[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-003":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-003","fire-110-1-alarm-evacuation-003",110,1,3,"建築物有某一樓層樓地板面積 900 平方公尺且設置之避難方向指示燈均為 C 級，該樓層最有可能為下列何種用途？",{"A":16,"B":17,"C":18,"D":19},"室內停車場","候船室","產後護理機構","KTV","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 146-5 條出口標示燈與避難方向指示燈應使用 A 級或 B 級之場所類型。\n【正解理由】第 146-5 條第一項規定非設於樓梯或坡道之避難方向指示燈設於該項各款場所時應使用 A 級或 B 級：第一款（第 12 條第二款第一目、第三款第三目、第五款第三目）與第三款（第 12 條第一款第六目）不論面積一律適用；第二款（第 12 條第一款第一目至第五目、第七目或第五款第一目）則以該層樓地板面積在一千平方公尺以上者為限。九百平方公尺仍得全面使用 C 級，只可能落在第二款且未達一千平方公尺之場所，故選 D。\n【逐項排除】\n(A) 室內停車場為第 12 條第三款第三目，落在第一款，不論面積均須 A 級或 B 級。\n(B) 候船室為第 12 條第二款第一目，同屬第一款場所，不因九百平方公尺而免除。\n(C) 產後護理機構屬第 12 條第一款第六目之護理機構，落在第三款，不論面積均須 A 級或 B 級。\n(D) KTV 為第 12 條第一款第一目之視聽歌唱場所，落在第二款，須該層樓地板面積一千平方公尺以上始須升級，本題九百平方公尺未達，得用 C 級，為本題應選者。\n【記憶點】九百平方公尺還能用 C 級，代表它是「滿一千平方公尺才升級」的第二款場所。","第 146-5 條把等級要求切成三種情境：第一項第一款（第 12 條第二款第一目之車站、飛機場大廈、候船室，第三款第三目之室內停車場與建築物依法附設之室內停車空間，第五款第三目之地下建築物）與第三款（第 12 條第一款第六目之醫院、長期照顧服務機構、老人福利機構、護理機構、身心障礙福利機構等）不論樓地板面積一律使用 A 級或 B 級；第二款（第 12 條第一款第一目至第五目、第七目或第五款第一目）則以該層樓地板面積在一千平方公尺以上為條件。光度要求並列於同項：出口標示燈標示面光度在二十燭光以上或具閃滅功能，避難方向指示燈標示面光度在二十五燭光以上，但設於走廊而其有效範圍內各部分容易識別該燈者不在此限。第一款第六目場所之出口標示燈另應採具閃滅功能或兼具音聲引導功能，並依第二項設於主要出入口、與火警自動警報設備連動、由主要出入口往避難方向所設探測器動作時停止閃滅及音聲引導；第三項則定避難方向指示燈設於樓梯或坡道者，樓梯級面或坡道表面照度應在一勒克司以上。電源面見第 155 條：緊急電源使用蓄電池設備，容量能有效動作二十分鐘以上；設於總樓地板面積五萬平方公尺以上、高層建築物總樓地板面積三萬平方公尺以上、地下建築物總樓地板面積一千平方公尺以上者之主要避難路徑時，容量在六十分鐘以上，並得採蓄電池設備與緊急發電機併設。配線則依第 156 條，蓄電池設備集中設置時直接連接於分路配線，不得裝置插座或開關。",true,[28,32,36,39,43,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-002","某樓高 12 層觀光旅館於最高樓層開設之餐廳，依各類場所消防安全設備設置標準之規定，其位於同樓層的廚房無須設置下列何種裝置？",2,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-004","有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",4,{"webId":37,"stem":38,"number":12,"year":11,"session":12},"fire-110-1-alarm-evacuation-001","下列有關建築物火警分區之劃定，何者符合各類場所消防安全設備設置標準的規定？",{"webId":40,"stem":41,"number":42,"year":11,"session":12},"fire-110-1-alarm-evacuation-005","避難方向指示燈之認可作業中，其引導燈具不包括下列何種附加功能？",5,{"webId":44,"stem":45,"number":46,"year":47,"session":12},"fire-109-1-alarm-evacuation-040","有關火警自動警報設備受信總機周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",40,109,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-006","緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",6,[53,56,60,64],{"webId":54,"year":47,"stem":55,"number":13},"fire-109-1-alarm-evacuation-003","瓦斯對於空氣之比重大於 1 時，其瓦斯漏氣檢知器應設於距瓦斯燃燒器具水平距離多少公尺以內？",{"webId":57,"year":58,"stem":59,"number":13},"fire-108-1-alarm-evacuation-003",108,"用途為補習班，居室樓地板面積 300 平方公尺，採用有效通風方式檢討，其排煙口設於天花板下方 80 公分內，試問有效通風面積最少須要多少平方公尺以上方可符合規定？",{"webId":61,"year":62,"stem":63,"number":13},"fire-107-1-alarm-evacuation-003",107,"下列何者非屬定溫式探測器可裝設場所？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-003",106,"裝設緊急廣播設備之建築物之規定，下列何者錯誤？",1785123170634]