[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-024","fire-110-1-fire-law-024",110,1,24,"依各類場所消防安全設備設置標準規定，有關連結送水管之送水設計壓力規定計算，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"送水設計壓力在下列計算值以上：送水設計壓力＝配管摩擦損失水頭＋消防水帶摩擦損失水頭＋落差＋放水壓力","消防水帶摩擦損失水頭為 4 公尺","立管水量，最上層與其直下層間為每分鐘 1200 公升，其他樓層為每分鐘 2400 公升","每一線瞄子支管之水量為每分鐘 130 公升","D",null,[],false,"本題考點：連結送水管送水設計壓力的計算要素與各項法定水量；題目問的是敘述錯誤者。\n【正解理由】依《各類場所消防安全設備設置標準》第 184 條第四款，「每一線瞄子支管之水量為每分鐘六百公升」。(D) 寫成每分鐘一百三十公升，該數值其實是第 34 條第一種室內消防栓的放水量，與本條規定不符，為敘述錯誤者，故選 D。\n【逐項排除】\n(A) 與第 184 條第一款「送水設計壓力＝配管摩擦損失水頭＋消防水帶摩擦損失水頭＋落差＋放水壓力」相同，敘述正確，非本題應選者。\n(B) 第 184 條第二款明定「消防水帶摩擦損失水頭為四公尺」，屬法定定值，敘述正確。\n(C) 第 184 條第三款規定立管水量「最上層與其直下層間為每分鐘一千二百公升，其他樓層為每分鐘二千四百公升」，敘述正確。\n(D) 瞄子支管水量應為每分鐘六百公升，本項誤植為一百三十公升，敘述錯誤，為本題應選者。\n【記憶點】連結送水管記 4 公尺、1200、2400、600；130 公升屬室內消防栓，別搬過來用。","送水設計壓力是連結送水管的核心參數。第 184 條第一款的算式 H＝h1＋h2＋h3＋60m 與第 183 條中繼幫浦全揚程算式同構，其中六十公尺是把最頂層所需放水壓力換算成水頭的固定值。第二款把消防水帶摩擦損失水頭直接定為四公尺，屬立法上的定值化，不必再依水帶長度逐次計算，這種法定定值最常被改成三公尺或五公尺當誘答。\n水量部分要整組記：立管在最上層與其直下層間為每分鐘一千二百公升，其他樓層為每分鐘二千四百公升，恰為兩倍關係；每一線瞄子支管為每分鐘六百公升；而第 183 條第二款的中繼幫浦出水量同為每分鐘二千四百公升，四個數字彼此對得起來，就不會被室內消防栓的一百三十公升混進來。\n各設備加壓送水裝置的附加常數也適合排成一張對照表：室內消防栓十七公尺（第 37 條）、室外消防栓二十五公尺（第 42 條）、自動撒水設備十公尺（第 58 條）、消防專用蓄水池採機械方式引水十五公尺（第 186 條）、連結送水管六十公尺（第 184 條）。這些常數反映各設備所需放水壓力的高低，連結送水管最高，因為要把水供到高層樓面的瞄子。配管另依第 181 條，立管管徑一百毫米以上，並能承受送水設計壓力一點五倍以上之水壓且持續三十分鐘；此外第 234 條明定，依本標準設置之室內消防栓、室外消防栓、自動撒水、水霧、泡沫、冷卻撒水、射水設備及連結送水管等設備，其消防幫浦、電動機、附屬裝置及配管摩擦損失計算由中央消防機關另定之，所以算式中的 h1、h2 並非隨意估算，而是另有技術規範可循。與本條最容易黏在一起的是第 183 條的中繼幫浦：一個講「消防車要送多大壓力進來」，一個講「大樓內部要再加多少揚程」，兩者共用六十公尺這個常數，但水量、水箱容量與串聯門檻各自獨立，作答時先辨明題目問的是送水設計壓力還是中繼幫浦。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-023","依各類場所消防安全設備設置標準規定，下列何者屬應設置室內消防栓設備的場所？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-025","某場所室內高度為 16 公尺，依各類場所消防安全設備設置標準規定，下列何者為可選擇之探測器種類？①定溫式特種 ②差動式分布型 ③光電式局限型一種 ④火焰式",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-022","依各類場所消防安全設備設置標準規定，避難器具於開口部與地面之間保有必要下降空間，下列敘述何者正確？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-026","依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-021","依各類場所消防安全設備設置標準規定，有關應設置自動撒水設備之場所，其撒水頭之位置規定，下列敘述何者正確？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-027","依各類場所消防安全設備設置標準規定，自動撒水設備得依實際情況需要選擇適當型式設置。但下列何種場所應設開放式？",27,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-024",111,"某室外儲槽場所儲槽儲存第四類公共危險物品，儲槽容量合計為 25 萬公秉，防液堤高度應在多少公尺以上？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-024",109,"依各類場所消防安全設備設置標準之規定，有一容納超過 300 人老人福利機構餐廳，其樓地板面積在多少平方公尺以上，廚房排油煙管及煙罩即應裝設簡易自動滅火裝置？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-024",108,"依消防法第 6 條及其相關規定，有關住宅用火災警報器下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-024",107,"消防法所稱消防防護計畫應包括之事項，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-024",106,"下列有關消防安全設備檢修專業機構管理辦法規定之敘述，何者錯誤？",1785123157977]