[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-019":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-019","fire-109-1-water-chemical-019",109,1,19,"某室內停車空間設置低發泡固定式泡沫滅火設備，每次檢修作業時，應選擇全部放射區域數多少比例以上之放射區域進行逐區放水試驗，測其放射分布及放射壓力？",{"A":16,"B":17,"C":18,"D":19},"10%","15%","20%","25%","C",null,[],false,"本題考點：固定式泡沫滅火設備（低發泡）綜合檢查，逐區放水試驗之放射區域抽測比例。\n【正解理由】依《各類場所消防安全設備檢修及申報作業基準》泡沫滅火設備綜合檢查之固定式泡沫滅火設備（低發泡），檢查方法明定「設置泡沫頭者，每次選擇全部放射區域數之 20％以上之放射區域，進行逐區放水試驗，測其放射分布及放射壓力」，並須於上述放射區域中距加壓送水裝置最遠者進行泡沫放射，測其發泡倍率及 25％還原時間，故選 C。\n【逐項排除】\n(A) 10％低於原文所定比例，抽測區域數不足，不符檢查方法之要求。\n(B) 15％同樣未達 20％門檻，屬自行折衷的數字，原文並未出現。\n(C) 20％與檢查方法「全部放射區域數之 20％以上」逐字相符，為應選者。\n(D) 25％是同一段落中「25％還原時間」所用的比例，指泡沫還原至全部泡沫水溶液量四分之一所需時間，屬性能測定項目而非抽測比例，兩個百分比同段出現正是本題陷阱。\n【記憶點】固定式低發泡泡沫：抽測區域「20％以上」，泡沫還原時間看「25％」。","抽測比例採「20％以上」而非全數，是在檢查可行性與代表性之間取得平衡：泡沫放射會耗用原液並造成場所污染，故以比例抽測，再指定「距加壓送水裝置最遠之放射區域」做泡沫放射，確保被驗的是壓力最不利點。判定方法分兩類，幫浦方式須確認啟動性能（加壓送水裝置應能確實啟動、表示與警報性能正常、電動機運轉電流在容許範圍內、運轉中無不規則不連續之雜音或異常震動發熱）、一齊開放閥應正常動作、放射分布及放射壓力應符合設計圖說、發泡倍率應在 5 倍以上、混合比率為設計時之稀釋容量濃度；重力水箱及壓力水箱方式則無啟動性能項目，改確認表示、警報等正常。\n設置端對照《各類場所消防安全設備設置標準》：第 70 條依膨脹比選放出口，膨脹比二十以下（低發泡）用泡沫噴頭或泡水噴頭，八十以上一千以下（高發泡）用高發泡放出口，膨脹比指泡沫發泡體積與發泡所需泡沫水溶液體積之比值；第 77 條規定泡沫噴頭方式之加壓送水裝置，出水量於泡沫放射區域有二區域以上時，以最大一個泡沫放射區域之最低出水量加倍計算，出水壓力須核算最末端一個泡沫放射區域全部泡沫噴頭放射壓力均達每平方公分一公斤以上或 0.1MPa 以上，並連接緊急電源；採泡沫消防栓箱者，同一樓層設一個時出水量每分鐘一百三十公升以上，設二個以上時每分鐘二百六十公升以上。\n室內停車空間的相關考點還有第 101 條：供室內停車空間使用之滅火藥劑，以第三種乾粉為限。停車空間可設泡沫或乾粉，命題常把兩套設備的數值並列互換，作答時先確認問的是哪一種設備。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-018","移動式泡沫滅火設備進行綜合檢查作業時，發泡倍率應在幾倍以上？",18,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-020","用於防護電氣設施之水霧滅火設備進行放水試驗時，最末端放射區域全部水霧噴頭之放水壓力均應能達到多少壓力以上？",20,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-017","某爆竹煙火儲存場所設置室外消防栓設備共 8 具，進行設備檢修綜合檢查時，至少應選擇配管上最遠最高處多少數量之室外消防栓實施放水試驗？",17,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-021","室內消防栓中之減水警報裝置，應於水量減至多少時發出警報？",21,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-016","製造年份超過 10 年之室內消防栓水帶進行耐水壓試驗時，施以 7 kgf\u002Fcm²以上水壓試驗多久時間，始得視為合格可繼續使用？",16,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-022","室內消防栓之箱面字樣，每字不得小於多少平方公分？",22,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-019",111,"下列有關滅火器性能檢查之敘述，何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-019",110,"依各類場所消防安全設備設置標準，應設置室內消防栓設備之場所，下列規定何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-019",108,"依各類場所消防安全設備檢修及申報作業基準，有關高壓式二氧化碳滅火藥劑儲存容器之滅火藥劑量檢查方法之注意事項中，鈷 60 有效使用年限約為多少年，如已超過時，應即時連絡專業單位處理或更換？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-019",107,"可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽之滅火器，每具滅火器對普通火災應具有 X 個以上之滅火效能值，對油類火災應具有 Y 個以上之滅火效能值，其中 X、Y 分別為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-019",106,"進行密閉濕式撒水設備綜合檢查時，末端查驗管之放水壓力應在那個範圍？",1785123167110]