[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-fire-law-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-消防法規概要-026","fire-109-1-fire-law-026",109,1,26,"原有照護思覺失調患者的康復之家想增設自動滅火設備，如採用小區劃型撒水頭（以第一種感度為限），依各類場所消防安全設備設置標準，其撒水頭間距要在多少公尺以上？",{"A":16,"B":17,"C":18,"D":19},"2","3","4","5","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 46 條第 1 項第 3 款小區劃型撒水頭之配置要件，特別是撒水頭間距之下限。\n【正解理由】康復之家屬住宿型精神復健機構，即第 46 條第 1 項第 3 款所引第 12 條第 2 款第 7 目之場所。依該款，此類場所之住宿居室、病房及其他類似處所，得採用小區劃型撒水頭（以第一種感度為限），任一點至撒水頭之水平距離在二點六公尺以下，撒水頭間距在三公尺以上，且任一撒水頭之防護面積在十三平方公尺以下。條文對間距明定為「三公尺以上」，故選 B。\n【逐項排除】\n(A) 2：二公尺低於該款所定間距下限；二點一與二點三公尺是同條第 2 款一般反應型與快速反應型撒水頭「水平距離」之上限，屬另一種尺度，不可與間距混用。\n(B) 3：即該款明定之間距下限，與題目所問「間距要在多少公尺以上」完全對應，為本題應選者。\n(C) 4：四公尺見於同條第 2 項高架儲存倉庫貨架撒水頭「每四公尺高度至少設置一個」，是高度方向的規定，非本款間距。\n(D) 5：若以五公尺為門檻，將把條文本來允許的三公尺、四公尺配置排除在外，與「三公尺以上」之文義不符。\n【記憶點】小區劃型三要件：水平距離二點六以下、間距三公尺以上、防護面積十三平方公尺以下。","第 46 條第 1 項第 3 款把小區劃型撒水頭的適用場所限定在第 12 條第 1 款第 3 目、第 6 目、第 2 款第 7 目、第 5 款第 1 目等場所之住宿居室、病房及其他類似處所，康復之家即屬第 2 款第 7 目之住宿型精神復健機構，因此有適用餘地。該款三個要件互相牽制：水平距離二點六公尺以下管「不能太疏」，間距三公尺以上管「不能太密」，防護面積十三平方公尺以下則框住單顆撒水頭的責任範圍。看到「以上」就要警覺條文問的是下限，這是全條唯一以下限管制的配置數值。\n小區劃型的水力參數自成一套：第 50 條規定撒水頭放水量每分鐘應在八十公升以上、設於高架倉庫者一百十四公升以上，放水壓力在每平方公分一公斤或 0.1MPa 以上，但小區劃型撒水頭之放水量每分鐘五十公升以上即可；第 57 條第 3 款規定使用側壁型或小區劃型撒水頭時，十層以下樓層以八個、十一層以上樓層以十二個撒水頭繼續放水二十分鐘之水量核算水源；第 58 條第 3 款則規定幫浦出水量以核算之撒水頭數乘以每分鐘九十公升（高架儲存倉庫一百三十公升），使用小區劃型撒水頭者改乘每分鐘六十公升。防護面積小、放水量低，水源與幫浦出水量跟著降，是這組數字的內在邏輯。\n同款延伸的側壁型撒水頭見第 46 條第 1 項第 4 款：牆面二側至撒水頭之水平距離在一點八公尺以下、牆壁前方至撒水頭之水平距離在三點六公尺以下，同樣以第一種感度為限，適用於住宿居室及其走廊、通道與其類似場所，常與小區劃型併列命題。另可對照同條第 1 款：戲院、舞廳、集會堂等表演場所之舞臺及道具室、電影院之放映室或儲存易燃物品之倉庫，任一點至撒水頭之水平距離在一點七公尺以下，是全條最嚴的配置密度，與住宿型場所的思維恰成對照。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-fire-law-025","依各類場所消防安全設備設置標準之規定，面積 400 坪的知名餐廳，所設置滅火器核算之最低滅火效能值應為多少？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-fire-law-027","有一 500 平方公尺地下停車場，採水霧滅火設備，依各類場所消防安全設備設置標準，其水源容量應保持多少立方公尺以上？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-fire-law-024","依各類場所消防安全設備設置標準之規定，有一容納超過 300 人老人福利機構餐廳，其樓地板面積在多少平方公尺以上，廚房排油煙管及煙罩即應裝設簡易自動滅火裝置？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-fire-law-028","依各類場所消防安全設備設置標準，有關裝設瓦斯漏氣火警自動警報設備之規定，下列敘述何者錯誤？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-fire-law-023","依各類場所消防安全設備設置標準，有關一一九火災通報裝置設置之規定，下列敘述何者正確？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-fire-law-029","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，全閉揚程應為性能曲線上全揚程之多少以下？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-026",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，液化石油氣備用量，供營業使用者，不得超過 X 公斤；供家庭使用者，不得超過 Y 公斤，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-026",110,"依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-026",108,"依防火牆及防火水幕設置基準規定，若防火水幕之防護高度為 12 公尺，請問其每公尺水幕長度放水量應在每分鐘多少公升以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-026",107,"公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法所稱高閃火點物品，指閃火點在攝氏 X 度以上之第 Y 類公共危險物品，X、Y 分別為多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-026",106,"下列有關防火水幕設備之水源容量規定之敘述，何者錯誤？",1785123158669]