所應在 Y 勒克司（Lux）以上。其中 X， Y 值為何？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-003","瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-009","有關避難方向指示燈裝設之敘述，下列何者錯誤？",9,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-006",110,"緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-006",108,"探測器應依裝置場所高度選擇探測器種類裝設，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-006",107,"下列何種使用瓦斯之場所，應設置瓦斯漏氣火警自動警報設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-006",106,"樓梯、斜坡通道、昇降機之昇降路及管道間等場所，其頂層相差在二層以下、水平距離多少範圍內，視為一火警分區？",1785123171367]