[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-fire-law-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-消防法規概要-031","fire-110-1-fire-law-031",110,1,31,"有關標示設備之規定，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在 2 勒克司（lx）以上","觀眾席引導燈之照度，在觀眾席通道地面之水平面上測得之值，在 0.2 勒克司（lx）以上","避難指標設於出入口時，裝設高度距樓地板面 1 公尺以下","出口標示燈及避難方向指示燈設置於 1500 平方公尺地下建築物之主要避難路徑，蓄電池容量應在 80 分鐘以上，並得採蓄電池設備及緊急發電機併設方式","B",null,[],false,"本題考點：標示設備之照度、裝設高度與緊急電源容量，四個選項的數值全部出自《各類場所消防安全設備設置標準》。\n【正解理由】依第一百四十六條之六，「觀眾席引導燈之照度，在觀眾席通道地面之水平面上測得之值，在零點二勒克司（lx）以上」，(B) 與條文逐字相符，故選 B。\n【逐項排除】\n(A) 錯在照度值。第一百四十六條之五第三項規定避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度應在一勒克司以上，不是二勒克司。\n(B) 與第一百四十六條之六相同；觀眾席通道本就是刻意保持昏暗的空間，引導燈只需微光即能辨識腳下，所以門檻訂得最低，為本題應選者。\n(C) 錯在裝設高度。第一百五十三條第一款規定避難指標設於出入口時，裝設高度距樓地板面一點五公尺以下，非一公尺。\n(D) 錯在分鐘數。第一百五十五條但書所列六十分鐘之場所包含「地下建築物，其總樓地板面積在一千平方公尺以上」，一千五百平方公尺之地下建築物主要避難路徑確實適用該但書，但容量是六十分鐘以上並得採併設方式，不是八十分鐘。\n【記憶點】照度由小到大：觀眾席引導燈零點二、樓梯避難方向指示燈一、緊急照明燈二（地下建築物之地下通道十）勒克司。","標示設備的四種器具見第十條：出口標示燈、避難方向指示燈、觀眾席引導燈、避難指標。第二十三條再定應設場所，其中觀眾席引導燈只有戲院、電影院、歌廳、集會堂及類似場所要設，避難指標則各類場所均應設置，但設有避難方向指示燈或出口標示燈時，在其有效範圍內得免設。\n光度與功能規定集中在第一百四十六條之五：出口標示燈及非設於樓梯或坡道之避難方向指示燈，設於該條所列場所時應使用Ａ級或Ｂ級，出口標示燈標示面光度應在二十燭光以上或具閃滅功能，避難方向指示燈標示面光度應在二十五燭光以上；供第十二條第一款第六目使用者，出口標示燈並應採具閃滅功能或兼具音聲引導功能，且須設於主要出入口、與火警自動警報設備連動，並在由主要出入口往避難方向所設探測器動作時停止閃滅及音聲引導。第一百四十六條之七則規定出口標示燈及避難方向指示燈應保持不熄滅，只有在無人期間、可利用自然採光辨識出入口或避難方向期間、因使用型態特別需要較暗之處所於較暗期間、主要供管理權人或其雇用之人等固定使用之處所這四種情形，才得減光或消燈；設於樓梯或坡道者更嚴，只適用前兩種。\n緊急電源是本題最容易失分的地方：第一百五十五條規定出口標示燈及避難方向指示燈之緊急電源應使用蓄電池設備，容量能有效動作二十分鐘以上；但設於總樓地板面積五萬平方公尺以上、高層建築物總樓地板面積三萬平方公尺以上、地下建築物總樓地板面積一千平方公尺以上等場所之主要避難路徑者，容量應在六十分鐘以上，並得採蓄電池設備及緊急發電機併設方式。對照第一百七十七條，緊急照明設備之緊急電源為三十分鐘以上，採併設方式時分別為十分鐘及三十分鐘以上；第一百七十八條則規定緊急照明燈在地面之水平面照度，地下建築物之地下通道應在十勒克司以上，其他場所二勒克司以上，走廊曲折點處並應增設。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-fire-law-030","可燃性高壓氣體儲存場所防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，強度應能承受可能預料之氣體爆炸衝擊，有關混凝土空心磚製防爆牆之規定，下列敘述何者正確？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-fire-law-032","裝置避難器具之固定部（係指裝設避難器具之樑、柱、樓板等堅固構造或經補強之部分）直接裝置在建築物主要構造部之施工方法，若以金屬膨脹錨定螺栓之施工方法，金屬膨脹錨定螺栓間之間隔，應為埋入深度之幾倍以上？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-fire-law-029","有一室外儲槽，其容量為 9000 公秉，依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，設有防火水幕，下列敘述何者正確？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-fire-law-033","依消防安全設備及必要檢修項目檢修基準規定，有關固定式泡沫滅火設備（低發泡）綜合檢查之檢查方法，下列敘述何者正確？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-fire-law-028","依各類場所消防安全設備設置標準規定，下列場所何者屬於乙類場所？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-fire-law-034","依消防安全設備及必要檢修項目檢修基準規定，室內消防栓設備水帶製造年份超過 10 年應使用耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。X＋Y 為多少？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-fire-law-031",111,"依消防安全設備及必要檢修項目檢修基準規定，使用加熱試驗器分別對差動式局限型 1 種探測器及離子式局限型光電式局限型 2 種探測器加熱，確認其應動作之時間分別是 A 秒內及 B 秒內，A+B 為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-031",109,"依各類場所消防安全設備設置標準，有關泡沫原液儲存量、泡沫原液與水混合使用濃度之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-031",108,"依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-031",107,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-031",106,"下列有關消防法施行細則第 15 條自衛消防編組規定之敘述，何者正確？",1785123158062]