[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-024","fire-110-1-water-chemical-024",110,1,24,"需設置自動撒水設備之場所中，下列何者應設開放式？",{"A":16,"B":17,"C":18,"D":19},"健身休閒中心（含提供指壓、三溫暖等設施之美容瘦身場所）","室內螢幕式高爾夫練習場","展覽場","集會堂使用之舞臺","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 43 條但書，哪些場所之自動撒水設備強制須採開放式。\n【正解理由】依《各類場所消防安全設備設置標準》第 43 條，自動撒水設備得依實際情況需要就密閉濕式、密閉乾式、開放式、預動式等擇一設置，「但供第十二條第一款第一目所列場所及第二目之集會堂使用之舞臺，應設開放式」。集會堂使用之舞臺正是但書後段逐字所列者，故選 D。\n【逐項排除】\n(A) 錯誤。健身休閒中心（含提供指壓、三溫暖等設施之美容瘦身場所）為第 12 條第一款第二目，但但書就第二目只及於「集會堂使用之舞臺」，不及於該目其他場所。\n(B) 錯誤。室內螢幕式高爾夫練習場同屬第 12 條第一款第二目，理由同 (A)，得依實際情況需要擇一型式，非強制開放式。\n(C) 錯誤。展覽場為第 12 條第一款第四目，不在但書所列的第一目與第二目之集會堂舞臺之內。\n(D) 正確。集會堂列於第 12 條第一款第二目，題目所指又是其舞臺，與第 43 條但書「第二目之集會堂使用之舞臺」完全相符。\n【記憶點】第 43 條但書只抓兩類：第一款第一目所列場所，以及第二目中「集會堂使用的舞臺」，第二目其他場所不算。","第 43 條列出自動撒水設備的五種型式：密閉濕式（平時管內貯滿高壓水，撒水頭動作時即撒水）、密閉乾式（平時管內貯滿高壓空氣，撒水頭動作時先排空氣，繼而撒水）、開放式（平時管內無水，啟動一齊開放閥，使水流入管系撒水）、預動式（平時管內貯滿低壓空氣，以感知裝置啟動流水檢知裝置，且撒水頭動作時即撒水），以及其他經中央主管機關認可者。原則是得依實際情況需要擇一設置，但書則把選擇權收回，對第 12 條第一款第一目所列場所及第二目之集會堂使用之舞臺強制採開放式。舞臺區布幕、道具與燈光線路集中，一旦起火即為面狀延燒，開放式以一齊開放閥使整個放水區域同時撒水，才追得上延燒速度，這是但書的著眼點。\n開放式一旦被要求，後續規定跟著綁定。第 54 條規定開放式自動撒水設備之放水區域：每一舞臺之放水區域在四個以下；放水區域在二個以上時，每一放水區域樓地板面積在一百平方公尺以上，且鄰接之放水區域相互重疊，使有效滅火。第 57 條第 2 款則規定水源容量：供第十二條第一款第一目使用場所及第二目集會堂之舞臺，在十層以下建築物之樓層時，應在最大放水區域全部撒水頭繼續放水二十分鐘之水量以上；在十一層以上建築物之樓層，則應在最大樓層全部撒水頭繼續放水二十分鐘之水量以上。三條合起來就是「型式、放水區域、水源容量」的完整鏈條，也是舞臺類考題最常見的串接方式。\n易混淆之處在於第 12 條第一款第二目同時收了保齡球館、撞球場、集會堂、健身休閒中心、室內螢幕式高爾夫練習場、遊藝場所、電子遊戲場、資訊休閒場所等，第 43 條但書只挑其中集會堂使用之舞臺，同目其他場所不受但書拘束。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-023","下列場所何者可選擇第二種室內消防栓選擇設置之？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-025","自動撒水設備之水源容量規定，若使用側壁型或小區劃型撒水頭時，十層以下樓層在 X 個撒水頭、十一層以上樓層在 Y 個撒水頭繼續放水 20 分鐘之水量以上。X、Y 分別為何？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-022","同一建築基地內有二棟以上建築物時，建築物間外牆與中心線水平距離第一層在 X 公尺以下，第二層在 Y 公尺以下，且合計各棟該第一層及第二層樓地板面積在 Z 平方公尺以上者，應設置消防專用蓄水池。X、Y、Z 分別為何？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-026","固定式泡沫滅火設備之泡沫放出口，若採用高發泡放出口，其泡沫膨脹比應選擇下列何者設置之？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-021","依各類場所消防安全設備設置標準，應就水霧、泡沫、乾粉、二氧化碳滅火設備等選擇設置之場所，下列場所何者得使用預動式自動撒水設備？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-027","二氧化碳滅火設備之全區放射或局部放射方式防護區域，對放射之滅火藥劑之排放規定，下列何者錯誤？",27,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-024",111,"十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-024",109,"室外消防栓設備之水帶箱設置，箱內應配置口徑 63 毫米及長多少公尺之水帶 2 條？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-024",108,"某一 15 樓層之建築物，其消防安全設備同時設有第一種室內消防栓及自動撒水設備，其屋頂水箱容量至少應為下列何者？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-024",107,"竣工查驗時，於屋頂使用口徑 16 mm 瞄子實施第一種室內消防栓綜合檢查，測得放水壓力為 4 kgf\u002Fcm2，所計算之每分鐘放水量約為：",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-024",106,"公共危險物品等場所設置移動式泡沫滅火設備時，其水源容量與放水量之規定，下列何者錯誤？",1785123166741]