[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-017":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-017","fire-109-1-alarm-evacuation-017",109,1,17,"一一九火災通報裝置之設置規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"設置遠端啟動裝置時，應設有可與設置一一九火災通報裝置場所通話之設備","應設於值日室等經常有人之處所","手動啟動裝置之操作開關距離樓地板面之高度，在 0.8 公尺以上 1.5 公尺以下","裝置附近，應設置送、收話器，可與內線電話共用","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 145-1 條一一九火災通報裝置之設置規定，爭點在裝置附近之送、收話器與內線電話的關係。\n【正解理由】第 145-1 條第五款明定「裝置附近，應設置送、收話器，並與其他內線電話明確區分」，要求的是與內線電話明確區分，而非與內線電話共用；共用會使通報時線路遭占用或誤接，與條文文義正好相反，故選 D。\n【逐項排除】\n(A) 敘述正確，同條第三款明定設置遠端啟動裝置時，應設有可與設置一一九火災通報裝置場所通話之設備。\n(B) 敘述正確，同條第二款明定應設於值日室等經常有人之處所，設有防災中心時應設於該中心。\n(C) 敘述正確，同條第四款明定手動啟動裝置之操作開關距離樓地板面之高度，在零點八公尺以上一點五公尺以下。\n(D) 敘述錯誤，條文要求送、收話器與其他內線電話「明確區分」，不得共用，為本題應選者。\n【記憶點】一一九通報裝置的話機要獨立標明、不與內線電話混用；操作開關高度仍是 0.8～1.5 公尺這組通用數字。","一一九火災通報裝置列在第 9 條警報設備種類的第五款，與火警自動警報設備、手動報警設備、緊急廣播設備、瓦斯漏氣火警自動警報設備並列。其應設場所見第 22-1 條，限於第 12 條第一款第六目所定醫院、療養院、榮譽國民之家、長期照顧服務機構、老人福利機構、護理機構、身心障礙福利機構等場所，以及其他經中央主管機關公告之供公眾使用場所——這些都是臥床、失智或行動不便者集中的避難弱者場所，起火時工作人員須同時疏散住民，很難再撥號說明地址，故要求裝置能自動撥接一一九並播放預錄之場所資訊。第 145-1 條共六款：第一款應具手動及自動啟動功能；第二款設於值日室等經常有人之處所，有防災中心者設於該中心；第三款遠端啟動裝置須能與裝置場所通話；第四款操作開關高度零點八公尺以上一點五公尺以下；第五款送、收話器與其他內線電話明確區分；第六款應避免斜裝置並採取有效防震措施。其中「值日室等經常有人之處所，但設有防災中心時設於該中心」與「操作開關零點八公尺以上一點五公尺以下」是警報設備的共通體例，第 126 條火警受信總機、第 138 條緊急廣播設備擴音機及操作裝置、第 142 條瓦斯漏氣受信總機都是同一組規定，差別在受信總機與擴音機、瓦斯漏氣受信總機另有「座式操作者為零點六公尺」的例外，一一九火災通報裝置則無此括號。第 238 條規定防災中心應設防災監控系統綜合操作裝置，監控火警自動警報設備與瓦斯漏氣火警自動警報設備之受信總機、緊急廣播設備之擴音機及操作裝置等，可與本條互相對照記憶。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-016","防煙壁為自天花板下垂 X 公分以上之垂壁，但地下建築物之地下通道，防煙壁應自天花板下垂 Y 公分以上，其中 X、Y 分別為：",16,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-018","依住宅用火災警報器認可基準之規定，住宅用火災警報器以警報音發出火災警報，於無響室中距離警報器中心前方 1 公尺處，音壓應有多少分貝以上？",18,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-015","有關排煙設備之設置規定，下列敘述何者錯誤？",15,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-019","具閃滅或音聲引導功能之出口標示燈設置規定，下列敘述何者正確？",19,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-014","某百貨商場之 5 樓樓地板面積為 2,100 平方公尺，依各類場所消防安全設備設置標準規定，該層樓至少應設置幾個防煙區劃？",14,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-020","B 級出口標示燈且有顯示避難方向符號者，其有效距離係指步行至該燈多少公尺之距離？",20,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-017",110,"下列那二種避難器具在性能檢查時，均須對其下降空地附近之支持或固定裝置進行判定？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-017",108,"某商場有一樓層，以防煙垂壁區劃為四區，各區劃樓地板面積分別為 100 平方公尺、300 平方公尺、250 平方公尺、200 平方公尺，採用機械排煙方式，四區劃僅設置 1 台排煙風機，試問該排煙風機之排煙量每分鐘不得小於多少立方公尺？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-017",107,"供緩降機或救助袋使用之支固器具及供懸吊型梯、滑杆或避難繩索使用之固定架，若使用螺栓固定時，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-017",106,"檢查緩降機性能時，有關常溫下降試驗之判定中，緩降機最大下降速度應在多少以內？",1785123171491]