[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-011","fire-109-1-alarm-evacuation-011",109,1,11,"避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",{"A":16,"B":17,"C":18,"D":19},"2 平方公尺","3 平方公尺","4 平方公尺","6 平方公尺","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 160 條收容人員計算表中，百貨商場供飲食或休息用部分的計算基數。\n【正解理由】避難器具的種類與設置數量以收容人員為入口參數，第 160 條開宗明義規定「第一百五十七條表列收容人員之計算，依下表規定」，即各類場所各有其計算方式；百貨商場一類，除從業員工數外，供飲食或休息用之部分係以該部分樓地板面積除三平方公尺所得之數計入收容人員，故選 B。\n【逐項排除】\n(A) 2 平方公尺：不是該表對飲食或休息用部分所定之除數；表中零點二平方公尺係電影片映演場所等立位部分之基數，用途型態與停留密度都不同，不可互換。\n(B) 3 平方公尺：與第 160 條表列百貨商場供飲食或休息用部分的計算方式相符。\n(C) 4 平方公尺：該表對飲食或休息用部分之除數為三平方公尺，四平方公尺是作答時常見的誤記。\n(D) 6 平方公尺：同屬常被誤植之數值，表中對飲食或休息用部分並未採此除數。\n【記憶點】百貨商場裡吃飯、休息的區域，每三平方公尺算一人。","收容人員不是統計數字，而是法定推估值：第 160 條的開頭寫明它是「第一百五十七條表列收容人員之計算」，可見收容人員正是第 157 條避難器具設置基準表的入口參數，人數級距一跨，避難器具的應設具數就跟著跳動，所以命題者偏愛從除數下手。該表的體例是逐類場所給一組合計式，除數大小反映停留型態：電影片映演場所（戲院、電影院）、歌廳、集會堂、體育館、活動中心為從業員工數加各觀眾席部分之合計，其中設固定席位部分以座椅數計，連續式席位為該座椅正面寬度除零點四公尺所得之數（未滿一之零數不計），設立位部分以該部分樓地板面積除零點二平方公尺，其他部分則除零點五平方公尺；遊藝場所、電子遊戲場、資訊休閒場所為從業員工數加上遊樂用機械器具能供進行遊樂之人數。可以看出：站著看表演的密度最高（零點二平方公尺一人），一般席次周邊次之（零點五平方公尺一人），而坐下來用餐、休息會佔用桌椅與走道，密度最低，因此百貨商場的飲食或休息用部分放寬到三平方公尺一人。記憶時把「零點二、零點五、三」三個除數依人員密度由高到低排成一列，比死記各類場所名稱有效。相關考點連結：同一條文也常改問「未滿一之零數不計」這類進位規則，或與避難器具的設置個數合併計算；另須留意從業員工數在各類場所都是必計項目，與樓地板面積換算所得之數相加後才是收容人員。場所用途一旦改變，收容人員與應設設備會同時變動，因此第 13 條規定各類場所於增建、改建或變更用途時原則適用變更前之標準，但用途變更為甲類場所使用時，該變更後用途之消防安全設備適用變更後之標準，避難器具即屬該條第一款所列、一律適用新標準的設備之一。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-010","緩降機之設置應保有必要操作面積（不含避難器具所占面積），其相關規定下列何者正確？",10,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-012","有關緊急電源插座之設置規定，下列敘述何者正確？",12,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-009","有關避難方向指示燈裝設之敘述，下列何者錯誤？",9,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-013","無線電通信輔助設備設置之規定，下列敘述何者錯誤？",13,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-008","緊急照明燈在地面之水平面照度，使用低照度測定用光電管照度計測得之值，在地下建築物之地下通道，其地板面應在 X 勒克司（Lux）以上，其他場所應在 Y 勒克司（Lux）以上。其中 X， Y 值為何？",8,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-014","某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",14,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-011",110,"特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-011",108,"為提升火災發生時之通報效率，並避免延誤報案致生重大火災事故，各類場所消防安全設備設置標準於 107 年 10 月 17 日增列下列那一種設備種類？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-011",107,"依各類場所消防安全設備設置標準規定，火警受信總機、中繼器及偵煙式探測器，有設定蓄積時間時，其蓄積時間之合計，每一火警分區在多少秒以下？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-011",106,"Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",1785123171426]