[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-008":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-008","fire-109-1-water-chemical-008",109,1,8,"預動式自動撒水設備竣工測試進行放水試驗時，開放末端查驗閥後，應在多久時間內正常放水？",{"A":16,"B":17,"C":18,"D":19},"20 秒","30 秒","60 秒","90 秒","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 55 條第三款，密閉乾式或預動式自動撒水設備自撒水頭動作至放水之時間上限。\n【正解理由】第 55 條第三款明定「撒水頭動作後，流水檢知裝置應在一分鐘內，使撒水頭放水」。乾式與預動式之流水檢知裝置二次側平時充填加壓空氣，撒水頭動作後必須先排氣，流水檢知裝置才會開啟讓水進入配管，因此法規容許一段排氣時間，但上限就是一分鐘。竣工測試以末端查驗閥模擬最遠支管撒水頭之動作，開放後應在 60 秒內正常放水，故選 C。\n【逐項排除】\n(A) 20 秒短於條文所定之一分鐘，並非法定判定值。\n(B) 30 秒亦非本款數值；第 55 條第一款所稱三十分鐘，是空氣壓縮機加壓達流水檢知裝置二次側設定壓力值之時間，兩者常被混為一談。\n(C) 60 秒即條文之「一分鐘內」，與規定完全相符，為正解。\n(D) 90 秒已逾條文所定上限，放水延遲將延誤初期滅火，不符規定。\n【記憶點】乾式、預動式二次側先排氣，撒水頭動作後「一分鐘內」放水。","密閉乾式與預動式的設計理由是防止凍結與水損：寒冷處所，或電腦室、圖書館等不能容忍誤放水之場所，二次側配管不充水而充加壓空氣。代價是放水延遲，所以第 55 條用四款把風險關回來——第一款要求空氣壓縮機為專用，並能在三十分鐘內加壓達流水檢知裝置二次側配管之設定壓力值；第二款要求二次側之減壓警報設於平時有人處，以便及早發現漏氣；第三款即本題的一分鐘內放水；第四款要求撒水頭使用向上型，但配管能採取有效措施者不在此限，用意是讓二次側殘水能排回，避免積水結冰或造成腐蝕。\n末端查驗閥是驗證這一分鐘的工具，規格見第 56 條：管徑在二十五毫米以上；依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端；一次側設壓力表，二次側設有與撒水頭同等放水性能之限流孔；距離地板面之高度在二點一公尺以下，並附有排水管裝置，標明末端查驗閥字樣。之所以挑「最遠、壓力最低」那一點，是因為該點合格則全系統合格。\n竣工加壓試驗另見第 45 條：自動撒水設備竣工時應做加壓試驗，密閉乾式管系應併行空氣壓試驗，空氣壓力達每平方公分二點八公斤（0.28MPa）之標準，壓力持續二十四小時，漏氣減壓量在每平方公分零點一公斤（0.01MPa）以下為合格。到了檢修階段，《各類場所消防安全設備檢修及申報作業基準》自動撒水設備綜合檢查則以末端查驗閥之放水壓力應在 1 kgf\u002Fcm² 以上 10 kgf\u002Fcm² 以下判定，並要求對加壓送水裝置最近及最遠之末端查驗閥各做放水試驗。竣工與檢修兩個階段的數值不同，是本科很典型的陷阱。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-007","下列何者非為消防機關辦理建築物消防安全設備審查及查驗作業基準規定，申請消防專用蓄水池查驗應檢附安裝施工測試佐證資料？",7,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-009","進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",9,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-006","消防幫浦設置呼水槽時，防止水溫上升用排放裝置之標稱口徑不得小於多少毫米？",6,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-010","全區放射方式之二氧化碳滅火設備，應設置從啟動裝置動作至二氧化碳放出時間至少多久的遲延裝置？",10,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-005","某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",5,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-011","乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",11,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-008",111,"固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-008",110,"消防搶救上之必要設備中，連結送水管之送水口設置，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-008",108,"移動式泡沫滅火設備之加壓送水裝置使用消防幫浦時，若同一樓層設 3 個泡沫消防栓箱時，其出水量應在每分鐘多少公升以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-008",107,"水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-008",106,"乾粉滅火設備進行性能檢查時，滅火藥劑檢查注意事項中，溫度超過Ｘ℃以上，濕度超過Ｙ%以上時，應暫停檢查，Ｘ及Ｙ分別為：",1785123166984]