[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-109-1-water-chemical-038":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-109-1-水與化學系統消防安全設備概要-038","fire-109-1-water-chemical-038",109,1,38,"消防專用蓄水池之設置規定，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"可與社區游泳池共用","有進水管投入後，能有效抽取所需水量之構造","其有效水量在 15 立方公尺以上","應設於消防車能接近至其 3 公尺範圍內易於抽取處","B",null,[],false,"本題考點：消防專用蓄水池設置規定的逐款比對，測驗有效水量、消防車接近距離與進水管投入構造三個要件。\n【正解理由】依《各類場所消防安全設備設置標準》第 185 條第一項第四款，消防專用蓄水池應「有進水管投入後，能有效抽取所需水量之構造」，選項文字與條文一致，故選 B。\n【逐項排除】\n(A) 第 185 條各款分別規範有效水量、水平距離、消防車接近距離、進水管投入構造及投入孔採水口，並無得與社區游泳池共用之規定；且該條第二項將有效水量限於蓄水池深度在基地地面下四點五公尺範圍內之水量，此敘述於條文中無據。\n(B) 與第 185 條第一項第四款逐字相符，為本題應選者。\n(C) 有效水量門檻寫錯，同條第一項第二款為「有效水量在二十立方公尺以上」，非 15 立方公尺。\n(D) 距離寫錯，同條第一項第三款為「設於消防車能接近至其二公尺範圍內，易於抽取處」，非 3 公尺。\n【記憶點】蓄水池三個數字：水平距離一百公尺、有效水量二十立方公尺、消防車接近二公尺。","本題四個選項其實是把第 185 條第一項第二款至第四款拆開重組，只改動數字，屬典型的數值辨識題。第二款「水平距離在一百公尺以下，且其有效水量在二十立方公尺以上」與第三款「設於消防車能接近至其二公尺範圍內，易於抽取處」是最常被改小或改大的兩處，第四款的進水管投入構造則因為沒有數字反而最少被動手腳，通常就是正解所在。\n二公尺這個數字在檢修階段也會再出現一次：《各類場所消防安全設備檢修及申報作業基準》消防專用蓄水池之外觀檢查，就進水管投入孔及採水口的周圍狀況，判定方法明定「消防車能到達二公尺以內，且使用上應無障礙」，並要求進水管投入孔標示消防專用蓄水池、採水口標示消防專用蓄水池採水口或採水口，標示應無損傷、脫落、污損；外形則須無變形、漏水、阻塞，投入孔蓋或採水口護蓋能確實開關。設置與檢修兩端數值一致，是記憶的好著力點。\n採機械方式引水者另有一套規定：依第 186 條，除準用前條有效水量規定外，任一採水口至建築物各部分之水平距離仍在一百公尺以下，並依水量級距配置加壓送水裝置與採水口——水量四十立方公尺未滿者出水量每分鐘一千一百公升、採水口一個；四十以上一百二十未滿者為每分鐘二千二百公升、二個；一百二十以上者為每分鐘三千三百公升、三個。其幫浦全揚程＝落差＋配管摩擦損失水頭＋15m，並應於採水口附近設啟動裝置及紅色啟動表示燈，採水口接裝六十三毫米陽式快接頭，距基地地面高度在一公尺以下零點五公尺以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-109-1-water-chemical-037","連結送水管之配管設置規定，應能承受送水設計壓力 1.5 倍以上之水壓，且能持續多少時間才合格？",37,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-109-1-water-chemical-039","公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",39,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-109-1-water-chemical-036","任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",36,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-109-1-water-chemical-040","儲槽規定設置補助泡沫消防栓時，下列敘述何者錯誤？",40,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-109-1-water-chemical-035","廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",35,{"webId":49,"stem":50,"number":12,"year":51,"session":12},"fire-110-1-water-chemical-001","公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",110,[53,57,60,64,68],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-038",111,"一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",{"webId":58,"year":51,"stem":59,"number":13},"fire-110-1-water-chemical-038","依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",{"webId":61,"year":62,"stem":63,"number":13},"fire-108-1-water-chemical-038",108,"依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",{"webId":65,"year":66,"stem":67,"number":13},"fire-107-1-water-chemical-038",107,"依各類場所消防安全設備設置標準之規定，下列何種場所不需設置室外消防栓設備？",{"webId":69,"year":70,"stem":71,"number":13},"fire-106-1-water-chemical-038",106,"乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",1785123167295]