[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-025","fire-109-1-alarm-evacuation-025",109,1,25,"有關火焰式探測器之設置，下列何者與各類場所消防安全設備設置標準之規定不同？",{"A":16,"B":17,"C":18,"D":19},"裝設於天花板、樓板或牆壁","距樓地板面 1.2 公尺範圍內之空間，應在探測器標稱監視距離範圍內","探測器不得設在有障礙物妨礙探測火災發生處","探測器設在日光照射之處","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 124 條火焰式探測器之設置規定，關鍵在「日光照射」這個否定要件。\n【正解理由】第 124 條明定火焰式探測器依下列規定設置：裝設於天花板、樓板或牆壁；距樓地板面一點二公尺範圍內之空間，應在探測器標稱監視距離範圍內；探測器不得設在有障礙物妨礙探測火災發生處；探測器設在「無日光照射之處」，但設有遮光功能可避免探測障礙者，不在此限。火焰式探測器係感測火焰所放出之紫外線或紅外線輻射而動作，日光同樣含有這兩種波段，設於日光照射處易生誤報或使受光元件失效，故條文要求設在無日光照射之處。選項 D 把「無日光照射之處」寫成「日光照射之處」，與條文相反，即為與規定不同者，故選 D。\n【逐項排除】\n(A) 與第 124 條第一款「裝設於天花板、樓板或牆壁」逐字相符。\n(B) 與第二款「距樓地板面一點二公尺範圍內之空間，應在探測器標稱監視距離範圍內」相符，此款在界定人員活動高度須被監視涵蓋。\n(C) 與第三款「不得設在有障礙物妨礙探測火災發生處」相符，因火焰輻射直線傳遞，遭遮蔽即無法感知。\n(D) 條文為「設在無日光照射之處」並附遮光功能之但書，本項刪去「無」字而牴觸條文，為本題應選者。\n【記憶點】火焰式探測器怕光也怕擋：要無日光照射、要無障礙物遮蔽。","第 124 條的四款設置規定，等於把火焰式探測器的偵測原理直接寫成法定要件。火焰式探測器以紫外線式、紅外線式或紫外線紅外線併用式感知燃燒火焰放出之特定波段輻射，屬輻射感知型，與感熱式（差動式、定溫式、補償式）靠熱氣流上升、偵煙式靠煙粒子進入偵測室的動作機制完全不同。因為它感知的是直線傳遞的輻射能，所以第三款要求不得設在有障礙物妨礙探測火災發生處；第四款要求設在無日光照射之處，理由是日光的紫外線與紅外線會使受光元件飽和或誤動作，但條文另設但書，設有遮光功能可避免探測障礙者不在此限，命題者常把這個但書刪掉而寫成絕對禁止，需留意。\n第二款「距樓地板面一點二公尺範圍內之空間，應在探測器標稱監視距離範圍內」，是把人員站立、蹲伏活動的高度帶界定為應被監視的空間，並非要求探測器裝設在一點二公尺高度，這是最常被誤讀的一款。\n可一併對照第 115 條探測器之裝置位置：天花板上設有出風口時，除火焰式、差動式分布型及光電式分離型探測器外，應距離該出風口一點五公尺以上；局限型探測器之裝置不得傾斜四十五度以上，但火焰式探測器不在此限。火焰式在這兩處都享有豁免，正因它不倚賴熱氣流或煙的流動路徑。再對照第 123 條光電式分離型探測器，其第一款同樣要求受光面設在無日光照射之處，並要求設在天花板等高度二十公尺以下之場所、光軸長度在該探測器標稱監視距離以下、光軸與警戒區任一點之水平距離在七公尺以下。兩種探測器都「怕日光」，是本科成對出現的高頻考點。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-024","有關標示設備設在避難出口避難指標之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-026","有關緊急廣播設備配線之設置，除依屋內線路裝置規則外，下列何者與各類場所消防安全設備設置標準之規定不同？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-023","有關地下建築物總樓地板面積在幾平方公尺以上應設置無線電通信輔助設備，下列何者與各類場所消防安全設備設置標準之規定相同？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-027","有關緩降機支固器具之裝置，下列何者與各類場所消防安全設備設置標準之規定不同？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-022","有關使用瓦斯之場所供各類場所消防安全設備設置標準第 12 條第 5 款第 1 目使用之地下層，其樓地板面積合計 X 平方公尺以上，且其中甲類場所樓地板面積合計 Y 平方公尺以上者，應設置瓦斯漏氣火警自動警報設備，下列何者與該設置標準之規定相同？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-028","有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",28,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-025",110,"下列有關火警受信總機之裝置規定，何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-025",108,"依各類場所消防安全設備設置標準規定，火警自動警報設備之火警發信機（非定址式）與 P 型受信總機，其配線為何種配線？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-025",107,"有一飯店，其三樓之樓地板面積為 1200 平方公尺，依各類場所消防安全設備設置標準規定，於設置出口標示燈時，除應使用 A 級或 B 級外，出口標示燈標示面光度應在多少燭光（cd）以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-025",106,"依緊急照明燈認可基準規定，內置電池型緊急電源供電照明時間應維持 1.5 小時以上（供緊急照明燈總數）後，其蓄電池電壓不得小於蓄電池額定電壓多少百分比？",1785123171573]