[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-109-1-alarm-evacuation-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-警報與避難系統消防安全設備概要-031","fire-109-1-alarm-evacuation-031",109,1,31,"有關緊急照明設備性能檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"A":16,"B":17,"C":18,"D":19},"照度於地下建築物之地下通道，緊急照明燈在地面之水平面照度應達 10 勒克斯（lux）以上","緊急電源應無不亮燈或閃爍之情形","緊急電源容量應能持續 30 分鐘以上","建築物總樓地板面積 6,000 平方公尺以下，檢查緊急電源容量能否持續 30 分鐘之檢查數量為 20 個以上","D",null,[],false,"本題考點：《各類場所消防安全設備檢修及申報作業基準》緊急照明設備性能檢查之判定方法，以及檢查數量的級距表。\n【正解理由】依該基準緊急照明設備之性能檢查，照度判定為地下建築物之地下通道，緊急照明燈在地面之水平面照度應達十勒克斯以上，其他場所應達二勒克斯以上；緊急電源判定為應無不亮燈或閃爍之情形，且電源容量應能持續三十分鐘以上。注意事項另以級距表定檢查緊急電源容量之檢查數量：建築物總樓地板面積 1000 平方公尺以下為 5 個以上、3000 平方公尺以下為 10 個以上、6000 平方公尺以下為 15 個以上、10000 平方公尺以下為 20 個以上、超過 10000 平方公尺者為 20 個加上每增加 5000 平方公尺增加 5 個。6000 平方公尺以下對應者為 15 個以上，故選 D。\n【逐項排除】\n(A) 與照度判定「地下建築物之地下通道應達十勒克斯以上」相符。\n(B) 與緊急電源判定「應無不亮燈或閃爍之情形」相符。\n(C) 與緊急電源判定「電源容量應能持續三十分鐘以上」相符。\n(D) 6000 平方公尺以下之檢查數量為 15 個以上，本項寫 20 個以上，係誤用 10000 平方公尺以下之級距，為本題應選者。\n【記憶點】面積級距 1000／3000／6000／10000，依序對應 5／10／15／20 個。","緊急照明的照度標準在設置端與檢修端是一致的。《各類場所消防安全設備設置標準》第 178 條規定，緊急照明燈在地面之水平面照度，使用低照度測定用光電管照度計測得之值，在地下建築物之地下通道其地板面應在十勒克司以上，其他場所應在二勒克司以上，但在走廊曲折點處應增設緊急照明燈；檢修基準性能檢查之照度項目即以同一儀器、同一組數值判定。「地下通道十、其他二」是唯一要背的照度組合，五倍之差來自地下通道無自然採光、避難方向不易辨識。\n檢查數量的級距表必須整張記住，不可自行換算成比例：1000 平方公尺以下 5 個以上、3000 平方公尺以下 10 個以上、6000 平方公尺以下 15 個以上、10000 平方公尺以下 20 個以上，超過 10000 平方公尺者為 20 個再加上每增加 5000 平方公尺增加 5 個。若誤記成「每 1000 平方公尺抽若干個」的比例算法，在 3000 平方公尺這一級就會算錯。\n性能檢查的其他項目也常被拿來當選項素材：檢查開關應無變形、損傷或端子鬆動，切斷常用電源時應能自動切換至緊急電源並即時亮燈、復舊時亦能自動切換回常用電源；保險絲類應無損傷、熔斷，且為所定之種類及容量；結線接續應無斷線、端子鬆動、脫落、損傷之情形。與標示設備之性能檢查對照，兩者在檢查開關、保險絲類、結線與緊急電源四大項目上的體例幾乎相同，差別在於標示設備另有光源與信號裝置（閃滅、音聲引導、減光、消燈）項目，緊急照明設備則另有照度實測與三十分鐘容量之檢查數量規定。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-alarm-evacuation-030","有關緊急廣播設備標示燈外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準規定相同？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-alarm-evacuation-032","有關無線電通信輔助設備保護箱標示之外觀檢查的判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-alarm-evacuation-029","有關瓦斯漏氣火警自動警報設備檢知器外觀檢查選取之檢查數量，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-alarm-evacuation-033","有關緊急電源插座外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-alarm-evacuation-028","有關緊急廣播設備啟動裝置與緊急電話設置場所之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-alarm-evacuation-034","有關排煙設備綜合檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",34,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-alarm-evacuation-031",110,"一一九火災通報裝置，下列規定何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-031",108,"依各類場所消防安全設備設置標準對於出口標示燈設置之相關規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-031",107,"依各類場所消防安全設備設置標準規定，公共危險物品製造場所及一般處理場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-031",106,"在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",1785123171633]