[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-014","fire-109-1-alarm-evacuation-014",109,1,14,"某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",{"A":16,"B":17,"C":18,"D":19},"7","5","3","2","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 188 條排煙設備的防煙區劃面積上限與區劃數換算。\n【正解理由】第 188 條第一款規定，每層樓地板面積每五百平方公尺內應以防煙壁區劃；但書所排除者為戲院、電影院、歌廳、集會堂等場所之觀眾席，及工廠等類似建築物且天花板高度在五公尺以上並以耐燃一級材料裝修者，百貨商場五樓不屬之。該層二千一百平方公尺須切分為每一區劃不超過五百平方公尺，二千一百除以五百等於四點二，區劃數須無條件進位為整數，至少五個，故選 B。\n【逐項排除】\n(A) 7：以每三百平方公尺區劃所得之數，但三百平方公尺是同條第二款地下建築物地下通道的基準，本題為地上五樓，不適用。\n(B) 5：四點二進位後之最小整數，可使每一區劃均不超過五百平方公尺。\n(C) 3：三個區劃平均每區七百平方公尺，已逾五百平方公尺上限。\n(D) 2：兩個區劃平均每區一千零五十平方公尺，超出上限更多。\n【記憶點】一般樓層每五百平方公尺一區劃，地下建築物之地下通道加嚴為三百平方公尺。","第 188 條把排煙設備從區劃、排煙口、風管一路寫到排煙量，數值密集：防煙壁指以不燃材料建造、自天花板下垂五十公分以上之垂壁或具有同等以上阻止煙流動構造者，地下建築物之地下通道則應下垂八十公分以上；防煙區劃範圍內任一位置至排煙口之水平距離在三十公尺以下，排煙口設於天花板或其下方八十公分範圍內，排煙口設在天花板下方而防煙壁下垂高度未達八十公分時，排煙口應設在該防煙壁之下垂高度內；排煙設備之排煙口、風管及其他與煙接觸部分應使用不燃材料，風管貫穿防火區劃時應在貫穿處設防火閘門。排煙口之開口面積在防煙區劃面積之百分之二以上，且以自然方式直接排至戶外，無法自然排出時應設排煙機；排煙機隨任一排煙口開啟而動作，排煙量在每分鐘一百二十立方公尺以上，一防煙區劃時為該區劃面積每平方公尺每分鐘一立方公尺以上，二區以上時為最大防煙區劃面積每平方公尺每分鐘二立方公尺以上，地下建築物之地下通道總排煙量則在每分鐘六百立方公尺以上。操作面上，排煙口設手動開關裝置及探測器連動自動開關裝置，手動操作部分設於距樓地板面八十公分以上一百五十公分以下之牆面，裝置於天花板時設操作垂鍊或垂桿在距樓地板一百八十公分之位置；緊急電源供電容量應供有效動作三十分鐘以上；但排煙口直接面向戶外且常時開啟者，得不受手動開關裝置與緊急電源二款之限制，因為它本來就不必等人操作、也不必靠電力維持開啟。把「五百、三百、五十、八十、三十、百分之二、一百二十」這串數字綁在第 188 條一起記，可同時應付區劃數與排煙量兩類計算。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-013","無線電通信輔助設備設置之規定，下列敘述何者錯誤？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-015","有關排煙設備之設置規定，下列敘述何者錯誤？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-012","有關緊急電源插座之設置規定，下列敘述何者正確？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-016","防煙壁為自天花板下垂 X 公分以上之垂壁，但地下建築物之地下通道，防煙壁應自天花板下垂 Y 公分以上，其中 X、Y 分別為：",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-011","避難器具設置數量需衡酌場所之收容人數，依各類場所消防安全設備設置標準規定，百貨商場供飲食或休息用場所之收容人數計算，應以該部分樓地板面積除多少？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-017","一一九火災通報裝置之設置規定，下列敘述何者錯誤？",17,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-014",110,"對火警自動警報設備二信號式受信總機進行火災表示之性能檢查時，接到第 1 報火警信號但尚未接到第 2 報火警信號時，下列那二種裝置均不應動作？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-014",108,"緊急照明設備性能試驗之水平面照度測試，切換為緊急電源狀態亮燈，經過 A 分鐘後，使用 B 測試，確認緊急照明燈之照度有無達到法規所規定之值。請問前述 A、B 為何？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-014",107,"依各類場所消防安全設備設置標準規定，火警受信總機若為壁掛型，總機操作開關距離樓地板面之高度，應該為多少公尺範圍？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-014",106,"依各類場所消防安全設備檢修及申報作業基準規定，火警自動警報設備之受信總機前應確保多少公尺以上空間以進行檢查及操作使用？",1785123171464]