[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-007":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-007","fire-109-1-alarm-evacuation-007",109,1,7,"除火焰式探測器外，一般局限型探測器裝設時，依各類場所消防安全設備設置標準之規定，不得傾斜幾度以上？",{"A":16,"B":17,"C":18,"D":19},"60","45","30","15","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 115 條探測器裝置位置中，局限型探測器的傾斜角度上限。\n【正解理由】第 115 條第五款明定「局限型探測器之裝置，不得傾斜四十五度以上。但火焰式探測器，不在此限」。題幹已把火焰式排除，所問即為一般局限型的四十五度界線；傾斜角度過大時，感熱室或偵煙室的入煙、入熱路徑會偏離設計狀態，感知時間隨之延遲，故條文以四十五度為限，故選 B。\n【逐項排除】\n(A) 60：大於條文所定之四十五度，若以六十度為界，等於把條文明文的限度往上放寬。\n(B) 45：與第 115 條第五款文字完全一致，是不得達到的傾斜界線。\n(C) 30：條文並未以三十度為界；此數值易與同標準第 120 條「探測器下端裝設在裝置面下方三十公分範圍內」的三十公分互相混淆，規範對象與單位都不同。\n(D) 15：遠低於條文所定限度，傾斜十五度仍在合格範圍內，不是不得超過的界線。\n【記憶點】局限型傾斜以四十五度封頂，只有火焰式探測器不受此限。","第 115 條共五款，是探測器裝置位置的總則：一、天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；二、牆上設有出風口時，應距離該出風口一點五公尺以上，但該出風口距天花板在一公尺以上時不在此限；三、天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內；四、局限型探測器以裝置在探測區域中心附近為原則；五、局限型不得傾斜四十五度以上，但火焰式不在此限。前三款處理的是氣流干擾，後兩款處理的是感知面朝向，合起來就是「別讓空調搶走火災的熱與煙」。火焰式為何能豁免傾斜限制？第 124 條給了答案：火焰式係以標稱監視距離涵蓋距樓地板面一點二公尺範圍內之空間，屬光學監視而非等待熱氣流上升，故其重點在裝設於天花板、樓板或牆壁且不得有障礙物妨礙探測、應設在無日光照射之處（設有遮光功能可避免探測障礙者不在此限），角度只要監視空間涵蓋得到即可。易混淆對照：第 117 條規範的是「不得設置的場所」而非角度，偵煙式或熱煙複合式局限型不得設於塵埃粉末或水蒸氣大量滯留、散發腐蝕性氣體、廚房等平時煙會滯留、顯著高溫、排放廢氣大量滯留、煙會大量流入、會結露等處所；火焰式另不得設於用火設備火焰外露之處所；同條末段並以表格方式，就前述八種場所狀況列出可選設的探測器種別，可見立法方式是「先禁後導」，而非一律不得設置任何探測器。條號與款次是本科高頻考點，記憶時把「一點五公尺、一公尺、四十五度」三個數字綁在第 115 條一起背。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-006","差動式局限型探測器進行性能檢查時，使用加熱式試驗器加熱確認動作時間，加熱後到探測器動作應在多少時間以內？",6,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-008","緊急照明燈在地面之水平面照度，使用低照度測定用光電管照度計測得之值，在地下建築物之地下通道，其地板面應在 X 勒克司（Lux）以上，其他場所應在 Y 勒克司（Lux）以上。其中 X， Y 值為何？",8,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-005","差動式局限型探測器係利用下列何構件，來防止設置場所因正常溫度變化而造成火災誤報？",5,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-009","有關避難方向指示燈裝設之敘述，下列何者錯誤？",9,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-004","某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",4,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-010","緩降機之設置應保有必要操作面積（不含避難器具所占面積），其相關規定下列何者正確？",10,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-007",110,"下列何種火警探測器在認可作業中須進行粉塵試驗？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-007",108,"有關無線電通信輔助設備設置規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-007",107,"有一防火構造建築物，其探測區域樓地板面積為 100 平方公尺，欲設置差動式分布型熱電偶式探測器，至少應該設置多少探測器數量？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-007",106,"如設置救助袋做為避難器具，下列敘述何者錯誤？",1785123171374]