[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-110-1-alarm-evacuation-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-警報與避難系統消防安全設備概要-026","fire-110-1-alarm-evacuation-026",110,1,26,"對於單相交流 110 V 之緊急電源插座進行外觀及性能檢查時，下列何者與消防安全設備及必要檢修項目檢修基準之規定不同？",{"A":16,"B":17,"C":18,"D":19},"其回轉相位應量測為右向回轉","額定電流應為 15 A","其為接地型插座","其為三孔之插座","A",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》第二十三章緊急電源插座的外觀檢查與性能檢查項目，以及單相交流一百一十伏特插座的規格。\n【正解理由】依該章性能檢查「回轉相位」之檢查方法，係「連接額定電壓 220V 之三相交流緊急電源插座，如與電動機連接時，應以相位計確認其是否依規定方向回轉」，判定方法為「應為正回轉（右向回轉）」。可見回轉相位是三相交流二百二十伏特插座的檢查項目，單相交流一百一十伏特只有單一相位、無相序可判，並不列入其檢查項目。(A) 對單相插座要求量測右向回轉，與基準規定不同，故選 A。\n【逐項排除】\n(A) 回轉相位僅就三相交流二百二十伏特插座實施，單相一百一十伏特無此判定，與基準不同，為本題應選者。\n(B) 外觀檢查明定緊急電源插座為單相交流 110V 用者，依圖 23-1 所示（額定 150V，15A）之插座，額定電流十五安培與《各類場所消防安全設備設置標準》第一百九十一條第二款「交流單相一百一十伏特（或一百二十伏特）十五安培」相符。\n(C) 同一判定方法明定該插座為接地型，第一百九十一條第四款亦定緊急電源插座為接地型，敘述相符。\n(D) 接地型單相插座除兩個電源極外另有接地極，即圖 23-1 所示之三孔構造，敘述相符。\n【記憶點】單相 110V：十五安培、接地型三孔；回轉相位（右向回轉）是三相 220V 才有的檢查項目。","緊急電源插座是供消防人員在火場使用照明或破壞器材的電源，設計思路是「火場搶救時仍要有電」，這也決定了它的檢查重點。依第二十九條，應設緊急電源插座之場所有三：十一層以上建築物之各樓層、總樓地板面積在一千平方公尺以上之地下建築物、依建築技術規則應設置之緊急昇降機間。\n第一百九十一條把規格寫得很細：裝設於樓梯間或緊急昇降機間等（含各該處五公尺以內之場所）消防人員易於施行救火處，且每一層任何一處至插座之水平距離在五十公尺以下；電流供應容量為交流單相一百一十伏特（或一百二十伏特）十五安培，容量約為一點五瓩以上；為接地型，裝設高度距離樓地板一公尺以上一點五公尺以下，且裝設二個於崁裝式保護箱；保護箱長邊及短邊分別為二十五公分及二十公分以上，為厚度在一點六毫米以上之鋼板或具同等性能以上之不燃材料製，箱內有防止插頭脫落之Ｌ型或Ｃ型護鉤，箱蓋易於開閉並標示緊急電源插座字樣（每字在二平方公分以上），保護箱須接地，與室內消防栓箱等併設時須設於上方且箱蓋須能另外開啟；保護箱上方設紅色表示燈；應從主配電盤設專用回路，各層至少設二回路以上，每一回路之連接插座數在十個以下；專用回路不得設漏電斷路器；各插座設容量一百一十伏特、十五安培以上之無熔絲斷路器；並連接至緊急供電系統。其中「不得設漏電斷路器」與「連接至緊急供電系統」正是為了避免火場中因潑水漏電而跳脫斷電。\n檢修基準第二十三章則分成兩層：外觀檢查看保護箱周圍狀況與字樣、外形與箱門開關、插座（單相交流 110V 用者依圖 23-1 額定 150V、15A 之接地型；三相交流 220V 用則依圖 23-2 額定 250V、30A 之接地型）、開關器與表示燈；性能檢查則實際操作，確認插頭可輕易拔出及插入、開關器開關性能正常、以三用電表確認單相與三相之端子電壓是否為規定值，以及三相插座之回轉相位。單相與三相的規格與檢查項目各自成套，作答時先看題目給的是哪一種電源，再對應該套規定。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-alarm-evacuation-025","下列有關火警受信總機之裝置規定，何者錯誤？",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-alarm-evacuation-027","依緊急廣播設備之揚聲器設置規定，廣播區域超過 100 平方公尺時，距揚聲器 1 公尺處所測得之音壓應為多少分貝以上？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-alarm-evacuation-024","差動式分布型探測器採熱電偶式時，下列敘述何者錯誤？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-alarm-evacuation-028","瓦斯漏氣火警自動警報設備進行性能檢查時，檢知區域警報裝置其音壓在距 1 公尺處應為多少分貝以上？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-alarm-evacuation-023","依各類場所消防安全設備設置標準，火警探測器之探測區域係指裝置面之四周以淨高 X 公分以上之樑或類似構造體區劃包圍者。偵煙式探測器，其裝置面之四周淨高應為 Y 公分，其中 X 及 Y 分別為：",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-alarm-evacuation-029","有關瓦斯漏氣檢知器之設置，當瓦斯對空氣之比重小於 1 時，應設於距瓦斯燃燒器具水平距離 A 公尺以內；當瓦斯對空氣之比重大於 1 時，應設於距瓦斯燃燒器具水平距離 B 公尺以內，其中 A 及 B 分別為：",29,[53,57,61,65],{"webId":54,"year":55,"stem":56,"number":13},"fire-109-1-alarm-evacuation-026",109,"有關緊急廣播設備配線之設置，除依屋內線路裝置規則外，下列何者與各類場所消防安全設備設置標準之規定不同？",{"webId":58,"year":59,"stem":60,"number":13},"fire-108-1-alarm-evacuation-026",108,"依各類場所消防安全設備設置標準規定，裝置面高度 10 公尺者，不可選擇下列何種探測器設置？",{"webId":62,"year":63,"stem":64,"number":13},"fire-107-1-alarm-evacuation-026",107,"依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，有關電源回路之配線耐燃保護，若電線裝於金屬導線管槽內，並埋設於防火構造物之混凝土內，混凝土保護厚度應為多少毫米以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-106-1-alarm-evacuation-026",106,"樓梯或斜坡通道以外之場所，廣播區域之殘響時間在 3 秒以上時，揚聲器之裝設需符合 r = 3 \u002F 4 QSα\u002Fπ (1 −α) 之計算公式，S 的定義為何？",1785123170882]