[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-fire-law-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-消防法規概要-036","fire-109-1-fire-law-036",109,1,36,"依避難器具支固器具及固定部之結構、強度計算及施工方法之規定，裝置避難器具固定部材料，使用直徑 1 公分錨定螺栓，設定試驗荷重 500 公斤力（kgf）時，則鎖緊扭力應為多少公斤力\u002F公分（kgf\u002Fcm）？",{"A":16,"B":17,"C":18,"D":19},"100","120","140","160","B",null,[],false,"本題考點：避難器具固定部所用錨定螺栓,其鎖緊扭力與試驗荷重之換算。\n【正解理由】依《避難器具支固器具及固定部之結構、強度計算及施工方法》關於固定部錨定螺栓之規定,鎖緊扭力是由螺栓直徑與設定試驗荷重相乘後再乘上係數 0.24 求得,即 T＝0.24DN(T 為鎖緊扭力,D 為螺栓直徑,以公分計,N 為設定試驗荷重,以公斤力計)。本題螺栓直徑 1 公分、設定試驗荷重 500 公斤力,代入後得 120,故選 B。\n【逐項排除】\n(A) 100 相當於把係數誤取為 0.20,係數記錯即得此值,與規定之 0.24 不符。\n(B) 120 由 0.24×1×500 求得,與規定之計算式完全相符,為本題應選者。\n(C) 140 相當於係數誤取 0.28,或把直徑 1 公分誤讀為其他值後再回推,均非規定所定。\n(D) 160 相當於係數誤取 0.32,是四個選項中偏離最遠者;由於本式對直徑與荷重都是線性關係,係數一錯,整個答案就等比例偏掉。\n【演算步驟】公式:T＝0.24DN。代入:T＝0.24×1 公分×500 公斤力。結果:T＝120。驗算:若螺栓直徑改為 1.2 公分、荷重不變,則 T＝0.24×1.2×500＝144,可見結果與直徑成正比。\n【記憶點】鎖緊扭力＝0.24×直徑×試驗荷重,係數 0.24 是本式唯一要背的數。","避難器具的固定部是整組器具的受力根部,救助袋、緩降機在使用時所有荷重最後都壓在那幾支錨定螺栓上,因此法規把「材料」「埋入深度」「轉矩」三件事分層規範。材料層面,《各類場所消防安全設備設置標準》第 173 條規定,供緩降機或救助袋使用之支固器具,及供懸吊型梯、滑杆或避難繩索使用之固定架,應使用符合 CNS 2473、4435 規定或具有同等以上強度及耐久性之材料,並應施予耐腐蝕加工處理。安裝層面,第 174 條規定固定架或支固器具使用螺栓固定時,一、使用錨定螺栓;二、螺栓埋入混凝土內不含灰漿部分之深度及轉矩值,依表規定:M10×1.5 埋入深度 45 公厘以上、轉矩值 150 至 250;M12×1.75 埋入 60 公厘以上、300 至 450;M16×2 埋入 70 公厘以上、600 至 850(單位為 kgf-cm)。\n\n這裡要特別分辨兩種題型:第 174 條的表是「依螺紋標稱直接查表」得到一個轉矩區間,本題則是「依設定試驗荷重計算」得到一個特定值,兩者切入點不同。作答時先看題目給的是螺紋標稱(M10、M12、M16)還是試驗荷重與直徑——給標稱就查表,給荷重就套算式。\n\n檢修端也對得上。《各類場所消防安全設備檢修及申報作業基準》避難器具之性能檢查,在支固器具及固定部一項明定以目視、操作及扭力扳手確認,判定方法包括:支固器具應無變形、龜裂、腐蝕及損傷;螺栓、螺帽應無鬆動或脫落;固定部(木材、鋼筋、鋼骨混凝土等)應無腐蝕、生鏽、變形、龜裂等對強度有影響之異常;穿孔錨栓工法之錨栓所使用螺帽之栓緊,應符合表 18-6 之栓緊轉矩。該表所列數值與《設置標準》第 174 條完全一致,可見設置與檢修兩端用的是同一套。\n\n延伸考點:第 161 條規定避難器具應設在避難時易於接近處、與安全梯等避難逃生設施保持適當距離、開口部具安全構造、平時裝設或必要時能迅即裝設,且開口部上下層應交錯配置不得在同一垂直線上(滑杆、避難繩索及避難橋除外);第 170 條則規定救助袋支固器具應以螺栓、熔接或其他堅固方法裝置。這幾條常與扭力計算合併出成一整組題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-fire-law-035","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準之規定，裝設消防撒水幫浦，設計水量為 600 公升\u002F分，其設計揚程為 50 公尺；當揚水量在 900 公升\u002F分時，其揚程需調校在下列何標準值以上，方能判定合格？",35,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-fire-law-037","依建築技術規則建築設計施工編之定義，每層陽臺面積之和，以不超過建築面積多少為限？其未達 8 平方公尺者，得建築 8 平方公尺。",37,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-fire-law-034","依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，幫浦所消耗之動力，在額定出水量 150%時，其軸動力不得超過馬達額定輸出馬力之多少以下？",34,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-fire-law-038","依建築技術規則建築設計施工編之定義，經主管機關認可後，下列何者屬「防火設備」？",38,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-fire-law-033","依各類場所消防安全設備檢修及申報作業基準之規定，各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後多少日內，分別填具消防安全設備檢修申報表及檢附消防安全設備檢修報告書，向當地消防機關申報？",33,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-fire-law-039","依各類場所消防安全設備設置標準之規定，以防護區域每平方公尺每分鐘放水量來看，儲存可燃物場所設置放水型撒水頭是一般場所要求的幾倍？",39,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-036",111,"受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-fire-law-036",110,"依建築技術規則建築設計施工編規定，夾層係指夾於樓地板與天花板間之樓層；同一樓層內夾層面積之和，超過多少平方公尺，視為另一樓層？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-036",108,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，下列何者不符合呼水裝置之規定？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-036",107,"依防火牆及防火水幕設置基準之規定，防火水幕設備之水源應連結加壓送水裝置，下列敘述何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-036",106,"下列有關各類場所消防安全設備檢修及申報作業基準行政函釋之敘述，何者錯誤？",1785123158773]