[{"data":1,"prerenderedAt":74},["ShallowReactive",2],{"q-fire-110-1-water-chemical-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":28,"sameNumber":53,"hasEssay":27},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":26,"indexable":27},"fire-110-1-水與化學系統消防安全設備概要-012","fire-110-1-water-chemical-012",110,1,12,"進行乾粉滅火設備性能檢查時，對於滅火藥劑檢查注意事項，溫度及濕度超過多少以上時，應暫停檢查？",{"A":16,"B":17,"C":18,"D":19},"溫度超過 30 ℃以上，濕度超過 70%以上","溫度超過 40 ℃以上，濕度超過 60%以上","溫度超過 50 ℃以上，濕度超過 50%以上","溫度超過 40 ℃以上，濕度超過 50%以上","B",null,[],false,"本題考點：乾粉滅火設備性能檢查中，滅火藥劑量檢查之環境限制，即溫度與濕度達何門檻應暫停檢查。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第八章乾粉滅火設備二、性能檢查（一）蓄壓式乾粉滅火藥劑儲存容器等之注意事項，明定「溫度超過 40℃以上，濕度超過 60％以上時，應暫停檢查」；同章加壓式乾粉滅火藥劑儲存容器之滅火藥劑量檢查，其注意事項載有完全相同之文字，兩處門檻一致，故選 B。\n【逐項排除】\n(A) 溫度 30 ℃、濕度 70%：溫度低於基準所載之 40 ℃，濕度高於所載之 60%，兩個數值均與原文不符。\n(B) 溫度 40 ℃、濕度 60%：與基準注意事項之文字逐字相符，為正解。\n(C) 溫度 50 ℃、濕度 50%：溫度與濕度同樣均與原文之 40 ℃、60% 不相符。\n(D) 溫度 40 ℃、濕度 50%：溫度部分與原文相符，但濕度原文為 60％，非 50％，屬只對一半的典型誘答。\n【記憶點】乾粉最怕受潮結塊，記「四十度、六十趴，超過就停手」。","這條注意事項的用意在乾粉的物性：藥劑量檢查須取下滅火藥劑充填蓋，自充填口測量藥劑高度或將容器置於台秤上測定重量，並取少量（約 300 ㏄）樣品確認有無變色或結塊，過程中藥劑必然與外氣接觸；環境高溫多濕時乾粉易受潮結塊，檢查行為本身即可能使藥劑變質，故基準以溫度、濕度雙門檻設下暫停條件。\n同一節的判定方法可一併記住：儲存所定之滅火藥劑應達規定量以上，並以顏色辨別種類——灰色為第四種乾粉、粉紅色為第三種乾粉、紫色系為第二種乾粉、白色或淡藍色為第一種乾粉；且不得有雜質、變質、固化等情形，以手輕握搓揉並自地面上高度五十公分處使其落下，應呈粉狀。蓄壓式者另須以釋壓閥將壓力洩放出，確認不得有殘壓，並確認壓力表指針有無歸零，歸零點之位置及指針動作應適當正常。\n加壓式者尚有加壓用氣體容器之氣體量判定：使用氮氣者，在溫度 35℃、0kgf／㎝² 狀態下，每 1 公斤乾粉滅火藥劑需氮氣 40 公升以上；使用二氧化碳者，每 1 公斤滅火藥劑需二氧化碳 20 公克以上，並加算清洗配管所需要量（20g／1 ㎏）以上，且應以另外之容器儲存。\n易混淆對照：蓄壓式與加壓式之別，在加壓氣體平時是否已充入藥劑容器。蓄壓式平時即為蓄壓狀態，故《各類場所消防安全設備設置標準》第 109 條規定蓄壓式乾粉滅火設備應設置以綠色表示使用壓力範圍之指示壓力表；加壓式則另備加壓用氣體容器，性能檢查項目因而多出放出閥、閥類、壓力調整器、連結管及集合管與定壓動作裝置等。",2,true,[29,33,37,41,45,49],{"webId":30,"stem":31,"number":32,"year":11,"session":12},"fire-110-1-water-chemical-011","室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",11,{"webId":34,"stem":35,"number":36,"year":11,"session":12},"fire-110-1-water-chemical-013","使用主成分為碳酸氫鈉之移動放射方式乾粉滅火設備，每一具噴射瞄子之每分鐘藥劑放射量應為下列何者？",13,{"webId":38,"stem":39,"number":40,"year":11,"session":12},"fire-110-1-water-chemical-010","實施泡沫噴頭外觀檢查，應進行之項目內容不包括下列那一項？",10,{"webId":42,"stem":43,"number":44,"year":11,"session":12},"fire-110-1-water-chemical-014","高壓電器設備其電壓在 7000 伏特以下時，水霧噴頭及配管與高壓電器設備應保持多少公分之標準離開距離？",14,{"webId":46,"stem":47,"number":48,"year":11,"session":12},"fire-110-1-water-chemical-009","依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",9,{"webId":50,"stem":51,"number":52,"year":11,"session":12},"fire-110-1-water-chemical-015","公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",15,[54,58,62,66,70],{"webId":55,"year":56,"stem":57,"number":13},"fire-111-1-water-chemical-012",111,"有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":59,"year":60,"stem":61,"number":13},"fire-109-1-water-chemical-012",109,"消防水系統設置呼水裝置時，其溢水用排水管口徑應在多少尺寸以上？",{"webId":63,"year":64,"stem":65,"number":13},"fire-108-1-water-chemical-012",108,"主成分為碳酸氫鉀及尿素化合物之乾粉滅火藥劑，採全區放射方式時，每立方公尺防護區域所需滅火藥劑量為多少公斤？",{"webId":67,"year":68,"stem":69,"number":13},"fire-107-1-water-chemical-012",107,"設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",{"webId":71,"year":72,"stem":73,"number":13},"fire-106-1-water-chemical-012",106,"簡易自動滅火設備進行性能檢查時，其蓄壓式滅火藥劑量應與標示重量差異在何範圍以內？",1785123166624]