[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-006":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-006","fire-109-1-water-chemical-006",109,1,6,"消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",{"A":16,"B":17,"C":18,"D":19},"15","20","25","32","A",null,[],false,"本題考點：消防幫浦「防止水溫上升用排放裝置」排放管之標稱口徑下限。\n【正解理由】幫浦在出水閥全閉之關閉運轉狀態下，馬達輸入功率幾乎全數轉為熱能蓄積於幫浦內部，故須自呼水管或幫浦出水側逆止閥一次側接出排放管，持續排放少量水以帶走熱量。候選之《各類場所消防安全設備檢修及申報作業基準》自動撒水設備性能檢查「配管」項，對此裝置只給判定方法：使加壓送水裝置啟動呈關閉運轉狀態，排放水量應在 q＝Ls×C／(60×Δt) 求得量以上（Ls 為幫浦關閉運轉時之出力 kw、C 為 860 kcal、Δt 為 30℃ 之幫浦內部水溫上昇限度），並未定口徑。標稱口徑之下限規定於《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》關於防止水溫上升用排放裝置之部分，為 15 毫米以上，故選 A。\n【逐項排除】\n(A) 15 毫米與該基準所定之標稱口徑下限相符，為正解。\n(B) 20 毫米非該裝置之規定值，口徑放大只是增加無謂之常時排水量。\n(C) 25 毫米是候選第 56 條末端查驗閥「管徑在二十五毫米以上」之數字，與本裝置無關。\n(D) 32 毫米同樣非規定值，屬一般配管常見口徑之誘答。\n【記憶點】防止水溫上升用排放裝置：口徑 15 毫米以上，水量看 q＝Ls×C／(60×Δt)。","呼水裝置與防止水溫上升用排放裝置常被放在同一題考，兩者處理的問題正好相反：呼水裝置解決幫浦位置高於水面時「吸不上水」，靠呼水槽、補給水管、減水警報裝置與底閥維持吸水管與幫浦內部滿水；排放裝置解決出水閥全閉時「水放不出去」造成的過熱。候選之檢修基準對呼水裝置的判定寫得很清楚：呼水槽水量減少時應能自動給水、水量減少至一半前應發出警報、底閥應無異物附著且呼水漏斗應能連續溢水，這幾個判定值與本題屬同一組考點。\n排放水量公式 q＝Ls×C／(60×Δt) 值得推導一次。Ls 是幫浦關閉運轉時之出力（kw），此時水未流出，軸功率幾乎全部轉為熱；C 取 860，是 1 kw-hr 相當於 860 kcal 的熱功當量；Δt 取 30℃，是幫浦內部容許之水溫上昇限度。把每小時發熱量 Ls×860 kcal 除以 60 化為每分鐘，再除以容許溫升 30℃，得到的就是每分鐘至少須排掉多少公升水。單位能夠對消，是因為 1 公升水升 1℃ 恰為 1 kcal，這也是公式看似跳躍卻成立的關鍵。\n同一「配管」項目除排放管外，還包含閥類與過濾裝置：閥類以手操作確認開、關動作是否容易進行，判定為開關操作應能容易進行；過濾裝置須分解打開確認過濾網有無變形、異物堆積，判定為應無變形、損傷、異物堆積等。乾式或預動式另有流水檢知裝置二次側配管之確認：關閉一次側制水閥後打開二次側排水閥，確認是否能適當排水，判定為二次側應無積水。這三項與排放管常混在同一題的選項裡，區辨方式是看檢查的是「開關順暢」「有無堆積」還是「水量足夠」。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-005","某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",5,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-007","下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",7,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-004","供集會堂使用之舞臺，應設置何種自動撒水設備？",4,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-008","預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",8,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-003","某建築物之室內、外消防栓、自動撒水及水霧滅火等設備配管採連通設計並共用消防幫浦，其共用消防幫浦之出水量和全揚程之要求標準為何？",3,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-009","進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",9,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-006",111,"消防幫浦之防止水溫上升用排放裝置，防止水溫上升用之排水管內之流水量，當幫浦在全閉狀態下連續運轉時，不使幫浦內部水溫，升高至攝氏多少度以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-006",110,"有關撒水頭位置裝置之規定，下列敘述何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-006",108,"使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-006",107,"泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-006",106,"全區放射二氧化碳滅火設備進行綜合檢查時，如為低壓式儲存系統，在放射試驗時需放射多少藥劑量？",1785123166970]