[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-031","fire-110-1-water-chemical-031",110,1,31,"公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",{"A":16,"B":17,"C":18,"D":19},"3.5","6","7","16","D",null,[],false,"本題考點：公共危險物品等場所之室外消防栓設備採鑄鐵管配管時，CNS 832 壓力管路鑄鐵管的標稱壓力下限。\n【正解理由】依《各類場所消防安全設備設置標準》第二百十條第四款，「採用鑄鐵管配管時，使用符合 CNS 八三二規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分十六公斤以上或 1.6MPa 以上」，故選 D。\n【逐項排除】\n(A) 3.5：同條第六款規定全部室外消防栓同時使用時，各瞄子出水壓力在每平方公分三點五公斤以上或 0.35MPa 以上，屬放水壓力下限，不是配管的標稱壓力。\n(B) 6：同條第三款所定的「六」是室外消防栓口徑在六十三毫米以上，屬管件口徑；該條就標稱壓力並無每平方公分六公斤之規定。\n(C) 7：同條第二款規定室外消防栓瞄子放水壓力超過每平方公分七公斤或 0.7MPa 時，應採取有效之減壓措施，七公斤是啟動減壓措施的門檻壓力。\n(D) 16：與第 210 條第四款文字相符，且 16 kgf\u002Fcm² 即條文並列的 1.6MPa，為本題應選者。\n【記憶點】第 210 條的壓力數字各有歸屬：鑄鐵管標稱壓力 16、瞄子減壓門檻 7、瞄子出水壓力 3.5，單位皆為 kgf\u002Fcm²。","第 210 條是《設置標準》第四編中室外消防栓設備的總則性規定，全條可拆成「準用」與「自訂」兩層。準用層為第一款：配管、試壓、室外消防栓箱及有效水量之設置，準用第 39 條、第 40 條第三款至第五款、第 41 條第二項及第三項；第二款加壓送水裝置準用第 42 條，但室外消防栓瞄子放水壓力超過每平方公分七公斤或 0.7MPa 時，應採取有效之減壓措施。\n自訂層則是本題所在的數值群：第三款口徑在六十三毫米以上，與防護對象外圍或外牆各部分之水平距離在四十公尺以下，且設置二支以上；第四款採鑄鐵管配管者，使用符合 CNS 832 之壓力管路鑄鐵管或具同等以上強度者，標稱壓力在每平方公分十六公斤以上或 1.6MPa 以上；第五款配管埋設於地下時應採有效防腐蝕措施，但使用鑄鐵管者不在此限；第六款全部室外消防栓同時使用時，各瞄子出水壓力在每平方公分三點五公斤以上或 0.35MPa 以上、放水量在每分鐘四百五十公升以上，設置數量超過四支時以四支計算；第七款水源容量在全部室外消防栓繼續放水三十分鐘之水量以上，超過四支者同以四支計算；第二項緊急電源除準用第 38 條外，供電容量應供有效動作四十五分鐘以上。\n單位換算是本條的隱藏考點：條文一律「每平方公分 N 公斤」與「N×0.1MPa」並列，故 16 kgf\u002Fcm²＝1.6MPa、7 kgf\u002Fcm²＝0.7MPa、3.5 kgf\u002Fcm²＝0.35MPa。\n同一設備在檢修端另有判定值：《消防安全設備及必要檢修項目檢修基準》第三章室外消防栓設備性能檢查之減壓措施，判定放水壓力應在 2.5kgf／cm² 以上 6kgf／cm² 以下；但公共危險物品等場所達顯著滅火困難者、爆竹煙火製造場所有火藥區之作業區或庫存區及爆竹煙火儲存場所設置第一種滅火設備之室外消防栓，其放水壓力應在 3.5kgf／cm² 以上，兩層各有適用場所。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-030","公共危險物品等場所消防設計及消防安全設備，其他滅火困難場所，應設置第幾種滅火設備？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-032","公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-029","公共危險物品等場所消防設計及消防安全設備，設置第五種滅火設備者，公共危險物品每達管制量之幾倍（含未滿）應有一滅火效能值？",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-033","依消防安全設備及必要檢修項目檢修基準，滅火器設置間距規定，下列何者錯誤？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-028","消防專用蓄水池規定之有效水量，指蓄水池深度在基地地面下多少公尺範圍內之水量，但採機械方式引水時，不在此限？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-034","依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-031",111,"應設置消防專用蓄水池之場所規定，下列何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-031",109,"使用水成膜泡沫液時，樓地板面積每平方公尺之泡沫頭放射量為每分鐘多少公升以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-031",108,"第四種乾粉滅火藥劑儲存容器，有關充填比之規定，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-031",107,"惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-031",106,"B-30 乾粉滅火器可以滅火之油盤面積為多少平方公尺？",1785123166819]