[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-024","fire-110-1-alarm-evacuation-024",110,1,24,"差動式分布型探測器採熱電偶式時，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"熱電偶應裝置在裝置面下方 30 公分範圍內","裝接於一個檢出器之熱電偶數，在 25 個以下","面積 100 平方公尺之防火構造建築物，至少應裝置 5 個探測器","檢出器應設於便於檢修處，且與裝置面不得傾斜 5 度以上","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第一百二十一條第二款，差動式分布型探測器採熱電偶式時的裝置深度、應設探測器數與一個檢出器可接的熱電偶數。\n【正解理由】第一百二十一條第二款第三目明定「裝接於一個檢出器之熱電偶數，在二十個以下」，上限是二十個。(B) 寫成二十五個以下，已超出條文所定上限，本題問敘述錯誤者，故選 B。\n【逐項排除】\n(A) 同款第一目明定「熱電偶應裝置在裝置面下方三十公分範圍內」，敘述正確。\n(B) 條文所定上限為二十個，二十五個以下與之不符，為本題應選者。\n(C) 同款第二目表列：防火構造建築物在八十八平方公尺以下至少四個；超過八十八平方公尺者應設四個，每增加二十二平方公尺（包括未滿）增設一個。一百平方公尺超出八十八平方公尺十二平方公尺，未滿二十二平方公尺仍算一個，四個加一個為五個，敘述正確。\n(D) 依同條關於檢出器之規定，檢出器應設於便於檢修處，且與裝置面不得傾斜五度以上，敘述正確。\n【記憶點】熱電偶式四個數字：裝置面下方三十公分、防火構造八十八平方公尺起算四個、每增二十二平方公尺加一個、一個檢出器最多二十個熱電偶。","差動式分布型探測器偵測的是一整個面的溫升速率，第一百二十一條依感測元件分成三種型式，各有各的設置規定，是本條最常被混用的地方。第一款空氣管式：每一探測區域內之空氣管長度，露出部分在二十公尺以上；裝接於一個檢出器之空氣管長度在一百公尺以下；空氣管裝置在裝置面下方三十公分範圍內；空氣管裝置在自裝置面任一邊起一點五公尺以內之位置，其間距在防火構造建築物為九公尺以下，其他建築物為六公尺以下，但依探測區域規模及形狀能有效探測火災發生者不在此限。第二款熱電偶式：熱電偶裝置在裝置面下方三十公分範圍內；應設探測器數依表列，防火構造建築物八十八平方公尺以下至少四個，超過者應設四個並每增加二十二平方公尺（包括未滿）增設一個，其他建築物七十二平方公尺以下至少四個，超過者應設四個並每增加十八平方公尺（包括未滿）增設一個；裝接於一個檢出器之熱電偶數在二十個以下。第三款熱半導體式：探測器下端裝設在裝置面下方三十公分範圍內；各探測區域在每一有效探測範圍至少設置二個，但裝置面高度未滿八公尺時，在每一有效探測範圍至少設置一個。\n熱電偶式的個數計算務必用「級距＋增量」的體例，不能換算成每平方公尺幾個的比例式。以其他建築物一百平方公尺為例：一百減七十二為二十八平方公尺，二十八除以十八得一點五餘數，因為條文寫明「包括未滿」，不足十八平方公尺的部分仍要增設一個，故增設二個，合計四加二等於六個；若誤用比例式就會算錯。\n計數體例上，第一百二十條的差動式局限型、補償式局限型及定溫式局限型是另一套邏輯：先依探測器種類與裝置面高度查「有效探測範圍」（如差動式局限型一種，防火構造建築物未滿四公尺為九十平方公尺、四公尺以上未滿八公尺為四十五平方公尺），再以每一有效探測範圍至少設置一個推算個數。局限型查有效探測範圍、分布型熱電偶式查面積級距與增量，兩者的表要分開記，題目常把兩張表的數字互相對調。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-023","依各類場所消防安全設備設置標準，火警探測器之探測區域係指裝置面之四周以淨高 X 公分以上之樑或類似構造體區劃包圍者。偵煙式探測器，其裝置面之四周淨高應為 Y 公分，其中 X 及 Y 分別為：",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-025","下列有關火警受信總機之裝置規定，何者錯誤？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-022","有一地下 3 層、地上 7 層之建築物，各層樓地板面積為 600 平方公尺，若地下 1 樓發生火警，則火警自動警報設備之鳴動樓層，下列何者正確？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-026","對於單相交流 110 V 之緊急電源插座進行外觀及性能檢查時，下列何者與消防安全設備及必要檢修項目檢修基準之規定不同？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-021","下列有關免設火警探測器之場所，何者錯誤？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-027","依緊急廣播設備之揚聲器設置規定，廣播區域超過 100 平方公尺時，距揚聲器 1 公尺處所測得之音壓應為多少分貝以上？",27,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-109-1-alarm-evacuation-024",109,"有關標示設備設在避難出口避難指標之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-024",108,"某防火構造建築物，供三溫暖洗澡區使用，面積為 130 m2，天花板高度為 3.6 m，請問下列何者為適當的探測器？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-024",107,"P 型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，依各類場所消防安全設備設置標準規定，不得超過多少個？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-024",106,"依各類場所消防安全設備設置標準規定，特別安全梯或緊急昇降機間排煙室之排煙設備設置排煙、進風風管時，下列何者有誤？",1785123170858]