[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-029":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-029","fire-109-1-water-chemical-029",109,1,29,"泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",{"A":16,"B":17,"C":18,"D":19},"水成膜泡沫液","酒精型泡沫液","蛋白質泡沫液","合成界面活性泡沫液","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 79 條泡沫原液與水混合使用之濃度，三種原液各對應哪些百分比。\n【正解理由】第 79 條明定：蛋白質泡沫液百分之三或百分之六；合成界面活性泡沫液百分之一或百分之三；水成膜泡沫液百分之三或百分之六。三款之中，唯一出現百分之一者為合成界面活性泡沫液，故選 D。\n【逐項排除】\n(A) 水成膜泡沫液：依第 79 條第三款為百分之三或百分之六，最低只到百分之三，不是本題所問的百分之一。\n(B) 酒精型泡沫液：第 79 條的濃度規定僅列蛋白質泡沫液、合成界面活性泡沫液、水成膜泡沫液三種，並未涵蓋酒精型泡沫液，該條既未給它任何濃度規格，自不能以之作為本題所問百分之一的答案。\n(C) 蛋白質泡沫液：依第 79 條第一款為百分之三或百分之六，與水成膜泡沫液的規格相同，同樣沒有百分之一這一檔，它靠的是厚實泡沫層覆蓋，原液比例本來就訂得較高。\n(D) 合成界面活性泡沫液：第 79 條第二款明定為百分之一或百分之三，是三種原液中唯一具備百分之一濃度者，為正確答案。\n【記憶點】三種原液濃度記「蛋白 3／6、水成膜 3／6、合成界面活性 1／3」——只有合成界面活性有百分之一。","第 79 條的三種濃度不是隨意訂的，而是對應各原液的發泡與滅火機制。蛋白質泡沫液以水解蛋白為基材，靠厚實且黏韌的泡沫層覆蓋油面、阻絕可燃蒸氣，需要較高的原液比例；水成膜泡沫液含氟界面活性劑，能在油面上鋪展出一層水膜封鎖油氣，濃度規格與蛋白質相同；合成界面活性泡沫液的界面活性效率最高，故可低至百分之一，也是三者中唯一具備百分之一規格者。濃度必須與放射量交叉記，兩者是兩張獨立的表：第 72 條第二款泡沫噴頭放射量表列蛋白質泡沫液樓地板面積每平方公尺六點五公升以上、合成界面活性泡沫液八公升以上、水成膜泡沫液三點七公升以上，可見濃度最低的合成界面活性反而放射量要求最高，不能用「濃度低就省水」的直覺互推。原液儲存量的算法在第 78 條：依第 76 條規定核算之水量與使用之泡沫原液濃度比核算，也就是水源先算完，再回頭乘濃度，順序不可顛倒。發泡型式方面，第 70 條以膨脹比分類並指定放出口，膨脹比二十以下為低發泡，選用泡沫噴頭或泡水噴頭；膨脹比八十以上一千以下為高發泡，選用高發泡放出口，且同條第二項界定膨脹比為泡沫發泡體積與發泡所需泡沫水溶液體積之比值。第 80 條第三款另規定移動式泡沫滅火設備之泡沫原液應使用低發泡。檢修端的對應是《各類場所消防安全設備檢修及申報作業基準》泡沫滅火設備之綜合檢查，於移動式泡沫滅火設備項下要求測定發泡倍率與二十五％還原時間，並利用糖度計法或比色計法測其混合比率，也就是把設計時的稀釋容量濃度實測回來核對，濃度規定與檢查方法在此接軌。另須留意第 218 條屬第四編公共危險物品等場所，雖然把泡沫原液濃度準用第 79 條，但其放射量與水源容量另有規定，不得整組搬到一般場所使用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-028","水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",28,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-030","泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",30,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-027","中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",27,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-031","使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",31,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-026","密閉式撒水頭之自動撒水設備末端查驗閥規定，下列何者錯誤？",26,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-032","二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",32,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-029",111,"變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-029",110,"公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-029",108,"有一室內停車空間，其防護區為 25 m × 16 m × 4 m，未設自動關閉裝置之開口部面積為 10 m2，擬設置全區放射式乾粉滅火設備，試問所需法定滅火藥劑量最少為多少公斤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-029",107,"全區放射二氧化碳滅火設備進行綜合檢查時，如為高壓式儲存系統，在放射試驗時需放射多少藥劑量？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-029",106,"10 型乾粉滅火器乾粉充填量約為多少公斤重？",1785123167207]