[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-026":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-026","fire-110-1-fire-law-026",110,1,26,"依各類場所消防安全設備設置標準規定，裝設火警自動警報設備之建築物，其火警分區劃定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"每一分區之任一邊長在 60 公尺以下。但裝設光電式分離型探測器時，其邊長得在 120 公尺以下","每一火警分區不得超過一樓層，並在樓地板面積 500 平方公尺以下","樓梯、斜坡通道、昇降機之昇降路及管道間等場所，在水平距離 60 公尺範圍內，且其頂層相差在二層以下時，得為一火警分區","樓梯或斜坡通道，垂直距離每 45 公尺以下為一火警分區。但其地下層部分應為另一火警分區","D",null,[],false,"本題考點：火警自動警報設備之火警分區如何劃定，考的是《各類場所消防安全設備設置標準》第一百十二條所列五款界限值。\n【正解理由】依《各類場所消防安全設備設置標準》第一百十二條第五款，「樓梯或斜坡通道，垂直距離每四十五公尺以下為一火警分區。但其地下層部分應為另一火警分區」，(D) 與條文逐字相符，故選 D。\n【逐項排除】\n(A) 錯在邊長。同條第二款明定每一分區之任一邊長在五十公尺以下，裝設光電式分離型探測器時邊長得在一百公尺以下，並非六十公尺與一百二十公尺。\n(B) 錯在面積門檻與但書被對調。第一款為每一火警分區不得超過一樓層，並在樓地板面積六百平方公尺以下；五百平方公尺是「上下二層樓地板面積之和」在該值以下時得二層共用一分區的例外條件。\n(C) 錯在水平距離。第四款所定樓梯、斜坡通道、昇降機之昇降路及管道間等場所，須在水平距離五十公尺範圍內且其頂層相差在二層以下，始得為一火警分區，非六十公尺。\n(D) 垂直距離四十五公尺與地下層另成一分區兩項要件均與第五款一致，為本題應選者。\n【記憶點】火警分區三個關鍵數：面積六百、邊長五十、垂直四十五，地下層永遠自成一區。","第一百十二條每一款其實都在回答同一個問題：受信總機亮起一個分區燈時，人要能迅速判斷火點落在多大的範圍內。面積上限六百平方公尺、任一邊長五十公尺，就是把「一個燈號」所對應的搜索範圍壓在合理值；同條第三款則給了放寬空間——如由主要出入口或直通樓梯出入口能直接觀察該樓層任一角落時，第一款規定之六百平方公尺得增為一千平方公尺，因為視線本身已取代了分區的定位功能。第二款對光電式分離型探測器把邊長放寬到一百公尺，理由在於該型探測器是以光軸做線型監視：依第一百二十三條，其受光面須設在無日光照射之處，受光器及送光器設在距背部牆壁一公尺範圍內，設於天花板等高度二十公尺以下之場所，光軸長度在標稱監視距離以下，光軸與警戒區任一點之水平距離在七公尺以下，其監視距離本就遠長於點型探測器。\n與緊急廣播設備的廣播分區可以併記：第一百三十四條規定每一廣播分區不得超過一樓層，室內安全梯或特別安全梯應垂直距離每四十五公尺單獨設定一廣播分區，安全梯或特別安全梯之地下層部分另設定一廣播分區——四十五公尺與地下層獨立這兩項要件，與火警分區第五款完全相同，一起背可省一半力氣。\n延伸考點落在受信總機端：第一百二十五條規定受信總機應具有火警區域表示裝置以指示火警發生之分區，附近並備有識別火警分區之圖面資料；裝置蓄積式探測器或中繼器之火警分區，該分區在受信總機不得有雙信號功能；受信總機、中繼器及偵煙式探測器有設定蓄積時間時，其合計每一火警分區在六十秒以下，使用其他探測器時在二十秒以下。配線面則見第一百二十七條：Ｐ型受信總機採數個分區共用一公用線方式配線時，該公用線供應之分區數不得超過七個，探測器回路電阻在五十Ω以下——「共用線七分區」也是同一組考點常見的延伸命題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-025","某場所室內高度為 16 公尺，依各類場所消防安全設備設置標準規定，下列何者為可選擇之探測器種類？①定溫式特種 ②差動式分布型 ③光電式局限型一種 ④火焰式",25,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-027","依各類場所消防安全設備設置標準規定，自動撒水設備得依實際情況需要選擇適當型式設置。但下列何種場所應設開放式？",27,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-024","依各類場所消防安全設備設置標準規定，有關連結送水管之送水設計壓力規定計算，下列敘述何者錯誤？",24,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-028","依各類場所消防安全設備設置標準規定，下列場所何者屬於乙類場所？",28,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-023","依各類場所消防安全設備設置標準規定，下列何者屬應設置室內消防栓設備的場所？",23,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-029","有一室外儲槽，其容量為 9000 公秉，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，設有防火水幕，下列敘述何者正確？",29,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-026",111,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，液化石油氣備用量，供營業使用者，不得超過 X 公斤；供家庭使用者，不得超過 Y 公斤，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-026",109,"原有照護思覺失調患者的康復之家想增設自動滅火設備，如採用小區劃型撒水頭（以第一種感度為限），依各類場所消防安全設備設置標準，其撒水頭間距要在多少公尺以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-026",108,"依防火牆及防火水幕設置基準規定，若防火水幕之防護高度為 12 公尺，請問其每公尺水幕長度放水量應在每分鐘多少公升以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-026",107,"公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法所稱高閃火點物品，指閃火點在攝氏 X 度以上之第 Y 類公共危險物品，X、Y 分別為多少？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-026",106,"下列有關防火水幕設備之水源容量規定之敘述，何者錯誤？",1785123158010]