[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-109-1-water-chemical-032":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-032","fire-109-1-water-chemical-032",109,1,32,"二氧化碳滅火設備採用移動放射方式時，每一具噴射瞄子所需滅火藥劑量在多少公斤以上？",{"A":16,"B":17,"C":18,"D":19},"80","90","100","110","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》二氧化碳滅火設備採移動放射方式時，每一具噴射瞄子應備之滅火藥劑量。\n【正解理由】第 82 條第三款把移動放射方式界定為「皮管接頭至防護對象任一部分之水平距離在十五公尺以下」的放射型式；其藥劑量則規定於第 83 條二氧化碳滅火藥劑量，該條依全區、局部、移動三種放射方式分款計量，移動放射方式係以每一具噴射瞄子為單位，所需滅火藥劑量在九十公斤以上，故選 B。\n【逐項排除】\n(A) 80：八十在候選規定中對應的是第 50 條撒水頭每分鐘八十公升的放水量，屬水系統流量，與二氧化碳藥劑重量既非同一設備也非同一單位。\n(B) 90：即移動放射方式每一具噴射瞄子所需之滅火藥劑量，為正確答案。\n(C) 100：一百公升是第 80 條第一款移動式泡沫滅火設備同一樓層各泡沫瞄子每分鐘的放射量，屬泡沫水溶液流量，容易與二氧化碳藥劑量混為一談。\n(D) 110：二氧化碳滅火設備的藥劑量規定中並無一百一十公斤這一格，是把九十向上湊整的誘答。\n【記憶點】移動式二氧化碳三個數字：一具瞄子藥劑九十公斤、放射量每分鐘六十公斤（攝氏二十度）、皮管接頭至防護對象十五公尺以內。","二氧化碳滅火設備的三種放射方式在第 82 條一次界定完畢：全區放射方式，須以不燃材料建造之牆、柱、樓地板或天花板等區劃間隔，且開口部設有自動關閉裝置，但能有效補充開口部洩漏量者得免設；局部放射方式，視防護對象之形狀、構造、數量及性質配置噴頭；移動放射方式，皮管接頭至防護對象任一部分之水平距離在十五公尺以下。三種方式各有各的藥劑量算法，全部收在第 83 條。全區放射方式依用途與容積查表，電信機械室、總機室為每立方公尺一點二公斤且開口部每平方公尺追加十公斤，其他場所依容積級距為一點零、零點九、零點八、零點七五公斤，並附滅火藥劑之基本需要量五十、一百三十五、一千二百公斤；局部放射方式對可燃性固體或易燃性液體存放於上方開放式容器、燃燒限於一面且無向外飛散之虞者，依防護對象表面積每平方公尺十三公斤核算，防護對象邊長小於零點六公尺時以零點六公尺計，追加倍數高壓式一點四、低壓式一點一。移動式的其他要件在第 96 條：儲存容器之容器閥能在皮管出口處以手動開關、儲存容器分設於各皮管設置處、近旁設紅色標示燈並標明移動式二氧化碳滅火設備字樣、設於火災時濃煙不易籠罩之處所，且每一具瞄子之藥劑放射量在溫度攝氏二十度時應在每分鐘六十公斤以上，皮管、噴嘴及管盤並符合 CNS 一一一七七之規定。把九十公斤除以每分鐘六十公斤，可知單具瞄子的藥劑僅能支撐約一分半，這正說明移動式只適用於局限、規模不大且人員能安全接近的火災。另須留意第 222 條屬第四編公共危險物品等場所，全區放射方式另有一套依防護區域體積的藥劑量表（未達五立方公尺一點二公斤起算，一千五百立方公尺以上零點七五公斤），不得與第 83 條互相套用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-031","使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",31,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-033","加壓式乾粉滅火設備應設壓力調整裝置，其可調整壓力至每平方公分多少公斤以下？",33,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-030","泡沫滅火設備計算之水溶液量，應加算充滿配管所需之泡沫水溶液量，且應加算總泡沫水溶液量之百分之多少？",30,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-034","乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",34,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-029","泡沫原液與水混合使用之濃度，下列何種原液之濃度為 1%？",29,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-109-1-water-chemical-035","廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",35,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-032",111,"二氧化碳滅火設備屬於公共危險物品等場所的那一類滅火設備？",{"webId":58,"year":59,"stem":60,"number":13},"fire-110-1-water-chemical-032",110,"公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-032",108,"依法令規定下列場所何者應設置滅火器？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-032",107,"泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-032",106,"二氧化碳全區放射方式之安全裝置，啟動裝置開關或拉桿開始動作至儲存容器之容器閥開啟，設有多少秒以上之遲延裝置？",1785123167234]