[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-014":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-014","fire-109-1-water-chemical-014",109,1,14,"測量室內消防栓瞄子直線放水之壓力時，應將壓力表之進水口，放置於瞄子前端多少距離處，讀取壓力表的指示值？",{"A":16,"B":17,"C":18,"D":19},"相當於瞄子口徑的 1\u002F3 距離","相當於瞄子口徑的 1\u002F2 距離","相當於瞄子口徑的距離","相當於瞄子口徑的 2 倍距離","B",null,[],false,"本題考點：室內消防栓綜合檢查中，測定瞄子直線放水壓力時壓力表進水口之放置位置。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》室內消防栓設備之綜合檢查，檢查方法明定「測量瞄子直線放水之壓力時，將壓力表之進水口，放置於瞄子前端瞄子口徑的二分之一距離處，讀取壓力表的指示值」。取二分之一口徑處，是因為水柱離開瞄子後會先略為收縮再開始擴散，量測點太近會受管內靜壓影響、太遠則水柱破碎而讀值偏低，唯有此處量得之動壓才能代入放水量計算式，故選 B。\n【逐項排除】\n(A) 相當於瞄子口徑的 1／3 距離過近，讀值偏高，非該基準所定之位置。\n(B) 相當於瞄子口徑的 1／2 距離，與基準文字逐字相符，為正解。\n(C) 相當於瞄子口徑之全長距離，已偏離規定位置，讀值偏低。\n(D) 相當於瞄子口徑 2 倍距離更遠，水柱已明顯擴散，量得之壓力不具代表性。\n【記憶點】壓力表放在瞄子前端「口徑的二分之一」處，室內、室外消防栓與射水設備一致。","量測位置之所以要標準化，是因為它是放水量計算式的輸入值。基準所列公式為 Q＝0.653D²√P，Q 為瞄子放水量（l\u002Fmin）、D 為瞄子口徑（mm）、P 為瞄子壓力（kgf\u002Fcm²）。以第一種消防栓常用之 13 毫米瞄子、壓力 1.7 kgf\u002Fcm² 代入：0.653×13²＝0.653×169＝110.4；√1.7≈1.304；110.4×1.304≈144 l\u002Fmin，恰好高於基準所定第一種消防栓 130 l\u002Fmin 以上之判定值。量測點只要挪動一點，判定就可能翻盤，這是把位置寫死在基準裡的理由。\n判定值宜成組記憶：室內消防栓綜合檢查之放水壓力應在 1.7 kgf\u002Fcm² 以上 7 kgf\u002Fcm² 以下，但公共危險物品等場所達顯著滅火困難者所設第一種滅火設備之消防栓為 3.5 kgf\u002Fcm² 以上 7 kgf\u002Fcm² 以下；放水量第一種 130 l\u002Fmin 以上、第二種 80 l\u002Fmin 以上，公共危險物品等場所顯著滅火困難者為 260 l\u002Fmin 以上。室外消防栓為 2.5 kgf\u002Fcm² 以上 6 kgf\u002Fcm² 以下、350 l\u002Fmin 以上，公共危險物品等場所及爆竹煙火製造或儲存場所則提高為 3.5 kgf\u002Fcm² 以上、450 l\u002Fmin 以上。射水設備放水壓力 3.5 kgf\u002Fcm² 以上、每具 450 l\u002Fmin 以上；補助撒水栓為 2.5 kgf\u002Fcm² 以上 10 kgf\u002Fcm² 以下、60 l\u002Fmin 以上。\n測試點的選擇同樣有規則：室內消防栓於裝置消防栓最多之最高樓層做放水試驗，以該樓層全部消防栓放水為準，超過二支時以二支同時放水；室外消防栓選配管上最遠最高處之二具；射水設備超過二具時選最遠最高處之二具。挑最不利點驗證合格，全系統才算合格。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-013","乾粉滅火設備設置啟動用氣體容器時，其容器之內容積應有多少以上？",13,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-015","公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",15,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-012","消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",12,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-016","製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",16,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-011","乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",11,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-017","某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",17,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-014",111,"開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-014",110,"高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-014",108,"依各類場所消防安全設備設置標準之規定，加壓式乾粉滅火設備應設壓力調整裝置，可調整壓力至若干 MPa 以下？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-014",107,"二氧化碳滅火系統採全區放射方式高壓式系統，共設有 24 瓶儲存容器，進行綜合檢查時，放射試驗所需之藥劑量，應為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-014",106,"達顯著滅火困難之公共危險物品室外儲存場所，設置室外消防栓設備，其緊急電源應使用發電機設備或蓄電池設備，供電容量應供其有效動作至少多久以上？",1785123167060]