[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-009","fire-110-1-alarm-evacuation-009",110,1,9,"瓦斯漏氣火警自動警報設備之性能試驗中，下列有關串接配線試驗之測試及判定，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"A":16,"B":17,"C":18,"D":19},"檢知器之配線應為輸送配線","火警分區數在 10 個以下時，試驗回路數為 1 個","火警分區數在 51 個以上時，試驗回路數為 3 個","受信總機之瓦斯漏氣表示應動作","D",null,[],false,"本題考點：串接（輸送）配線試驗所驗的是回路斷線之自動檢出，其判定為斷線表示，而非瓦斯漏氣表示。\n【正解理由】依《各類場所消防安全設備設置標準》第 144 條第二款，常開式檢知器信號回路之配線採用串接式並加設終端電阻，其目的逐字寫明係「以便藉由瓦斯漏氣受信總機作斷線自動檢出用」。串接配線試驗即據此使回路呈斷線狀態，判定受信總機能否作出斷線（故障）之表示；受信總機之瓦斯漏氣表示，須以加瓦斯試驗使檢知器動作才會動作，並非串接配線試驗之判定項目。故與消防安全設備測試報告書測試方法及判定要領規定不同者為 (D)，故選 D。\n【逐項排除】\n(A) 檢知器之配線應為輸送配線：輸送配線即串接式配線，與第 144 條第二款相符，非應選者。\n(B) 火警分區數在 10 個以下時，試驗回路數為 1 個：屬該要領就試驗回路數所定之分級抽測，與規定相符；候選條文未附該要領全文，本項僅引至要領層級。\n(C) 火警分區數在 51 個以上時，試驗回路數為 3 個：同屬前開分級抽測之最上一級，與規定相符。\n(D) 受信總機之瓦斯漏氣表示應動作：串接配線試驗之判定對象為斷線自動檢出，與第 144 條第二款所定目的不符，為本題應選者。\n【記憶點】串接配線加終端電阻是為了抓斷線，試驗要看斷線表示，不是瓦斯漏氣表示。","瓦斯漏氣火警自動警報設備的配線規定集中在第 144 條三款：一、電源回路導線間及導線對大地間之絕緣電阻值，以直流五百伏特額定之絕緣電阻計測定，對地電壓在一百五十伏特以下者應在零點一ＭΩ以上、超過一百五十伏特者在零點二ＭΩ以上，檢知器回路則每一警報分區在零點一ＭΩ以上；二、常開式檢知器信號回路之配線採用串接式並加設終端電阻，供受信總機作斷線自動檢出；三、檢知器回路不得與本設備以外之設備回路共用。對照第 127 條之火警自動警報設備配線，其測定用額定電壓為直流二百五十伏特，Ｐ型受信總機採數個分區共用一公用線時該公用線供應之分區數不得超過七個，探測器回路電阻在五十Ω以下——兩套配線規定分屬不同設備，數值不可互引。性能檢查面，檢修基準瓦斯漏氣火警自動警報設備章之檢知器檢查，使用加瓦斯試驗器（對空氣之比重未滿一者使用甲烷，大於一者使用異丁烷），並依表 15-2 按一回路之檢知器數量選取檢查數量（一至五個選一個、六至十個選二個，其後每五個遞增一個，三十個以上為百分之二十）；測得之時間扣除介入中繼器之五秒與採第三種測法之二十秒後，應在六十秒內。檢知區域警報裝置之音壓應在七十分貝以上，且音色有別於其他機械噪音。警報裝置部分，瓦斯漏氣表示燈判定應無明顯劣化且正常亮燈，動作之檢知器其所在位置應能容易辨識；檢知區域警報裝置之鳴動區域應適當，於檢知區域內任一點均能有效聽到。緊急電源依第 145 條，蓄電池設備應能使二回路有效動作十分鐘以上、其他回路監視十分鐘以上；設有本設備之建築物並依第 22 條應設置緊急廣播設備。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-008","下列何組感知線型或分布型探測器在進行外觀試驗時，均須判定其感熱元件之極性有無誤接？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-010","各型探測器在性能試驗中，下列有關其動作試驗的動作時間，何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-007","下列何種火警探測器在認可作業中須進行粉塵試驗？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-011","特別安全梯間與緊急昇降機間兼用之排煙室，如設置排煙管道及進風管道，下列何者在綜合試驗中應判定合格？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-006","緊急廣播設備在樓梯或斜坡通道以外之場所，其設置之揚聲器採性能設計時，在揚聲器標示上如加註下列那二種項目者，該廣播區域內任一點至揚聲器之水平距離方可不受到 10 公尺以下的限制？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-012","建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",12,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-109-1-alarm-evacuation-009",109,"有關避難方向指示燈裝設之敘述，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-009",108,"緩降機固定架或支固器具使用錨定螺栓固定時，選用螺紋標稱為 M12×1.75 之螺栓，試問其螺栓埋入混凝土內不含灰漿部分之深度（mm）及轉矩值須為多少（kgf-cm）？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-009",107,"以下有關各類場所消防安全設備設置標準對火警分區的規定，何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-009",106,"差動式分布型探測器為熱電偶式時，熱電偶應裝置在裝置面下方多少公分範圍內？",1785123170697]