[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-031","fire-109-1-water-chemical-031",109,1,31,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"A":16,"B":17,"C":18,"D":19},"3","3.5","3.7","4.2","C",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 72 條泡沫頭放射量，其中泡沫噴頭依原液種類查表的那一格。\n【正解理由】第 72 條第二款泡沫噴頭放射量表列：蛋白質泡沫液樓地板面積每平方公尺六點五公升以上、合成界面活性泡沫液八公升以上、水成膜泡沫液三點七公升以上。題幹指定水成膜泡沫液，對應表列數值為每分鐘三點七公升，故選 C。\n【逐項排除】\n(A) 3：第 72 條表列只有六點五、八、三點七三格，並無三公升；三這個數字在泡沫規定中出現於第 79 條的濃度百分之三，是濃度不是放射量。\n(B) 3.5：三點五見於第 80 條第二款移動式泡沫滅火設備泡沫瞄子放射壓力每平方公分三點五公斤以上或 0.35MPa 以上，屬壓力而非放射量，兩者單位不同。\n(C) 3.7：與第 72 條第二款表中水成膜泡沫液「三點七以上」逐字相符，為正確答案。\n(D) 4.2：四點二見於第 105 條乾粉滅火設備蓄壓式配管壓力上限 4.2MPa，屬乾粉設備的壓力界線，與泡沫頭放射量無涉。\n【記憶點】泡沫噴頭放射量記「蛋白六點五、合成八、水成膜三點七」；泡水噴頭則固定每分鐘七十五公升。","第 72 條把泡沫頭分成兩類計量，這是最常被忽略的一點：第一款泡水噴頭放射量在每分鐘七十五公升以上，單位是「每個噴頭每分鐘幾公升」；第二款泡沫噴頭依原液種類查表，單位是「樓地板面積每平方公尺每分鐘幾公升」。前者算個數、後者算面積，代錯就整題偏掉。水成膜泡沫液之所以是表中最低的三點七，關鍵在含氟界面活性劑能在油面上鋪展成水膜、封鎖可燃蒸氣，效率高，不必靠厚泡沫層堆量；蛋白質泡沫靠泡沫層本身的機械強度與耐熱性覆蓋油面，需要六點五；合成界面活性泡沫液雖然依第 79 條原液濃度可低至百分之一，放射量反而要求八公升最高，可見濃度表與放射量表彼此獨立，不能互推。放射量的下一步是放射區域與水源：第 75 條規定使用泡沫噴頭時，每一放射區域在樓地板面積五十平方公尺以上一百平方公尺以下；使用泡水噴頭時，放射區域占其樓地板面積三分之一以上且至少二百平方公尺，但樓地板面積未達二百平方公尺者，放射區域依其實際樓地板面積計，這個但書是計算題的常見扣分點，只抄前半句就會把小面積場所算成二百平方公尺。第 76 條第一款再以依第 72 條核算之最低放射量，在最大一個泡沫放射區域繼續放射二十分鐘以上計算水量，第二項還要加算充滿配管所需之泡沫水溶液量與總量的百分之二十。因此完整的計算鏈是：查放射量表、定放射區域面積、乘二十分鐘、加配管量、再外加兩成，最後依第 78 條以濃度比回推原液儲存量。命題者在這一組條文上最愛做的變化有三種：一是換原液種類，考的其實是第 72 條的表；二是把泡水噴頭與泡沫噴頭對調，考的是單位；三是在放射區域上動手腳，把樓地板面積訂在二百平方公尺以下，考的是第 75 條第二款的但書。三種變化都能由同一條計算鏈拆解，先確定用哪一種噴頭，再決定放射量的單位是「每個」還是「每平方公尺」，最後才代入面積與時間，順序顛倒就容易在第一步就選錯數值。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-030","泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-032","二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-029","泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-033","加壓式乾粉滅火設備應設壓力調整裝置，其可調整壓力至每平方公分多少公斤以下？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-028","水霧滅火設備之放射區域有 2 區以上者，其主管管徑不得小於多少毫米？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-034","乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-031",110,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-031",108,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-031",107,"惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-031",106,"B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",1785123167225]